2010-03-01 11:48:09****PROVISO****
 ****REVISION REQUIRED PRIOR TO FIRST INSPECTION***
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. EITHER REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE
 FOR EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE THAT THE
 CODE CHANGED EFFECTIVE MARCH 1, 2009. JUSTIFICATION FOR
 EXPOSURE B (RATHER THAN EXPOSURE C) SHALL BE SIGNED AND
 SEALED FROM THE ENGINEER OF RECORD AND WILL BE SUBJECT
 TO REVIEW.
  
 2. PRODUCT APPROVAL REQUIRED FOR THE PAN ROOF, FAC9B72.
 PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD FBC*106 PRIOR TO SUBMITTAL.
  
  
  