| Date |
Text |
| 2010-02-24 15:57:37 | ** DENIED ** |
| | |
| | |
| | 1) NOTE: PLEASE ADJUST NFPA-101 AS LISTED ON E-0. |
| | INDICATES 2003 EDITION HOWEVER PER FAC 69A-03.012 AND |
| | THE ADOPTION OF TH E2007 FBC W/2009 SUPPLEMENTS. |
| | * THIS COULD HAVE BEEN REDLINED HOWEVER PLANS ARE |
| | COMING BACK FOR OTHER NOTES. |
| | |
| | 2) NOTE: PLEASE SUBMIT THE COMPLETED ENERGY |
| | CALCULATIONS FOR REVIEW. PLEASE BE SURE TO COMPLETE THE |
| | CALCULATIONS WITH ALL REQUIRED SYSTEMS IN FBC CHAPTER |
| | 13 IN THE INPUT DATA REPORT AND COORDINATE WITH PLANS. |
| | PLEASE SEE PAGE TWO OF THE SUBMITTED CALCULATIONS WHICH |
| | STATES THE INPUT DATA REPORT MUST BE SUBMITTED WITH THE |
| | COMPLIANCE REPORT. THERE ARE NO INPUT DATA REPORT |
| | SHEETS SUBMITTED. |
| | PLEASE KNOW THAT ALL SYSTEMS INCLUDING HOT WATER PIPING |
| | SYSTEMS ARE REQUIRED. THE SUMMARY SHEETS STATES * NONE |
| | ENTERED*. PLEASE EXPLAIN HOW THIS IS POSSIBLE? SEE |
| | MINIMUM UNDER 13-411, 13-412. |
| | THE SUBMITTED FLA COM IS FOR METHOD *A* , WHOLE |
| | BUILDING COMPLIANCE. THIS IS AN EXISTING BUILDING |
| | MEETING THE DEFINITION OF A RENOVATION PER SECTION 202. |
| | PLEASE EXPLAIN THE USE OF METHOD *A*. |
| | PLEASE EXPLAIN WHAT APPEARS TO BE METHOD *B* ON PLANS. |
| | PLEASE KNOW THAT THERE IS NO LONGER *ACCENT OR |
| | DECRETIVE* ALLOWANCES UNDER THE NEW CODE. |
| | |
| | ** PLEASE BE SURE TO SEE APPENDIX B4.1.1 FOR TRACK |
| | LIGHTING AND OTHER LUMINAIRE WATTAGES. |
| | |
| | 3) NOTE: PLEASE EXPLAIN THE MSB AS SHOWN. THE MSB |
| | SCHEDULE STATES THE MAIN OVER CURRENT PROTECTION IS |
| | 600AMPS YET THE RISER DOES NOT INDICATE ANY 600AMP OCP. |
| | NEED TO VERIFY. |
| | 230.70.230.71.230.76, 310.16 ETC |
| | |
| | 4) NOTE: PLEASE VERIFY THE MAIN OVER CURRENT PROTECTION |
| | FRO EACH OF THE TWO SUB PANELS. THE MSB SCHEDULE |
| | INDICATES 225AMP OCP FOR EACH PANEL HOWEVER THE FEEDERS |
| | TO EACH OF THE PANELS *LPA AND LPB* ARE ONLY RATED FOR |
| | 200AMPS PER 310.16, 110.14. |
| | THE OTHER ITEM WHICH IS NOT CLEAR IS THE RISER |
| | INDICATES 200AMP OCP FOR THE SAME TWO PANELS WHICH IS |
| | NOT THE SAME AS THE INFORMATION PROVIDED ON THE MSB |
| | SCHEDULE. |
| | PLEASE COORDINATE THE OCP AND CONDUCTOR SIZES FOR EACH. |
| | |
| | 5) NOTE: PLEASE SEE 406.8 AND MAKE NOTE OF RECEPTACLES |
| | IN WET/DAMP LOCATIONS. |
| | |
| | 6) NOTE: PLANS DO CONTAIN A NOTE THAT STATES EXTERIOR |
| | LIGHTING TO OPERATE THROUGH A TIME CLOCK. HOWEVER A |
| | STANDARD TIME CLOCK DOES NOT MEET MINIMUM REQUIRED BY |
| | FBC 13-415.AB.1.4. |
| | ONE OF THE TWO METHODS OF CONTROLS FOR MINIMUM CONTROLS |
| | IS REQUIRED. |
| | PHOTO-SENSOR TYPE CONTROLS OR |
| | ASTRONOMICAL TIME CLOCK WITH A MINIMUM OF 10HR |
| | PROGRAMMING BATTERY BACK UP. |
| | |
| | 7) NOTE: PLEASE SEE FBC 13-415.AB.1.2. |
| | EVEN WHEN LIGHTING IS IN A BUILDING SMALLER THAN 5K SQ |
| | FT IN THE FOLLOWING ROOMS AUTOMATED LIGHTING CONTROLS |
| | LISTED ARE REQUIRED TO MEET MINIMUM CODE. |
| | THIS HAS BEEN CONFIRMED WITH THE STATE OF FLORIDA. |
| | |
| | CLASSROOMS, |
| | CONFERENCE ROOMS/MEETING ROOMS AND |
| | LUNCH/BREAK ROOMS. |
| | |
| | 8) NOTE: PLEASE SEE COMMENTS FROM FIRE MARSHAL FOR A |
| | FEW POSSIBLE MISSING EXIT SIGNS PER NFPA-101. |
| | PLEASE SEE NFPA_101 7.8.1.3,7.9.1.2,.2.2 FOR MINIMUM |
| | FOOT CANDLE LEVELS REQUIRED FOR EMERGENCY EGRESS |
| | LIGHTING. THERE NO PHOTO-METRICS SUBMITTED AND |
| | DESIGNATED EGRESS PATH TO SOME AREAS APPEAR TO BE |
| | DEFICIENT FOR SOME LIGHTS. |
| | PLEASE SEE FOYER AREA. |
| | |
| | 9) NOTE: THE PLANS INDICATE CARE AREAS, WILL THERE BE |
| | ANY DOCTORS, NURSES PRESENT PERFORMING EXAMS? PLEASE |
| | SEE NEC 517.10 AND REDUNDANT GROUNDING REQUIRED IN EXAM |
| | ROOMS IN 517.13. |
| | |
| | 10) NOTE: LOW VOLTAGE AS SHOWN ON PLANS SUCH AS CATV, |
| | PHONE, DATA OR SPEAKERS WILL BE UNDER SEPARATE PERMITS. |
| | ANY PROPOSED EGRESS/ACCESS CONTROLS WILL BE UNDER |
| | SEPARATE PERMIT AND PLANS. |
| | THESE PLANS MAY BE REFERENCED FOR TV, PHONE, DATA AND |
| | LV SPEAKERS ONLY FOR TURN-AROUND LV PERMITS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |