| 2010-02-18 13:24:21 | *DENIED ** |
| | |
| | 1) NOTE: PLANS ARE REQUIRED TO CONTAIN CODES FOR DESIGN |
| | BASED ON THE APPLICATION DATE. |
| | ALL PERMIT APPLICATIONS AFTER OCTOBER 1ST, 2009 SHALL |
| | BE UNDER THE FOLLOWING ADOPTED CODES. |
| | 2008 NFPA-70 |
| | 2006 NFPA-101 |
| | 2007 FBC W/2009 SUPPLEMENTS. |
| | |
| | 2) NOTE: PLANS ARE MISSING A REQUIRED DESIGN |
| | PROFESSIONAL PER FS 471.003, 481.229, 489. ALL SHEETS |
| | EXCEPT ELECTRICAL CONTAIN A TITLE BLOCK FOR AN ENGINEER |
| | ALONG WITH SIGNATURE AND SEAL. HOWEVER ELECTRICAL |
| | SHEETS DO NOT CONTAIN ANY RESPONSIBLE DESIGNER AS |
| | REQUIRED. |
| | |
| | 3) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS AND |
| | COORDINATE WITH THE SUBMITTED PANEL SCHEDULE. LOADS ON |
| | CIRCUITS, WIRING, OVER CURRENT PROTECTION ETC NEEDS TO |
| | BE VERIFIED. |
| | PLEASE ALSO SEE 700.12F FOR CIRCUITING OF EMERGENCY |
| | LIGHTS TO LOCAL LIGHTING BRANCH CIRCUIT. |
| | 240.4,408.4, 310.16 ETC |
| | |
| | 3) NOTE: MISSING REQUIRED LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.AB.5. NOT ALL LIGHTING IS SHOWN |
| | ON PLANS AS EXISTING. PLEASE ALSO INCLUDE SPECIFIC |
| | FIXTURE INFORMATION AS REQUIRED TO VERIFY MINIMUM CODE |
| | COMPLIANCE. |
| | |
| | 4) NOTE: PLEASE SEE FBC 13-415.AB.1.1,.1.2, .1.3 FOR |
| | MISSING REQUIRED AUTOMATED LIGHTING CONTROLS. THIS IS A |
| | TENANT SPACE IN A BUILDING GREATER THAN 5K SQ FT. |
| | |
| | 5) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS THE LOAD |
| | SHOWN FOR SHOW WINDOW ONLY INCLUDES WHAT IS SHOWN AS |
| | FIVE LINEAR FT OF WINDOW. |
| | THE PLANS INDICATE TWO FIVE FOOT WINDOWS. PLEASE ADJUST |
| | LOADS. |
| | 220.43A, 220.14G |
| | |
| | 6) NOTE: PLEASE SEE 600.5 FOR REQUIRED MISSING SIGN |
| | CIRCUIT. PLEASE ALSO BE SURE TO ADD REQUIRED MINIMUM |
| | LOAD. |
| | |
| | 7) NOTE: PLEASE VERIFY THE METHOD OF EQUIPMENT |
| | GROUNDING FROM MAIN TO PANEL. |
| | 250.110,250.122 |
| | |
| | 8) NOTE: PLEASE SEE 422.13 WHICH REQUIRE STORAGE TYPE |
| | WATER HEATER LOADS TO BE FIGURED AT 125%. PLEASE SEE |
| | COMMENTARY WHICH WAS REVISED IN THE 2005 NEC AS THIS |
| | LOAD IS CONSIDERED CONTINUOUS. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |