| 2010-02-16 16:56:29 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- ACCORDING TO SEC. R301.2.1.4.3 OF THE 2009 REVISIONS | | | TO THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS | | | LOCATED ON EXPOSURE "C" NOT "B". | | | MODIFIED BITUMEN SYSTEM SELECTED (W-32) DOESN'T RESIST | | | THE UPLIFT PRESSURES OF SEC. R301 OF 2007 FLORIDA | | | RESIDENTIAL CODE AND NAIL ENHANCING IS NOT ALLOWED. | | | NEED TO SELECT SYSTEM THAT MEETS OR EXCEEDS THE | | | CALCULATED DESIGN PRESSURES FOR EXPOSURE "C". | | | | | | JULIO GOMEZ | | | COMBINATION COMMERCIAL PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|