| Plan Review Notes For Permit 10020238 |
| Permit Number |
10020238 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-02-17 14:50:14 | *DENIED ** | | | | | | 1) NOTE: PLANS SHALL CONTAIN MINIMUM ADOPTED CODES. | | | PLANS MAY NOT STATE * LATEST EDITION*. ALL PERMIT | | | APPLICATIONS AFTER OCTOBER 1ST, 2009 SHALL BE UNDER THE | | | 2008 NEC. | | | NO OTHER CODE EDITIONS WERE SHOWN. | | | | | | 2) NOTE: NO CONDUCTORS, WIRING SIZES, OR CONDUIT | | | INFORMATION IS SHOWN ON PLANS. | | | 310.16,240.4, SEE ALL OF NEC 514.,514.4,514.7,514.8 | | | CAN NOT REVIEW FOR CODE COMPLIANCE OF MINIMUM | | | CONDUCTORS, CIRCUITING ETC WITH THE INFORMATION NOT | | | SHOWN ON THE PLANS. | | | | | | 3) NOTE: PLEASE SHOWN NEW OR EXISTING LOCATION FOR | | | EMERGENCY SHUT OFF PER 514.11A,B,C. | | | | | | 4) NOTE: PLEASE SEE 514.16 FOR GROUNDING REQUIREMENTS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|