Plan Review Notes
Plan Review Notes For Permit 10020362
Permit Number 10020362
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-02-22 10:44:19*****DENIED*****
  
  
 1. WHAT IS ADDRESS FOR THIS PROJECT SITE LOCATION? BE
 ADVISED OF THE FOLLOWING ADDRESS DICREPANCIES:
 SUBMITTED APPLICATION (1701 OLD OKEECHOBEE ROAD), PLAN
 SHEETS CVR THRU A602 (1701 OLD OKEECHOBEE ROAD, SUITE
 1727, PLAN SHEETS M0.1 THRU FS2.2 (1727 OLD OKEECHOBEE
 ROAD)
  
 2. PLEASE EXPLAINE THE DIFFERENCES IN THE SQARE FOOTAGE
 IN THE SCOPE OF WORK SECTION COMPARED TO THE CODE
 RESEARCH SECTION AS LISTED ON THE CVR SHEET.
  
 3. STRUCTURES UNDERGOING CONSTRUCTION, ALATERATION, OR
 DEMOLITIONS OPERATIONS SHALL COMPLY WITH NFPA 241 -
 2004 EDITION.
  
 4. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 5. NO DOOR OPENING SHOWN FOR DOOR #24 ON A101 SHEET.
  
 6. ON SHEET A131 IN THE LOWERE LEFT CORNER OF THE
 DIAGRAM, IT APPEARS THAT THE PATH OF TRAVEL FOR THE
 TRAVEL DISTANCE PASSES THROUGH A WALL. PLEASE EXPLAIN.
  
 7. PROPERLY LIST THE PORTABLE FIRE EXTINGUISHERS AS
 2A10BC INSTEAD OF 2A100BC AS LISTED ON A131 & A132
 SHEETS.
  
 8. ON SHEET FA0.1, AMEND FIRE ALARM NOTE #17 TO REFLECT
 THAT DUCT SMOKE DETECTORS IATE A GENERAL FIRE ALARM (AS
 PER LOCAL CODES) .
  
 9. IT IS LISTED ON SHEET FA2.2 THAT ROOM 112 IS A
 COMBINATION JANITOR/ELECTRICAL ROOM. STORAGE AND/OR
 COMBUSTIBLES SHALL NOT BE ALLOWED IN ELECTRICAL ROOMS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722