| 2010-02-22 10:44:19 | *****DENIED***** |
| | |
| | |
| | 1. WHAT IS ADDRESS FOR THIS PROJECT SITE LOCATION? BE |
| | ADVISED OF THE FOLLOWING ADDRESS DICREPANCIES: |
| | SUBMITTED APPLICATION (1701 OLD OKEECHOBEE ROAD), PLAN |
| | SHEETS CVR THRU A602 (1701 OLD OKEECHOBEE ROAD, SUITE |
| | 1727, PLAN SHEETS M0.1 THRU FS2.2 (1727 OLD OKEECHOBEE |
| | ROAD) |
| | |
| | 2. PLEASE EXPLAINE THE DIFFERENCES IN THE SQARE FOOTAGE |
| | IN THE SCOPE OF WORK SECTION COMPARED TO THE CODE |
| | RESEARCH SECTION AS LISTED ON THE CVR SHEET. |
| | |
| | 3. STRUCTURES UNDERGOING CONSTRUCTION, ALATERATION, OR |
| | DEMOLITIONS OPERATIONS SHALL COMPLY WITH NFPA 241 - |
| | 2004 EDITION. |
| | |
| | 4. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 5. NO DOOR OPENING SHOWN FOR DOOR #24 ON A101 SHEET. |
| | |
| | 6. ON SHEET A131 IN THE LOWERE LEFT CORNER OF THE |
| | DIAGRAM, IT APPEARS THAT THE PATH OF TRAVEL FOR THE |
| | TRAVEL DISTANCE PASSES THROUGH A WALL. PLEASE EXPLAIN. |
| | |
| | 7. PROPERLY LIST THE PORTABLE FIRE EXTINGUISHERS AS |
| | 2A10BC INSTEAD OF 2A100BC AS LISTED ON A131 & A132 |
| | SHEETS. |
| | |
| | 8. ON SHEET FA0.1, AMEND FIRE ALARM NOTE #17 TO REFLECT |
| | THAT DUCT SMOKE DETECTORS IATE A GENERAL FIRE ALARM (AS |
| | PER LOCAL CODES) . |
| | |
| | 9. IT IS LISTED ON SHEET FA2.2 THAT ROOM 112 IS A |
| | COMBINATION JANITOR/ELECTRICAL ROOM. STORAGE AND/OR |
| | COMBUSTIBLES SHALL NOT BE ALLOWED IN ELECTRICAL ROOMS. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |