Plan Review Notes
Plan Review Notes For Permit 10020288
Permit Number 10020288
Review Stop P
Sequence Number 1
Notes
Date Text
2010-03-03 16:04:22DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 BUILDING
  
 1. SHT A-0.00 THE OCCUPANCY LOAD IS INDICATED AS 90
 OCCUPANTS. PLEASE SEE THE COMMENTS OF JWITMER BUILDING
 PLANS EXAMINER 1A THRU 1D CONCERNING THE OCCUPANT LOAD.
 MINIMUM FACILITIES FOR PLUMBING FIXTURES IS BASED ON
 TABLES 1104.1.1 & 403.1. AFTER VERIFICATION OF THE
 OCCUPANCY LOAD, MORE COMMENTS MAY BE FORTHCOMING.
  
 2. SHT A-1.02 GALVANIZED SCUPPER DETAIL SHOWS AN 8 INCH
 X 2 INCH OVERFLOW SCUPPER. PER SECTION 1107.3 SCUPPERS
 SHALL NOT HAVE AN OPENING DIMENSION OF LESS THAN 4
 INCHES. ALSO PLEASE INDICATE THE SIZE OF THE EXISTING
 ROOF DRAINS TO VERIFY THE REQUIRED SIZE OF THE OVERFLOW
 SCUPPERS.
  
 3. SHT A-5.01 TOILET ROOMS 112, 115 & 116. WALLS WITHIN
 2 FEET OF THE WATER CLOSETS SHALL COMPLY WITH SECTION
 1210.2. THE INFORMATION SHOWN ON THE FLOOR PLAN, 112
 (W-5.11), 115 (W-1.11) & 116 (W-1.10) DOES NOT REFLECT
 THE INFORMATION ON THE FINISH SCHEDULE. PLEASE CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  