Plan Review Notes
Plan Review Notes For Permit 10020355
Permit Number 10020355
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-03-31 10:26:51 
 1387 10TH STREET
 PERMIT NUMBER 10020355
  
 1. THE SMOKE ALARMS DISPLAYED ON THE PLANS ARE TO BE
 MULTI-STATION. WHEN ONE ACTIVATES, THEY SHALL ALL
 OPERATE.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 ALARM SYSTEM.
  
 3. THE PLANS DESIGNATE SIX OCCUPANTS. HOWEVER NO
 EVACUATION CRITERIA FOR THE RESIDENTS HAS BEEN
 ESTABLISHED. WILL THE EVACUATION CAPABILITIES OF THE
 RESIDENTS BE DEFINED AS SLOW, PROMPT, OR IMPRACTICAL?
  
 4. PLEASE SUBMIT AN EMERGENCY EVACUATION PLAN TO THIS
 OFFICE FOR REVIEW.
  
 5. A 4" STEP DOWN IS LOCATED IN THE TV ROOM. CHANGES IN
 ELEVATIONS LESS THAN 12" SHALL BE BY RAMPS. (NFPA 101,
 SECTION 7.1.7.1)
  
 6. COULD NOT LOCATE ANY PORTABLE FIRE EXTINGUISHERS.
  
 7. SLEEPING ROOM DOORS SHALL BE AT LEAST 1-3/4 " SOLID
 BONDED WOOD CORE CONSTRUCTION.
  
 8. ZONING APPROVAL WILL BE REQUIRED FOR THIS
 RESIDENTIAL BOARD AND CARE FACILITY, SMALL FACILITY
 LESS THAN 16 RESIDENTS.
  
 9. PLEASE DESIGNATE ON THE PLANS THE PRIMARY AND
 SECONDARY MEANS OF ESCAPE.
  
 10. PLEASE DESCRIBE DOOR HARDWARE AND LOCKING DEVICES
 ON PRIMARY AND SECONDARY MEANS OF ESCAPE.
  
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX
  
 WESLEY JOLIN, FIRE PROTECTION ENGINEER
 BUREAU OF FIRE PREVENTION
 (561) 805-6730 PHONE
 (561) 804-4774 FAX