2010-03-01 09:55:16REVIEW #: 1ST
 ACTION: DENIED
  
 SUBMITTE PLANS REVIEWED FOR COMPLIANCE WITH THE
 FOLLOWING:
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NO MECHNAICAL SCOPE OF WORK IS PROPOSED ON THE
 SUBMITTED PLANS. HOWEVER, A CHANGE OF OCCUPANCY
 CLASSIFICATION REQUIRES THAT COMPLIANCE WITH THE
 VENTILATION REQUIREMENTS FOR THE NEW OCCUPANCY BE
 DEMONSTRATED IN ACCORDANCE WITH FBC-EB SECTION 909.1.
 PROVIDE SPACE-BY-SPACE VENTILATION CALCULATIONS BASED
 ON FBC-M TABLE 403.3 OR ASHRAE 62.1-2004 TABLE 6-1. A
 TEST AND BALANCE REPORT MAY BE SUBMITTED TO DEMONSTRATE
 THE CURRENT VENTIALTION SYSTEM COMPLIES WITH THE
 VENTILATION RATE REQUIREMENTS OF THE NEW OCCUPANCY OR A
 PLAN SHALL BE SUBMITTED TO SHOW HOW COMPLIANCE WILL BE
 ACHIEVED.
  