| 2010-02-23 17:33:35 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. THERE ARE MULTIPLE FLEX RETURN AIR DUCTS WHICH ARE |
| | MISSING SIZES ON PAGES M2.1 AND M2.2. SHOW MISSING DUCT |
| | SIZES IN ACCORDANCE WITH FBC-M 603.1 AND FBC-M 601.4. |
| | |
| | 2. FLOOR PLAN ON M2.1 SHOWS FIRE DAMPER INSTALLED IN A |
| | WALL WHICH IS NOT SHOWN AS FIRE RATED ON ARCHITECTURAL |
| | OR LIFE SAFETY PLANS. FIRE DAMPERS SHALL BE INSTALLED |
| | IN RATED ASSEMBLIES PER FBC-M 607.2. |
| | |
| | 3. PAGE M2.2 KEY NOTE #7 REFERENCES PLUMBING DRAWINGS |
| | FOR CONDENSATE DISPOSAL AT AHU-1. PLUMBING PLANS SHOW |
| | NO CONDENSATE DISPOSAL SYSTEM FOR THIS AHU. SHOW MEANS |
| | AND LOCATION OF CONDENSATE DISPOSAL IN ACCORDANCE WITH |
| | FBC-M 307.2.1. |
| | |
| | 4. PAGE M6.1 RTU SCHEDULE NOTE #13 CALLS FOR AUX |
| | CONDENSATE CONTROL SYSTEM ON SECONDARY DRAIN. DOWNDRAFT |
| | UNITS SHALL HAVE AUXILIARY DRAIN PROTECTION INSTALLED |
| | IN THE PRIMARY DRAIN PAN IN ACCORDANCE WITH FBC-M |
| | 307.2.3.1. |
| | |
| | 5. SUPPLY FLEX SCHEDULE ON PAGE M6.1 PROVIDES FLEX |
| | SIZES FOR DUCTS STARTING AT 50-125 CFM. THERE ARE |
| | SUPPLY DUCTS PROVIDING FEWER THAN 50 CFM. PROVIDE THE |
| | INTENDED SIZE OF THESE SUPPLY FLEX DUCTS IN ACCORDANCE |
| | WITH FBC_M 603.1. |
| | |
| | 6. PAGE M7.1: MANUFACTURER AND INSTALLATION DETAIL FOR |
| | A/C STAND DOES NOT CORRESPOND WITH THE SUBMITTED |
| | PRODUCT APPROVAL. STAND INSTALLATION SHALL BE IN |
| | ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA PRODUCT |
| | APPROVAL. |
| | |
| | 7. PAGE M2.2: MEN'S RESTROOM 120 SHOWS 50 TOTAL CFM OF |
| | EXHAUST. FLOOR PLAN SHOWS A WATER CLOSET AND A URINAL |
| | IN THIS RESTROOM. MINIMUM 100 CFM OF EXHAUST IS |
| | REQUIRED IN THIS ROOM PER FBC-M TABLE 403.3 AND ASHRAE |
| | 62.1-2004 TABLE 6-4. |
| | |
| | 8. PROVIDE MANUFACTURER'S DATA SHOWING ALL OUTDOOR |
| | APPLIANCES AND EQUIPMENT, SUCH AS CONDENSERS, RTUS, |
| | FANS AND ROOF CAPS ARE DESIGNED FOR WIND RESISTANCE IN |
| | ACCORDANCE WITH FBC-M 301.12. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |
| | RONALD J. REGUEIRO |
| | 561.805.6719 |
| | [email protected] |