| 2010-03-04 15:33:42 | **PROVISO** | | | | | | AHU #2 DUCT SMOKE DETECTOR IS SHOWN LOCATED IN THE | | | TRUNK LINE, DOWNSTREAM OF THE FIRST SUPPLY BRANCH. | | | REQUIRED SMOKE DETECTORS SHALL BE INSTALLED TO MONITOR | | | THE ENTIRE AIRFLOW IN ACCORDANCE WITH FBC-M 606.3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|