Plan Review Notes
Plan Review Notes For Permit 10020288
Permit Number 10020288
Review Stop B
Sequence Number 1
Notes
Date Text
2010-03-02 15:54:19BUILDING PLAN REVIEW
 PERMIT: 10020288
 ADD: 3115 45TH ST
 CONT: SERRAES CONSTRUCTION
 TEL: (561)848-6607
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 MARCH 03/ 2010
  
 1) SHEET A-0.00 LIFE SAFETY PLAN:
  
 1A) THE PLANS INDICATE AN AREA OF FIXED SEATING
 CLAIMING THE REQUIREMENT OF 1004.7. THE OCCUPANT LOAD
 IS PROVIDED BY OCCUPANCY TYPE, NOT BY ROOM NUMBER, IT
 IS CONFUSING AS TO WHAT AREAS ARE BEING CONSIDERED AN
 ASSEMBLY AREA. TABLE 1004.1.1 & SECTION 1004.7.
  
 1B) ROOM# 103 THE TRAINING ROOM IF CONSIDERED WITH
 TABLES AND CHAIRS HAS AN OCCUPANT LOAD OF 738/15= 49.2
 OR 50 OCCUPANTS. SEE TABLE 1017.1, ASSEMBLY OCCUPANCY <
 30 REQUIRES A ONE HOUR RATED CORRIDOR. IF CHAIRS ( NOT
 FIXED) ARE FIGURED INTO THE EQUATION THEN
 738/7= 105.4 OR 106 OCCUPANTS. IN EITHER CASE TABLE
 1017.1 WILL REQUIRE A 1 HR RATED CORRIDOR.
  
 1C) THE OTHER ISSUE WITH ROOM 103 THE TRAINING ROOM IS
 THERE IS ONLY ONE MEANS OF EGRESS INTO THIS ROOM.
 PLEASE REVIEW TABLE 1019.2 FOR ASSEMBLY A3 OCCUPANCY
 WITH ONE MEANS OF EGRESS NO MORE THAN 49 OCCUPANTS MAY
 OCCUPY THIS ROOM.
  
 1D) ROOM 117 THE CHAPEL IS ALSO TO BE CONSIDERED A
 ASSEMBLY A3 OCCUPANCY CONSIDERING THE SQ FT AS 682 SQ
 FT/15= 46 OCCUPANTS. THE CORRIDOR WOULD ALSO NEED TO BE
 1 HOUR RATED, SEE TABLE 1017.1.
 PLEASE NOTE THE ASSEMBLY ROOMS MEET THE EXCEPTION <
 THAN 750 SQ FT AND WOULD NOT NEED OCCUPANCY SEPARATION
 BETWEEN OCCUPANCIES.508.3.1.
  
 1E) WITHIN THE CHAPEL IT APPEARS AT THE END OF THE ROOM
 WHERE AN ALTER IS LOCATED IT APPEARS A CHANGE IN
 ELEVATION? IF SO PLEASE INDICATE THE GRADE CHANGE.
 PROVIDE COMPLIANCE WITH VERTICAL ACCESSIBILITY.
 11-4.1.6(1)(K)(III).
  
  
 1F) OTHER INCIDENTAL USE AREAS THAT WOULD NEED
 SEPARATION PLEASE REVIEW 508.2, MECHANICAL ROOMS,
 STORAGE ROOMS> THAN 100 SQ FT (CLOTHES CLOSET # 125).
 ALSO NOTE ROOM ELECTRICAL, TECH/ DATA ROOM, IF THIS IS
 A TRUE IT ROOM REVIEW NEC 645.4(5) FOR 1 HR SEPARATION.
  
