| 2010-02-23 07:28:32 | DENIED |
| | REFERENCE: |
| | FBC-2007 EXISTING BUILDING |
| | FBC-2007 PLUMBING |
| | FBC-2007 BUILDING |
| | FBC-2007 CHAPTER 11 |
| | |
| | 1. PER SECTION 906.1 ACCESSIBILITY IN PORTIONS OF |
| | BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE |
| | FLORIDA BUILDING CODE, BUILDING. PLEASE SHOW |
| | COMPLIANCE. |
| | |
| | 2. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER |
| | TABLES 1004.1.1 & 403.1. SHOW THE OCCUPANCY LOAD OF |
| | EACH SECTION OF EACH AREA INCLUDING THE OCCUPANCY LOAD |
| | OF THE PLAN AREA/STAGE AT 5 NET, (WORST CASE |
| | OCCUPANCY). -- A SERVICE SINK IS REQUIRED PER TABLE |
| | 403.1. PLEASE INDICATE THE LOCATION OF THE REQUIRED |
| | FIXTURE. |
| | |
| | 3. SHT 1 OF 5 INDICATES DAYCARE CLASSROOM AREA AT 4,205 |
| | S.F., BUT ADDITION OF ALL 9 CLASSROOMS ONLY ADDS UP TO |
| | 2,948 S.F. PLEASE CLARIFY. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |