Plan Review Notes
Plan Review Notes For Permit 10020397
Permit Number 10020397
Review Stop B
Sequence Number 1
Notes
Date Text
2010-02-24 15:19:13BUILDING PLAN REVIEW
 PERMIT: 09100379
 REVISION: 10020397
 ADD: 500 BELVEDERE SUITE 642
 CONT: QUAD M CONSTRUCTION
 TEL: (561)722-2303
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW REVISION
 ACTION: DENIED
  
 1) THE ELECTRICAL PLANS INDICATE A DANCE AREA AND
 NIGHTCLUB, PLEASE UPDATE THE ARCHITECTURAL SHEETS':
  
 A-1.0 PROPOSED FLOOR PLAN
  
 A-2.0 LIFE SAFETY PLAN AND PROPOSED OCCUPANT LOAD
 ISSUED PLANS INDICATE A OCCUPANCY OF 81.
  
 A-3.0 FURNATURE AND EGRESS PLANS.
  
 2) THE LAST KNOWN USE (OCCUPATIONAL LICENSE) MADE BEEN
 A RESTARAUNT (40 SEATS) AND BAKERY WWITH THE CHANGE OF
 OCCUPANCY TO A RESTARAUNT (A2) OCCUPANCY THIS ENACTED
 CHAPTER 9 OF THE EXISTING BUILDING CODE.
  
 2A) EXISTING BUILDING CODE: SECTION 904 FIRE PROTECTION
 904.1 GENERAL. FIRE PROTECTION REQUIREMENTS OF SECTION
 912 SHALL APPLY WHERE A BUILDING OR PORTIONS THEREOF
 UNDERGO A CHANGE OF OCCUPANCY CLASSIFICATION.
  
 EXISTING BUILDING CODE; 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING , SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2007 FBC- BUILDING. 903.2.1.2 GROUP A-2. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2
 OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS
 EXISTS:
 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2).
 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE.
 3. THE FIRE AREA IS LOCATED ON A FLOOR OTHER THAN THE
 LEVEL OF EXIT DISCHARGE.
 4. NIGHTCLUBS OR SIMILAR USAGE WHEN OCCUPANT LOAD IS
 100 OR MORE.
  
 3) EXISTING BUILDING CODE, SECTION 905 MEANS OF EGRESS
 905.1 GENERAL. MEANS OF EGRESS IN PORTIONS OF BUILDINGS
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH SECTION 912.
 912.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD
 CATEGORY. WHEN A CHANGE OF OCCUPANCY GROUP IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING .
  
  
 4) EXISTING BUILDING CODE, SECTION 906 ACCESSIBILITY
 906.1 GENERAL. ACCESSIBILITY IN PORTIONS OF BUILDINGS
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.
 912.8 ACCESSIBILITY. EXISTING BUILDINGS OR PORTIONS
 THEREOF THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
  
  
  
  
  
  