Plan Review Notes
Plan Review Notes For Permit 10020416
Permit Number 10020416
Review Stop E
Sequence Number 1
Notes
Date Text
2010-02-25 08:58:51** DENIED **
  
  
 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2.( 2004
 FBC AS PERMITTED).
 THE WATTSTOPPER TS-400 DOES NOT MEET THE MAXIMUM TIME
 ALLOWED FOR OVER RIDE OR TIME ON. IT ALLOWS 12HRS OF
 TIME ON. THE SPECS ALSO STATE A MAXIMUM WATTAGE FOR
 THIS DEVICE WHICH IS MUCH LESS THAN THE LOAD SHOWN ON
 PLANS.
 THIS COULD BE REDLINED HOWEVER REVIEWS FROM OTHER
 TRADES ARE STILL NEEDED FOR SAME SHEET.
  
  
 2) NOTE: THE VALUE AS STATED FOR INCREASED SCOPE OF
 WORK IS LOW. PLEASE PROVIDE CONTRACT FOR NEW SCOPE.
 PLEASE SEE FBC 108.3 AS THE APPLIED VALUE IS TO INCLUDE
 DESIGN FEES, ALL LABOR, EQUIPMENT AND MATERIALS EVEN IF
 ANY OF THESE THINGS ARE OWNER SUPPLIED.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  