2010-02-24 16:51:50BUILDING PLAN REVIEW
 PERMIT: 10020252
 ADD: 5707 S DIXIE # 3
 CONT: BROUGHTON CONSTRUCTION, LLC
 TEL: (561)644-4488
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 FEB. 24/ 2010
  
 1) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY: A) THE EDITION OF THE CODE UNDER WHICH
 THE PROJECT IS DESIGNED. PLEASE ALSO NOTE COMPLIANCE
 WITH THE 2007 FBC EXISTING BUILDING CODE AND SECTION
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) THE PERMIT APPLICATION INDICATES UNDER THE
 DESCRIPTION OF WORK THE CUTTING OF EXISTING SLAB.
 ADDITIONAL INFORMATION IS REQUIRED. 106.1.2
 ADMINISTRATIVE CODE.
 2A) PLANS FAIL TO INDICATE COMPLIANCE WITH TERMITE
 TREATMENT OF SOILS WHERE SLAB HAS BEEN CUT AND GRADE
 DISTURBED. 1816.1 TERMITE PROTECTION. TERMITE
 PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL-APPLIED PESTICIDES,
 BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT.
 2B) PLANS FAIL TO INDICATE WHAT TYPE OF MATERIALS WILL
 BE USED FOR THE NEW FLOOR SYSTEM. IF CONCRETE AND HOW
 THE NEW SECTION OF FLOOR WILL BE SECURED TO THE
 EXISTING FLOOR SLAB.
  
 3) SHEET# 1 THE DOORWAY LEADING INTO THE BREAK ROOM
 DOES NOT PROVIDE THE SIZE OF THE DOOR, NOR DOES THE
 PLANS INDICATE COMPLIANCE WITH SECTION:
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 4) SHEET# 1 INDICATES A 2HR FIRE SEPARATION REQUIRED.
 TENANT SEPARATION WALLS COVERED UNDER FBC-B 708 ONLY
 REQUIRE 1 HOUR SEPARATION. IF OCCUPANCY SEPARATION IS
 TO BE CONSIDERED WE WILL NEED TO SEE WHAT OCCUPANCIES
 ARE ON BOTH SIDES OF THIS TENANT TO DETERMINE THE HOUR
 RATING, TABLE 508.3.3. NOTE PLANS INDICATE 2 HR
 SEPARATION. AN AREA OF CONCERN THE MECHANICAL REVIEW
 WILL DWELL ON WILL BE VENTILATION REQUIREMENTS FOR THE
 MANICURE AND PEDICURE STATIONS, HOW WILL THE
 VENTILATION REQUIREMENTS BE MET AND WILL THE
 TENANT SEPARATION WALLS BE CUT FOR THE ADDITIONAL
 DUCTWORK. DETAILS WILL BE NEEDED POSSIBLY FOR
 PENETRATIONS OF FIRE RATED TENANT SEPARATION WALLS,
 PLEASE SEE FBC-B SECTION 712.
  
 5) PLEASE PROVIDE DETAILS FOR BREAK ROOM COUNTER AND
 SINK. SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE
 FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 6) PLANS FAIL TO INDICATE THE LOCATION OF THE PORTABLE
 FIRE EXTINGUISHER. FBC-B 906.1 GENERAL. PORTABLE FIRE
 EXTINGUISHERS SHALL BE PROVIDED IN OCCUPANCIES AND
 LOCATIONS AS REQUIRED BY THE FLORIDA FIRE PREVENTION
 CODE.
  
 7) PLEASE PROVIDE COMPLIANCE WITH: TABLE 803.3 MINIMUM
 INTERIOR FINISH CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS BASED ON
 OCCUPANCY.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  