| Plan Review Notes For Permit 10020159 |
| Permit Number |
10020159 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-03-01 09:55:16 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | SUBMITTE PLANS REVIEWED FOR COMPLIANCE WITH THE | | | FOLLOWING: | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | NO MECHNAICAL SCOPE OF WORK IS PROPOSED ON THE | | | SUBMITTED PLANS. HOWEVER, A CHANGE OF OCCUPANCY | | | CLASSIFICATION REQUIRES THAT COMPLIANCE WITH THE | | | VENTILATION REQUIREMENTS FOR THE NEW OCCUPANCY BE | | | DEMONSTRATED IN ACCORDANCE WITH FBC-EB SECTION 909.1. | | | PROVIDE SPACE-BY-SPACE VENTILATION CALCULATIONS BASED | | | ON FBC-M TABLE 403.3 OR ASHRAE 62.1-2004 TABLE 6-1. A | | | TEST AND BALANCE REPORT MAY BE SUBMITTED TO DEMONSTRATE | | | THE CURRENT VENTIALTION SYSTEM COMPLIES WITH THE | | | VENTILATION RATE REQUIREMENTS OF THE NEW OCCUPANCY OR A | | | PLAN SHALL BE SUBMITTED TO SHOW HOW COMPLIANCE WILL BE | | | ACHIEVED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|