Plan Review Notes
Plan Review Notes For Permit 10020362
Permit Number 10020362
Review Stop E
Sequence Number 1
Notes
Date Text
2010-02-19 12:13:13** DENIED **
  
 1) NOTE: SEE CVR SHEET. NOTES UNDER LIFE SAFETY/FIRE
 SPRINKLER SECTIONS INDICATES 2004 FLORIDA BUILDING
 CODE.
 THE FOLLOWING CODES ARE RELEVANT TO THIS PROJECT AS
 APPLIED AFTER OCTOBER 1ST, 2009.
 SHEET M-1 INDICATES 2005 NEC. HOWEVER IF THIS IS THE
 ONLY COMMENT ON THIS SHEET THIS MAY BE REDLINED.
  
 2007 FBC W/2009 SUPPLEMENTS.
 2006 NFPA-101
 2008 NFPA-70
  
 2) NOTE: PERMIT APPLICATIONS AND PLANS ALL INDICATE
 *OLD* OKEECHOBEE RD. THIS OFFICE IS WELL AWARE THE
 STREET SIGNAGE INDICATING *OLD OKEECHOBEE RD*. THE
 ACTUAL LEGAL ADDRESS IS *OKEECHOBEE RD*. THIS HAS BEEN
 ADJUSTED ON APPLICATIONS. PLANS DO NOT NEED TO
 RE-PRINTED, THIS MAY BE ADJUSTED BY HAND.
  
  
 3) NOTE: THE SUBMITTED FLA COM CALCULATIONS ARE
 INDICATING THE ENTIRE SPACE UNDER TYPE OF BUILDING AS
 OFFICE. THIS IS NOT CORRECT. ONCE *OFFICE* IS ENTERED
 UNDER TYPE OF BUILDING THE ALLOWANCES ARE GIVEN TO
 ENTIRE SQ FT UNDER OFFICE. THIS WOULD EXPLAIN THE
 ALLOWANCE OF NEARLY 45K WATTS OF LIGHTING ALLOWED.
 THE SQ FT OF OFFICE IS LISTED AS LOW AS 11,970 AND
 ,12312 ON PLANS.
 ANOTHER COORDINATION ISSUE IS SHEETS A010, A011
 INDICATE ALL LIGHTING IN WAREHOUSE AS EXISTING TO
 REMAIN. WHY IS PRESCRIPTIVE CALCULATIONS FOR WAREHOUSE
 BEING ENTERED INTO THE INPUT DATA REPORT OF THE
 SUBMITTED CALCULATIONS?
 *PLEASE CONFIRM SPACE #155 IN THE IDR SHOWING MANUAL
 ON/OFF WHEN PLANS INDICATE AUTOMATED CONTROLS.
 * TRACK LIGHTING SHOWN IN AREAS 100 AND 123 ARE NOT
 LISTED ON FIXTURE LEGEND. IT IS NOT POSSIBLE TO
 COORDINATE THE IDR IF THE FIXTURES ARE NOT KNOWN.
 PLEASE BE SURE TO SEE THE APPENDIX SECTION B4.1.1 FOR
 TRACK LIGHTING REQUIREMENTS.
  
 4) NOTE: LIGHTING IN CLOSETS SUCH AS 137 AND 137 IS TOO
 CLOSE TO ASSUMED DIMENSIONS REQUIRED BY NEC. SEE
 410.6,410.8. THE MINIMUM CLEARANCES ARE REQUIRED
 WHETHER OR NOT CLOTHING IS GOING TO BE HUNG IN CLOSETS.
 MINIMUM CLEARANCES ARE REQUIRED FOR STORAGE OF ANY
 POSSIBLE COMBUSTIBLES.
  
 5) NOTE: ROOM #112 MAY NOT BE JANITOR STORAGE. THIS
 ROOM IS TO BE FOR ELECTRICAL ONLY UNLESS SEPARATION IS
 MADE BETWEEN THE TWO LOCATIONS.
 PLEASE SEE 110.26 AND 240.24D.
  
 6) NOTE: ALL NEW LIGHTING SHALL COMPLY WITH FBC
 13-415.AB.1.1,.1.2 AND .1.3 FOR INTERIOR LIGHTING.
 ROOM #147 ON PLANS INDICATES STANDARD 3-WAY SWITCHES
 WITH A NOTE #2. NOTE #2 MENTIONS TO SEE LIGHTING DETAIL
 ON SHEET 6.1 HOWEVER PER THE LIGHTING CONTROL/CONTACTOR
 LEGEND AND DETAIL THIS ROOM AND CIRCUIT IS NOT LISTED.
 PLEASE PROVIDE REQUIRED CONTROLS FOR LOCATION AS THIS
 IS A SEPARATE SPACE WITHIN THE TENANT SPACE.
 PLEASE SEE LIGHTING SUCH AS TRACK LIGHTING, P2 FIXTURES
 ETC WHICH REQUIRE SEPARATE CONTROLS. PLANS INDICATE
 CIRCUITING TO TIME CLOCK LIGHTING CONTROLS HOWEVER NO
 LOCATIONS ON PLANS FOR SEPARATE CONTROLS PER
 13-415.AB.1.3 COULD BE LOCATED.
 AREAS 158, 101 ARE THE SAME. THE SINGLE POLE LIGHT
 SWITCH AS AN OVER RIDE IS NOT PERMITTED.
 ROOM 150 IS NOT LISTED ON DETAIL CONTACTOR LEGEND.
 PLEASE ALSO ADJUST OVER RIDE CONTROL AS NOTED ABOVE.
 SINGLE POLE DIMMER DOES NOT MEET OVER RIDE SEPARATE
 CONTROLS.
  
 7) NOTE: ROOM #125 IS LISTED AS ANY IT ON ARCHITECTURAL
 PLANS AS WELL AS ELECTRICAL PLANS AND OTHER TRADE
 PLANS.
 BASED ON THE PLANS THIS ROOM DOES *NOT* MEET ALL OF THE
 REQUIREMENTS PER NEC 645.4 (1-5) OR NFPA-75 2003. THE
 WIRING METHODS PERMITTED IN 645 ARE LESS STRINGENT FROM
 CHAPTERS 1-4 OF THE NEC.
 VERIFICATION WITH OWNER/OWNER*S IT PERSONNEL MAY BE
 NEEDED IF WIRING PER 645 IS DESIRED.
 THIS ROOM DOES NOT MEET ALL ITEMS 1-5 AS NOTED. PLEASE
 ADJUST PLANS FOR AN IT ROOM BY DEFINITION OR REVISE
 PLANS AND LIST NOTE TO STATE * NO WIRING METHODS PER
 NEC 645 PERMITTED* OR WORDS TO THAT AFFECT.
  
 8) NOTE: FYI. KEEP IN MIND ALL CONDENSATE PUMPS ABOVE
 CEILING AREAS SHALL NOT BE CORD TYPE. SHALL BE WIRED
 WITH ACCEPTABLE WIRING METHODS PERMITTED IN THE NEC.
 CORDS ABOVE THE CEILING ARE NOT PERMITTED. 400.8 (1-5)
 THIS IS FOR ALL LOCATIONS.
  
 9) NOTE: EMERGENCY AND NORMAL EGRESS LIGHTING REQUIRED
 FOR EXTERIOR AREAS WHERE THERE ARE SIDEWALKS AND STAIRS
 FOR OCCUPANCY LEADING AWAY FROM BUILDING. THERE ARE
 SEVERAL LOCATIONS IN WHICH THE OCCUPANT WILL EXIT THE
 BUILDING DOORWAY AND STILL BE REQUIRED TO TRAVERSE
 WALKWAY AS WELL AS STAIR AREAS.
 PLEASE SEE FBC 1006, NFPA101 7.8.1.3, 7.9.1.1, 7.9.2.2.
 ** THIS WAS BROUGHT UP IN MEETING PREVIOUSLY HELD
 HOWEVER MEP DESIGN TEAM WAS NOT PRESENT. IF THIS WERE
 THE ONLY COMMENT A PROVISO CONDITION COULD HAVE BEEN
 GRANTED.
 ** WHAT ABOUT LIGHTING IN SINK/AREA #133?
  
  
 10) NOTE: ALL CIRCUITING SHALL BE SPECIFICALLY
 IDENTIFIED. PANEL *H* FOR EXAMPLE IS EXISTING AND IT IS
 UNDERSTOOD SOME OF THESE CIRCUITS MAY NOT BE KNOWN AT
 THIS TIME. THESE WOULD BE REQUIRED TO BE REVISED BEFORE
 FINAL, SUBMITTED, REVIEWED, STAMPED AND ON-SITE BEFORE
 FINAL INSPECTION. 408.4
 LOADS AND CIRCUITING FOR OTHER NEW LOADS NEED TO
 COORDINATE. LOADS, ETC AS LISTED CAN NOT BE VERIFIED AS
 SOME ITEMS ARE LISTED BELOW.
 * WHAT IS CIRCUIT L-19? STATES ONLY RECEPTACLE ON PANEL
 SCHEDULE HOWEVER PLANS APPEAR TO SHOW SOME SORT OF
 APPLIANCE.
 * WHAT ABOUT CIRCUIT #LB-12 LISTED ON PANEL SCHEDULE
 FOR ROOM #130, YET PLANS ALSO INDICATES THIS FOR A
 DEDICATED COPIER IN ROOM #136. PLEASE ADJUST CIRCUITS,
 LOAD, AND PANEL.
 *PLEASE EXPLAIN LOADS ON RECEPTACLE CIRCUITS, HOW IS
 LOAD FOR ONE GENERAL RECEPTACLE THE SAME AS THE LOAD
 FOR SEVERAL ON ONE CIRCUIT? HOW IS THE LOAD FOR THE
 MICROWAVE ( LB 24) THE SAME AS THE LOAD FOR THE
 DEDICATED COPIER WHICH IS ALSO ON GENERAL RECEPTACLES?
 HOW ARE THE APPLIANCES THE SAME?
 PLEASE SEE 220.44, 220.12,220.14, 220.18 ETC.
 ** PLEASE SEE CIRCUITS LB27,29 ON PANEL SCHEDULE AND ON
 SHEET E3.1 AS THESE ARE BOTH LISTED FOR LIGHTING IN
 ROOMS 101,123 AND 130, YET POWER PLANS INDICATE
 DEDICATED CIRCUITS FOR FUTURE EQUIPMENT IN ROOM 147.
  
 ** PLEASE GO THROUGH ALL NEW CIRCUITING FOR LOAD, OVER
 CURRENT PROTECTION ETC.
  
 11) NOTE: PLEASE PLACE NOTE ON PLANS FOR MULTI-WIRE
 BRANCH CIRCUITS. 210.4B OF THE NEC HAS SUBSTANTIALLY
 CHANGED FROM THE 2005 CODE. THIS IS NOT ONLY FOR DEVICE
 WITH THE SAME YOKE AS PREVIOUSLY REQUIRED IN THE CODE.
 THIS OFFICE IS FINDING MANY PROJECTS WHERE THIS CHANGE
 IN THE CODE IS NOT KNOWN.
  
 12) NOTE: AS REQUESTED IN MEETING HELD PRIOR TO
 SUBMITTAL OF PERMIT APPLICATION, PLEASE SUBMIT THE
 MANUFACTURES SPECS/CUT SHEETS FOR THE NEW PROPOSED ATS.
 110.3,90.7
 ** PLEASE BE AWARE OF POSSIBLE COMMENTS FROM OTHER
 TRADES FOR THE POSSIBLE LOCATION OF FUTURE GENERATOR.
 A MEANS OF DISCONNECT FOR FEEDERS FROM GENERATOR WILL
 BE REQUIRED PER 225.31-225.39 UNLESS MEETING THE
 702.11. K3EEP IN MIND BOTH REQUIREMENTS OF 702.11 ARE
 REQUIRED. *WITHIN SIGHT OF THE BUILDING AND READILY
 ACCESSIBLE*. IF THE UNIT IS LOCATED IN AN ENCLOSURE
 WHICH MAY BE REQUIRED BY OTHER TRADE REVIEWS THEN THIS
 MEANS OF DISCONNECT AT THE GENERATOR MAY NO LONGER BE
 READILY ACCESSIBLE.
 DISCONNECT WILL NOT BE PERMITTED INSIDE THE BUILDING
 WHERE IN THE EVENT OF EMERGENCY FIRE DEPARTMENT OR
 OTHER PERSONNEL CAN NOT GAIN IMMEDIATE AND PROTECTED
 ACCESS TO TURN OFF POWER.
  
 13) NOTE: PLEASE SHOW LOCATION OF ALL ELECTRICAL PANELS
 AND PROPOSED LOCATIONS OF PANELS AND EQUIPMENT ON
 PLANS. ( DEPENDING ON NOTE12.
  
 14) NOTE: THE MECHANICAL POWER PLANS DO INDICATE SOME
 GFI RECEPTACLES AS REQUIRED PER 210.63 AND 210.8B3
 HOWEVER NOT ALL MEET DISTANCE REQUIRED PER 210.63
  
 15) NOTE: SPLICE BOXES SHALL INDICATE MINIMUM SIZING
 PER 314.28
  
 16) NOTE: PLEASE SEE FBC CHAPTER 13, SECTION 13-412 AND
 13-411. THE PLANS INDICATE NEW WATER HEATING YET THE
 IDR DOES NOT CONTAIN ANY INFORMATION FOR WATER HEATING,
 OR PIPING INSULATION MINIMUMS. SEE 13-400.0.B.4 AS THIS
 IS REQUIRED EVEN IF NOT MEETING THE DEFINITION OF A
 RENOVATED BUILDING. SEE COMMENTS FROM OTHER POSSIBLE
 TRADES SUCH AS THE PLUMBING REVIEW.
  
 17) NOTE: ALL TENANT MAINS/MEANS OF DISCONNECT SHALL BE
 LABELED IN MAIN ELECTRICAL ROOM. AS NOTED ABOVE THE
 DISCONNECTING MEANS FOR GENERATOR IS NOT KNOWN AT THIS
 TIME.
 PLEASE LABEL RISER. PLEASE ALSO VERIFY WITH FIRE
 MARSHAL THAT MORE THAN ONE DISCONNECT/METER WILL BE
 PERMITTED FOR SINGLE TENANT.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  