| Date |
Text |
| 2010-03-03 16:04:22 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 BUILDING |
| | |
| | 1. SHT A-0.00 THE OCCUPANCY LOAD IS INDICATED AS 90 |
| | OCCUPANTS. PLEASE SEE THE COMMENTS OF JWITMER BUILDING |
| | PLANS EXAMINER 1A THRU 1D CONCERNING THE OCCUPANT LOAD. |
| | MINIMUM FACILITIES FOR PLUMBING FIXTURES IS BASED ON |
| | TABLES 1104.1.1 & 403.1. AFTER VERIFICATION OF THE |
| | OCCUPANCY LOAD, MORE COMMENTS MAY BE FORTHCOMING. |
| | |
| | 2. SHT A-1.02 GALVANIZED SCUPPER DETAIL SHOWS AN 8 INCH |
| | X 2 INCH OVERFLOW SCUPPER. PER SECTION 1107.3 SCUPPERS |
| | SHALL NOT HAVE AN OPENING DIMENSION OF LESS THAN 4 |
| | INCHES. ALSO PLEASE INDICATE THE SIZE OF THE EXISTING |
| | ROOF DRAINS TO VERIFY THE REQUIRED SIZE OF THE OVERFLOW |
| | SCUPPERS. |
| | |
| | 3. SHT A-5.01 TOILET ROOMS 112, 115 & 116. WALLS WITHIN |
| | 2 FEET OF THE WATER CLOSETS SHALL COMPLY WITH SECTION |
| | 1210.2. THE INFORMATION SHOWN ON THE FLOOR PLAN, 112 |
| | (W-5.11), 115 (W-1.11) & 116 (W-1.10) DOES NOT REFLECT |
| | THE INFORMATION ON THE FINISH SCHEDULE. PLEASE CLARIFY. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |