| Date |
Text |
| 2010-03-02 15:54:19 | BUILDING PLAN REVIEW |
| | PERMIT: 10020288 |
| | ADD: 3115 45TH ST |
| | CONT: SERRAES CONSTRUCTION |
| | TEL: (561)848-6607 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | MARCH 03/ 2010 |
| | |
| | 1) SHEET A-0.00 LIFE SAFETY PLAN: |
| | |
| | 1A) THE PLANS INDICATE AN AREA OF FIXED SEATING |
| | CLAIMING THE REQUIREMENT OF 1004.7. THE OCCUPANT LOAD |
| | IS PROVIDED BY OCCUPANCY TYPE, NOT BY ROOM NUMBER, IT |
| | IS CONFUSING AS TO WHAT AREAS ARE BEING CONSIDERED AN |
| | ASSEMBLY AREA. TABLE 1004.1.1 & SECTION 1004.7. |
| | |
| | 1B) ROOM# 103 THE TRAINING ROOM IF CONSIDERED WITH |
| | TABLES AND CHAIRS HAS AN OCCUPANT LOAD OF 738/15= 49.2 |
| | OR 50 OCCUPANTS. SEE TABLE 1017.1, ASSEMBLY OCCUPANCY < |
| | 30 REQUIRES A ONE HOUR RATED CORRIDOR. IF CHAIRS ( NOT |
| | FIXED) ARE FIGURED INTO THE EQUATION THEN |
| | 738/7= 105.4 OR 106 OCCUPANTS. IN EITHER CASE TABLE |
| | 1017.1 WILL REQUIRE A 1 HR RATED CORRIDOR. |
| | |
| | 1C) THE OTHER ISSUE WITH ROOM 103 THE TRAINING ROOM IS |
| | THERE IS ONLY ONE MEANS OF EGRESS INTO THIS ROOM. |
| | PLEASE REVIEW TABLE 1019.2 FOR ASSEMBLY A3 OCCUPANCY |
| | WITH ONE MEANS OF EGRESS NO MORE THAN 49 OCCUPANTS MAY |
| | OCCUPY THIS ROOM. |
| | |
| | 1D) ROOM 117 THE CHAPEL IS ALSO TO BE CONSIDERED A |
| | ASSEMBLY A3 OCCUPANCY CONSIDERING THE SQ FT AS 682 SQ |
| | FT/15= 46 OCCUPANTS. THE CORRIDOR WOULD ALSO NEED TO BE |
| | 1 HOUR RATED, SEE TABLE 1017.1. |
| | PLEASE NOTE THE ASSEMBLY ROOMS MEET THE EXCEPTION < |
| | THAN 750 SQ FT AND WOULD NOT NEED OCCUPANCY SEPARATION |
| | BETWEEN OCCUPANCIES.508.3.1. |
| | |
| | 1E) WITHIN THE CHAPEL IT APPEARS AT THE END OF THE ROOM |
| | WHERE AN ALTER IS LOCATED IT APPEARS A CHANGE IN |
| | ELEVATION? IF SO PLEASE INDICATE THE GRADE CHANGE. |
| | PROVIDE COMPLIANCE WITH VERTICAL ACCESSIBILITY. |
| | 11-4.1.6(1)(K)(III). |
| | |
| | |
| | 1F) OTHER INCIDENTAL USE AREAS THAT WOULD NEED |
| | SEPARATION PLEASE REVIEW 508.2, MECHANICAL ROOMS, |
| | STORAGE ROOMS> THAN 100 SQ FT (CLOTHES CLOSET # 125). |
| | ALSO NOTE ROOM ELECTRICAL, TECH/ DATA ROOM, IF THIS IS |
| | A TRUE IT ROOM REVIEW NEC 645.4(5) FOR 1 HR SEPARATION. |
| | |
| | 1G) THE DOOR THAT LEADS INTO ROOM 108 IS MISSING THE |
| | REQUIRED 18 INCHES AT THE LATCH SIDE OF THE DOOR. |
| | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC |
| | OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE |
| | FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES |
| | SHALL BE CLEAR & LEVEL. |
| | |
| | 1H) THE DOOR LEADING INTO THE DIRECTORS OFFICE ROOM# |
| | 114 ALSO WILL NEED TO MEET THE REQUIREMENTS OF |
| | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC |
| | OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE |
| | FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES |
| | SHALL BE CLEAR & LEVEL. |
| | |
| | 2) SHEET AD 1.01 THE EXISTING ACCESSIBLE RAMP DOES NOT |
| | INDICATE COMPLIANCE WITH 11-4.29.5/ DUTY TO PROVIDE |
| | ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY.11-4.1.6(2) (2)(A). |
| | |
| | 3) PRODUCT APPROVALS: THE CONTRACTOR HAS ONLY SUBMITTED |
| | THE FLORIDA COVERSHEETS, NOT THE ASSOCIATED REPORTS. |
| | WITH ONLY THE COVER SHEET AND NO SUB-SYSTEM HIGHLIGHTED |
| | NOR THE PRODUCT APPROVAL THEMSELVES THE POSITIVE AND |
| | NEGATIVE PRESSURES CAN NOT BE VERIFIED FOR THESE |
| | PRODUCTS; |
| | 3A) FL 8835-R1/ 2007 EAGLE ROOFING PRODUCTS- ROOF TILE |
| | THE MIAMI-DADE NOA WAS SUBMITTED, NOR ROOFING |
| | SUB-SYSTEM IDENTIFIED WHICH WOULD IDENTIFY POSITIVE AND |
| | NEGATIVE PRESSURES AND LIMITATIONS. |
| | |
| | 3B) FL 479-R2/ 2004 CERTAIN TEED CORPORATION MODIFIED |
| | BITUMEN ROOF SYSTEMS |
| | THE MIAMI-DADE NOA WAS SUBMITTED, NOR ROOFING |
| | SUB-SYSTEM IDENTIFIED WHICH WOULD IDENTIFY POSITIVE AND |
| | NEGATIVE PRESSURES AND LIMITATIONS. |
| | |
| | 3C) FL 8712-R1 YKK AP EXTERIOR DOORS |
| | THE INSTALLATION INSTRUCTIONS NOR THE EVALUATION REPORT |
| | WAS NOT SUBMITTED WHICH WOULD HAVE IDENTIFIED THE |
| | POSITIVE AND NEGATIVE PRESSURES |
| | |
| | 3D) FL 243-R8 PGT WINDOWS FIXED |
| | THE MIAMI-DADE NOA WAS SUBMITTED, NOR ROOFING |
| | SUB-SYSTEM IDENTIFIED WHICH WOULD IDENTIFY POSITIVE AND |
| | NEGATIVE PRESSURES AND LIMITATIONS. |
| | |
| | 3E) FL 4553-R2 CECO DOOR EXTERIOR SWING DOOR- |
| | CERTIFICATION MARK OR LISTING MAY OR MAY NOT MEET |
| | PRESSURES SINCE PRESSURES ARE NOT GIVEN, NOR WERE |
| | INSTALLATION INSTRUCTIONS SUBMITTED. |
| | 4) 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 5) SHEET S1.01 & A-3.01 THE ELEVATIONS INDICATE A ROOF |
| | PITCH OF 5/12 AND A FLAT ROOF. SHEET S1.01 PROVIDES |
| | PRESSURES FOR ROOFING TRIBUTARY AREAS BUT NOT THE |
| | ACTUAL PRESSURES FOR COMPONENTS AND CLADDING. NOTE |
| | THERE WILL BE TWO DIFFERENT PRESSURE DUE TO A FLAT ROOF |
| | AS WELL AS A 5/12 PITCHED ROOF. IN BOTH CASES ZONES 1, |
| | 2 AND 3 WILL NEED TO BE ADDRESSED. |
| | FOR EXAMPLE FOR A FLAT ROOF IN ZONE 3, THE NEGATIVE |
| | PRESSURES WILL BE -89 WITH MULTIPLIERS OF 1.21 FOR |
| | EXPOSURE ???C???. |
| | |
| | 6) SHEET A-4.01 BUILDING SECTION# 1 INDICATES THE USE |
| | OF ICYNENE INSULATION AT THE CEILING LEVEL WHERE AS |
| | SECTION# 2 INDICATES THE ICYNENE INSULATION AT THE TOP |
| | CHORD OF THE TRUSS? 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED, DISCREPANCY. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |