| 2010-02-17 10:36:54 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- NEED TO PROVIDE RAS 117 CALCULATIONS FOR NAIL | | | ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY | | | GENERAL LIMITATION #7 ON SHEET 29 OF NOA SUBMITTED. | | | ACCORDING TO GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | 09-0224.01 SUBMITTED THE RAS 117 CALCULATIONS NEED TO | | | BE SIGNED AND SEALED BY ANY OF THE PROFESSIONALS | | | LISTED. SEE LAST PAGE OF NOA SUBMITTED. | | | | | | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $135.23 | | | FOR UPDATED VALUATION. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|