Plan Review Notes
Plan Review Notes For Permit 10020387
Permit Number 10020387
Review Stop E
Sequence Number 1
Notes
Date Text
2010-02-24 16:22:04 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS PER 106.1.1 FBC AS AMENDED.
  
 2} INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED
 UNDER. 2007 FBC, 2008 NEC ETC. ADD TO NOTES FOR CLARITY
 IN THE FIELD AND COMPLIANCE WITH 106.1.3 FBC AS
 AMENDED.
  
 3} AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF
 WORK PURPOSED. 105.1
  
 4} A SEPARATE PERMIT IS REQUIRED FOR LOW VOLTAGE AND
 THE CARD READER.106.3.5.1.2 FBC AS AMENDED. PROVIDE
 MANUFACTURERS SPECS FOR THE CARD READING EQUIPMENT.
  
 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 6} PLEASE LOCATE ALL SERVICE EQUIPMENT ON A SITE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 ALSO THE BOOTH LOCATION.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  