| Date |
Text |
| 2010-02-22 13:47:16 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | |
| | 1. A SANITARY ISOMETRIC RISER DIAGRAM IS REQUIRED. |
| | SECTION 106.3.5.1.3(4)(6)(13). SHOW ALL PIPE SIZES, |
| | TRAPS, VENTS ETC. SECTIONS 701.1, 901.1 & 1001.1. |
| | |
| | 2. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED. SECTION |
| | 106.3.5.1.3(3)(10)(13). SHOW ALL PIPES SIZES, VALVES & |
| | (WHERE REQUIRED BY SECTION 604.9), WATER HAMMER |
| | ARRESTORS. (DISH WASHER). |
| | |
| | 3. INDICATE HOW THE SANITARY AND WATER WILL BE ROUTED |
| | FROM ONE SIDE OF THE ROOM TO THE OTHER. SECTION |
| | 106.1.1. |
| | |
| | 4. VALUE INDICATED ON THE APPLICATION APPEARS TO BE |
| | LOW. PLEASE PROVIDE A CONTRACT SIGNED BY THE OWNER. |
| | VALUE SHALL INCLUDE ALL MATERIALS, LABOR |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |