Plan Review Notes
Plan Review Notes For Permit 10020159
Permit Number 10020159
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-02-07 23:37:00*****DENIED*****
  
 AS THIS IS A CHANGE OF OCCUPANCY FROM AN "EXISTING
 ASSEMBLY OCCUPANCY " TO A "NEW DAY CARE OCCUPANCY" ,
 CHAPTER 16 OF NFPA 101 - LIFE SAFETY CODE - 2006
 EDITION SHALL BE REFERENCED.
  
 1. THE REQUIREMENTS OF 16.2.11 SHALL BE MET AS IT
 RELATES TO SPECIAL MEANS OF EGRESS FEATURES - WINDOWS
 FOR RESCUE.
  
 2. SHOW THE LOCATION OF THE EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHERS ON THE APPROPIATE PLAN
 SHEET.
  
 3. AS PER 16.2.6, PROVIDE TRAVEL DISTANCE TO EXITS.
  
 4. AS PER 16.3.3.2, SPECIFY THE INTERIOR WALL AND
 CEILING FINISH MATERIALS.
  
 5. PLANS SHOW NO DOOR DETAIL. BE REMINDED THAT : *
 EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS CAN
 OPEN THE DOOR FROM THE INSIDE OF THE CLOSET
 (16.2.2.2.4) ; * EVERY BATHROOM DOOR LOCK SHALL BE
 DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE
 OUTSIDE BY AN OPENING DEVICE THAT SHALL BE READILY
 ACCESSIBLE TO THE STAFF (16.2.2.2.5) .
  
 6. SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY
 CLIENTS (16.5.1.2) .
  
 7. ON SHEET 2, IT IS NOTED THAT "ACCESS TO THE SECOND
 LEVEL TO BE 100% CLOSED OFF", HOWEVER SHEET 4 APPEARS
 TO INDICATE THAT THE SECOND LEVEL WILL BE UTILIZED IN
 SOME CAPACITY. IN ADDITION THE SUBMITTED FIRE ALARM
 PLAN (PERMIT #09120456) SHOWS DEVICES TO BE INSTALLED
 IN THE OFFICES, CONFERENCE ROOM, MEETING ROOM, AND THE
 KITCHEN ON THE SECOND FLOOR. PLEASE EXPLAIN THIS
 DISCREPANCY.
  
 8. WILL THE KITCHEN/COOKING FACILTIES BE USED?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722