| Date |
Text |
| 2010-02-24 16:18:30 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 BUILDING |
| | FBC-2007 CHAPTER 11 |
| | |
| | 1. PER TABLE 104.3 THREE DRINKING FOUNTAINS ARE |
| | REQUIRED. THE FLOOR PLAN SHOWS 1 DRINKING FOUNTAIN. |
| | PLEASE SHOW THE LOCATION OF THE OTHER 2 REQUIRED |
| | DRINKING FOUNTAINS. ALSO SEE SECTION 410.1. |
| | |
| | 2. SHT A101 ROOM 117 SUBMIT A DETAIL FOR THE SHOWER |
| | SHOWING COMPLIANCE WITH SECTION 11-4.21 WITH ALL |
| | SUBSECTIONS. |
| | |
| | 3. SHT A200 DETAILS 1, 3, 4, 7 & 9. THE CABINET DOORS |
| | ARE NOT ALLOWED IN THE "CLEAR FLOOR SPACE" REQUIRED FOR |
| | THE BREAKROOM/LOUNGE SINKS. SECTION 11-4.24.5. PLEASE |
| | DELETE FROM DETAILS. |
| | |
| | 4. SHT P5.1 THE SANITARY ISOMETRIC RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| | REQUIREMENTS. THE HDCP LAV IN ROOM 116 AND THE BREAK |
| | ROOM SINK IN ROOM 115 ARE NOT SHOWN ON THE RISER |
| | DIAGRAM ONLY ONE URINAL IN ROOM 115 IS SHOWN ON THE |
| | RISER DIAGRAM. THE MOP SINK AND SINK IN SINK AREA 133 |
| | SHALL NOT DISCHARGE THROUGH THE HORIZONTAL WET VENT FOR |
| | THE BATHROOM FIXTURES. SECTION 909.1. THE SINKS SHALL |
| | DISCHARGE DOWNSTREAM OF THE BATHROOM FIXTURES. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |