| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-03-09 12:03:39 | *****PROVISO***** | | | | | | PLAN SHEET 1 OF 5 STAMPED, INITIALED, AND DATED UNDER | | | THE FOLLOWING SPECIFIC CONDITIONS: | | | | | | 1. SHOW THE LOCATION OF THE 2A10BC RATED FIRE | | | EXTINGUISHERS WHICH SATIFIES THE 75' TRAVEL DISTANCES. | | | | | | 2. PROVIDE TRAVEL DISTANCE TO EXITS AS PER LIFE SAFETY | | | CODE - NFPA 101: 16.2.6 - 2006 EDITION. | | | | | | 3. SPECIFY THE INTERIOR WALL AND CEILING FINISH | | | MATERIALS AS PER THE LIFE SAFETY CODE - NFPA 101: | | | 16.3.3.2 - 2006 EDITION. | | | | | | 4. PROVIDE THE DOOR SCHEDULE ON THE APPROPIATE PLAN | | | SHEET. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|