Plan Review Notes
Plan Review Notes For Permit 10020252
Permit Number 10020252
Review Stop P
Sequence Number 1
Notes
Date Text
2010-03-03 10:45:34DENIED
 REFERENCE;
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007CHAPTER 11
  
 1. SHT 1 THE BREAKROOM SINK SHALL BE ACCESSIBLE. SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCES
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED)
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
  
 1A. A 5 FOOT TURNING AREA IS REQUIRED IN THE BREAKROOM.
 SECTION 11-4.2.3.
  
 2. SHT P1 THE PRINTED NAME AND SIGNATURE OF THE PERSON
 DESIGNING THE PLUMBING SHALL BE ON THE SHEET. SECTION
 106.1.
  
 3. SHT P1 THE SANITARY RISER DIAGRAM DOES NOT MEET
 CODE. THE WASH MACHINE FIXTURE DRAIN SHALL CONNECT TO A
 BRANCH DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES IN
 DIAMETER PER SECTION 406.3 AND SHALL HAVE A STANDPIPE A
 MINIMUM 18 INCHES AND A MAXIMUM OF 48 INCHES ABOVE THE
 TRAP WEIR PER SECTION 802.4. ALSO THE PEDICURE CHAIR IS
 NOT VENTED. SECTIONS 901.2 & 901.2.1.
  
 4. SHT P1 THE WATER ISOMETRIC DOES NOT MEET CODE. WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE WASH MACHINE PER
 SECTION 604.9 AND SHALL BE LOCATED NEAR THE FIXTURE IN
 AN "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201. --
 SHOW ALL PIPE SIZES FOR THE WATER PIPING, AS WELL AS
 ALL PIPING TO THE PEDICURE CHAIR & THE SHAMPOO SINKS.
 SECTION 106.3.5.1.3.
  
 5. SHT P1 WATER ISOMETRIC, A FULL OPEN VALVE IS
 REQUIRED ON THE WATER SUPPLY PIPE TO THE WATER HEATER
 PER SECTION 606.2(7) AND THERMAL EXPANSION CONTROL IS
 REQUIRED PER 607.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved