Plan Review Notes
Plan Review Notes For Permit 10020238
Permit Number 10020238
Review Stop E
Sequence Number 1
Notes
Date Text
2010-02-17 14:50:14*DENIED **
  
 1) NOTE: PLANS SHALL CONTAIN MINIMUM ADOPTED CODES.
 PLANS MAY NOT STATE * LATEST EDITION*. ALL PERMIT
 APPLICATIONS AFTER OCTOBER 1ST, 2009 SHALL BE UNDER THE
 2008 NEC.
 NO OTHER CODE EDITIONS WERE SHOWN.
  
 2) NOTE: NO CONDUCTORS, WIRING SIZES, OR CONDUIT
 INFORMATION IS SHOWN ON PLANS.
 310.16,240.4, SEE ALL OF NEC 514.,514.4,514.7,514.8
 CAN NOT REVIEW FOR CODE COMPLIANCE OF MINIMUM
 CONDUCTORS, CIRCUITING ETC WITH THE INFORMATION NOT
 SHOWN ON THE PLANS.
  
 3) NOTE: PLEASE SHOWN NEW OR EXISTING LOCATION FOR
 EMERGENCY SHUT OFF PER 514.11A,B,C.
  
 4) NOTE: PLEASE SEE 514.16 FOR GROUNDING REQUIREMENTS.
  
  