| 2010-02-22 14:03:38 | UNDERGROUND STORAGE TANK (UST) | | | 3031 OKEECHOBEE BOULEVARD | | | PERMIT # 10020238 | | | | | | 1. THE REMOVAL AND INSTALLATION OF THE OLD AND NEW | | | UNDERGROUND STORAGE TANKS SHALL COMPLY WITH NFPA 30 AND | | | NFPA 30A. | | | | | | 2. COULD NOT LOCATE EXISTING FUEL DISPENSING PUMPS AND | | | EMERGENCY DISCONNECT TO BE USED WITH THE NEW | | | UNDERGROUND STORAGE TANK. | | | | | | 3. THE REMOVAL OF THE EXISTING FUEL TANK AND | | | APPURTENANT EQUIPMENT MUST BE DONE SAFELY AND IN | | | ACCORDANCE WITH RECOGNIZED SAFETY PRACTICES. | | | | | | 4. PLEASE PROVIDE PRODUCT DATA ON THE PROPOSED | | | UNDERGROUND STORAGE TANK. | | | | | | 5. PLEASE EXPLAIN HOW THE EMERGENCY DISCONNECT FOR THE | | | FUEL STORAGE TANK WILL BE IDENTIFIED. | | | | | | 6. PLEASE INDICATE APPROPRIATE THIRD-PARTY LISTINGS FOR | | | THE UNDERGROUND STORAGE TANK AND APPURTENANT EQUIPMENT. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|