| Plan Review Notes For Permit 10020240 |
| Permit Number |
10020240 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-02-22 12:34:04 | TEMP FAILED, NEW PLANS TO BE SUBMITTED. | | | SPOKEN TO GC, AND ENGINEER | | | #2 SEC FOR 300AMP SERVICE NOT PERMITTED. 240.4,310.16 | | | GEC TOO SMALL. 250.66 |
|