 1G) THE DOOR THAT LEADS INTO ROOM 108 IS MISSING THE
 REQUIRED 18 INCHES AT THE LATCH SIDE OF THE DOOR.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 1H) THE DOOR LEADING INTO THE DIRECTORS OFFICE ROOM#
 114 ALSO WILL NEED TO MEET THE REQUIREMENTS OF
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 2) SHEET AD 1.01 THE EXISTING ACCESSIBLE RAMP DOES NOT
 INDICATE COMPLIANCE WITH 11-4.29.5/ DUTY TO PROVIDE
 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.11-4.1.6(2) (2)(A).
  
 3) PRODUCT APPROVALS: THE CONTRACTOR HAS ONLY SUBMITTED
 THE FLORIDA COVERSHEETS, NOT THE ASSOCIATED REPORTS.
 WITH ONLY THE COVER SHEET AND NO SUB-SYSTEM HIGHLIGHTED
 NOR THE PRODUCT APPROVAL THEMSELVES THE POSITIVE AND
 NEGATIVE PRESSURES CAN NOT BE VERIFIED FOR THESE
 PRODUCTS;
 3A) FL 8835-R1/ 2007 EAGLE ROOFING PRODUCTS- ROOF TILE
 THE MIAMI-DADE NOA WAS SUBMITTED, NOR ROOFING
 SUB-SYSTEM IDENTIFIED WHICH WOULD IDENTIFY POSITIVE AND
 NEGATIVE PRESSURES AND LIMITATIONS.
  
 3B) FL 479-R2/ 2004 CERTAIN TEED CORPORATION MODIFIED
 BITUMEN ROOF SYSTEMS
 THE MIAMI-DADE NOA WAS SUBMITTED, NOR ROOFING
 SUB-SYSTEM IDENTIFIED WHICH WOULD IDENTIFY POSITIVE AND
 NEGATIVE PRESSURES AND LIMITATIONS.
  
 3C) FL 8712-R1 YKK AP EXTERIOR DOORS
 THE INSTALLATION INSTRUCTIONS NOR THE EVALUATION REPORT
 WAS NOT SUBMITTED WHICH WOULD HAVE IDENTIFIED THE
 POSITIVE AND NEGATIVE PRESSURES
  
 3D) FL 243-R8 PGT WINDOWS FIXED
 THE MIAMI-DADE NOA WAS SUBMITTED, NOR ROOFING
 SUB-SYSTEM IDENTIFIED WHICH WOULD IDENTIFY POSITIVE AND
 NEGATIVE PRESSURES AND LIMITATIONS.
  
 3E) FL 4553-R2 CECO DOOR EXTERIOR SWING DOOR-
 CERTIFICATION MARK OR LISTING MAY OR MAY NOT MEET
 PRESSURES SINCE PRESSURES ARE NOT GIVEN, NOR WERE
 INSTALLATION INSTRUCTIONS SUBMITTED.
 4) 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 5) SHEET S1.01 & A-3.01 THE ELEVATIONS INDICATE A ROOF
 PITCH OF 5/12 AND A FLAT ROOF. SHEET S1.01 PROVIDES
 PRESSURES FOR ROOFING TRIBUTARY AREAS BUT NOT THE
 ACTUAL PRESSURES FOR COMPONENTS AND CLADDING. NOTE
 THERE WILL BE TWO DIFFERENT PRESSURE DUE TO A FLAT ROOF
 AS WELL AS A 5/12 PITCHED ROOF. IN BOTH CASES ZONES 1,
 2 AND 3 WILL NEED TO BE ADDRESSED.
 FOR EXAMPLE FOR A FLAT ROOF IN ZONE 3, THE NEGATIVE
 PRESSURES WILL BE -89 WITH MULTIPLIERS OF 1.21 FOR
 EXPOSURE ???C???.
  
 6) SHEET A-4.01 BUILDING SECTION# 1 INDICATES THE USE
 OF ICYNENE INSULATION AT THE CEILING LEVEL WHERE AS
 SECTION# 2 INDICATES THE ICYNENE INSULATION AT THE TOP
 CHORD OF THE TRUSS? 106.1.2 ADDITIONAL INFORMATION
 REQUIRED, DISCREPANCY.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved