Plan Review Notes
Plan Review Notes For Permit 10020362
Permit Number 10020362
Review Stop P
Sequence Number 1
Notes
Date Text
2010-02-24 16:18:30DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 BUILDING
 FBC-2007 CHAPTER 11
  
 1. PER TABLE 104.3 THREE DRINKING FOUNTAINS ARE
 REQUIRED. THE FLOOR PLAN SHOWS 1 DRINKING FOUNTAIN.
 PLEASE SHOW THE LOCATION OF THE OTHER 2 REQUIRED
 DRINKING FOUNTAINS. ALSO SEE SECTION 410.1.
  
 2. SHT A101 ROOM 117 SUBMIT A DETAIL FOR THE SHOWER
 SHOWING COMPLIANCE WITH SECTION 11-4.21 WITH ALL
 SUBSECTIONS.
  
 3. SHT A200 DETAILS 1, 3, 4, 7 & 9. THE CABINET DOORS
 ARE NOT ALLOWED IN THE "CLEAR FLOOR SPACE" REQUIRED FOR
 THE BREAKROOM/LOUNGE SINKS. SECTION 11-4.24.5. PLEASE
 DELETE FROM DETAILS.
  
 4. SHT P5.1 THE SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE HDCP LAV IN ROOM 116 AND THE BREAK
 ROOM SINK IN ROOM 115 ARE NOT SHOWN ON THE RISER
 DIAGRAM ONLY ONE URINAL IN ROOM 115 IS SHOWN ON THE
 RISER DIAGRAM. THE MOP SINK AND SINK IN SINK AREA 133
 SHALL NOT DISCHARGE THROUGH THE HORIZONTAL WET VENT FOR
 THE BATHROOM FIXTURES. SECTION 909.1. THE SINKS SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM FIXTURES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  