Plan Review Notes
Plan Review Notes For Permit 10020288
Permit Number 10020288
Review Stop M
Sequence Number 1
Notes
Date Text
2010-03-04 15:33:42**PROVISO**
  
 AHU #2 DUCT SMOKE DETECTOR IS SHOWN LOCATED IN THE
 TRUNK LINE, DOWNSTREAM OF THE FIRST SUPPLY BRANCH.
 REQUIRED SMOKE DETECTORS SHALL BE INSTALLED TO MONITOR
 THE ENTIRE AIRFLOW IN ACCORDANCE WITH FBC-M 606.3.
  