Plan Review Notes
Plan Review Notes For Permit 10020397
Permit Number 10020397
Review Stop E
Sequence Number 1
Notes
Date Text
2010-02-23 10:07:02** DENIED **
  
  
 1) NOTE: ELECTRICAL PLANS ARE OK AND WILL BE STAMPED
 HOWEVER BUILDING, FIRE MARSHAL, MECHANICAL AND PLUMBING
 REVIEW IS TO BE DONE FOR NIGHT-CLUB/DANCE OCCUPANCY AS
 SHOWN ON PLANS.
 ONCE ANY COMMENTS FROM THOSE TRADES ARE ADDRESSED
 ELECTRICAL WILL BE STAMPED AND REDLINED. SEE NOTE #2
 FOR REDLINED COMMENT.
 SEE CHAPTER 3 OF THE FBC FOR OCCUPANCY.
  
 2) NOTE: THE LIGHT FIXTURES WILL BE REQUIRED TO BE
 SPECIFIC TO THE TYPE OF FIXTURE, BULBS, WATTAGE ETC
 13-415.AB.5 FOR PRESCRIPTIVE REQUIREMENTS.
  
 3) NOTE: APPLIED VALUE FOR COMPLETE SCOPE OF WORK WAS
 NOT INCREASED ON REVISION. THE ORIGINAL SCOPE/PERMIT
 APPLICATION DID NOT INCLUDE NEW ELECTRICAL AND OTHER
 BUILD OUT ITEMS.
 PLEASE ADJUST VALUE. FBC 108.3
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  