| Date |
Text |
| 2010-03-08 14:57:37 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | NFPA 99C 1999 |
| | |
| | 1. SHT 1 COMPRESSOR AIR INTAKE SHALL BE FROM OUTSIDE |
| | THE BUILDING WHEN PRACTICAL OR SHALL BE LOCATED WITHIN |
| | A ROOM WHERE NO CHEMICAL BASED MATERIAL IS STORED OR |
| | USED. THE COMPRESSOR IS SHOWN IN A WORKROOM WITH A |
| | WASHER AND DRYER. THIS IS NOT APPROVED. SECTION |
| | 4-5.1.1.3(E). PLEASE INDICATE WHERE THE AIR INTAKE FOR |
| | THE COMPRESSOR WILL BE FROM. |
| | |
| | 2. SHT 1 COMPRESSOR AIR INTAKE SHALL BE LOCATED WHERE |
| | NO CONTAMINATION FROM VACUUM SYSTEM DISCHARGES OR |
| | PARTICULATE MATER IS ANTICIPATED. THE COMPRESSOR AIR |
| | INTAKE SHALL BE TAKEN FROM A SPACE OTHER THAN AN |
| | OPERATORY AND OTHER THAN THE ROOM OR SPACE IN WHICH |
| | THERE IS AN OPEN OR SEMI-OPEN DISCHARGE FROM A LEVEL 3 |
| | VACUUM SYSTEM. [SEE 4-5.1.1.3.] |
| | |
| | 3. SHT 2 REVISION #9 VACUUM VENT TERMINATION OUT THE |
| | NORTH WALL IS NOT APPROVED PER SECTION 713.6. |
| | |
| | 4. SHT 3 LIQUIDS FROM A LEVEL 3 VACUUM SYSTEM, PER |
| | 4-5.2.2 SHALL BE DIRECTLY CONNECTED TO THE SANITARY |
| | DRAINAGE SYSTEM THROUGH AN APPROPRIATELY TRAPPED AND |
| | VENTED DRAIN. SECTION 4-5.2.1.3. - THE GAS SHALL BE |
| | DISCHARGED OUT-DOORS IN A MANNER THAT WILL MINIMUZE THE |
| | HAZARDS OF NOISE AND CONTAMINATION TO THE FACILITY AND |
| | TO THE ENVIRONMENT. SECTION 4-5.2.1.4. - THE EXHAUST |
| | SHALL BE LOCATED REMOTE FROM ANY DOOR, WINDOW, AIR |
| | INTAKE OR OTHER OPENINGS IN THE BUILDING WITH |
| | PARTICULAR ATTENTION GIVEN TO SEPARATE LEVELS OF INTAKE |
| | OR DISCHARGE. CARE SHALL BE EXERCISED TO AVOUD |
| | DISCHARGE LOCATIONS EONTRAINDICATED TO PREVAILING |
| | WINDS, ADJACENT BUILDINGS, TOPOGRAPHY OR OTHER |
| | ENFLUENCES. SECTION 4-5.2.1.5. |
| | |
| | 5. SHT 3 AIR/VACUUM RISER DENIED. NOTE STATES 2" PVC |
| | VENT TO NORTH EXTERIOR WALL MINIMUM 10' FROM O.A.I. OR |
| | EXTERIOR DOORS (ABOVE SPA #6 - SEE SHEET #2). PER |
| | SECTION 713.6 THE VENT SHALL RUN UP ABOVE THE ROOF. |
| | ALSO THE FUTURE VACUUM INDICATES 'DRAIN TO FLOOR DRAIN |
| | WHICH IS NOT APPROVED PER SECTION 4-5.2.1.3. |
| | |
| | 6. SHT 3 WATER RISER DIAGRAM. NOTE 1/2" TO VACUUM SEE |
| | AIR/VACUUM RISER THIS SHEET, BUT RISER SHOWS WATER TO |
| | THE COMPRESSOR NOT THE VACUUM. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 7. SHT 3 WATER RISER DIAGRAM SHOWS AN RP2 BELOW LAV 1. |
| | PLEASE INDICATE WHAT MAKE & MODEL AN RP2 IS ON THE |
| | PLUMBING FIXTURE SCHEDULE AND SUBMIT MANUF |
| | SPECIFICATIONS FOR THE RP2 TO DETERMINE IF A DRAIN IS |
| | REQUIRED. SECTION 106.1.2 (MORE INFORMATION REQUIRED). |
| | |
| | 8. SHT 3 WATER RISER DIAGRAM PLEASE INDICATE ON THE |
| | PLUMBING FIXTURE SCHEDULE WHAT TYPE OF FILTER THE WSF |
| | IS. INDICATE MAKE AND MODEL AND SUBMIT MANUF. |
| | SPECIFICATIONS FOR THE FILTER SHOWING COMPLIANCE WITH |
| | SECTIONS 611.1 OR 611.3. |
| | |
| | 9.SHT 3 WASTE RISER DIAGRAM. INDICATE ON THE PLUBMING |
| | FIXTURE SCHEDULE WHAT AN FSC IS. INDICATE MANUF. MAKE & |
| | MODEL. SECTION 106.1.2. |
| | |
| | 10. SHT 3 WASTE RISER DIAGRAM. FS AT FORMER HAIR SINKS |
| | TO BE CAPPED. NOTE 'A' INDICATES 6' BUT SECTION 704.5 |
| | PROHIBITS DEAD ENDS, (OVER 2 FEET). PLEASE ADJUST NOTE |
| | TO REFLECT CODE REQUIREMENTS. |
| | |
| | 11. SHTS SD1 & SD2 THE REQUIRED CLEAR FLOOR SPACE FOR |
| | THE ACCESSIBLE SHOWERS IS 36" BY 48". THIS IS NOT |
| | INDICATED. SEE FIGURE 29 IN CHAPTER 11 OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 12. THE PLAN/PERMIT REVISION FORM INDICATES THE |
| | INCREASE IN VALUE OF WORK AT ZERO. ALL NEW |
| | MATERIAL/LABOR & DESIGN FOR THE AIR/VACUUM SYSTEMS, |
| | WATER PIPING, FILTER, VALVES, SANITARY PIPING, TRAPS, |
| | FITTINGS SHALL BE INDICATED. PLEASE SHOW VALUATION FOR |
| | ALL REVISED WORK. |
| | |
| | 13. A SEPARATE MEDGAS PERMIT IS REQUIRED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |