| 2010-02-07 23:37:00 | *****DENIED***** |
| | |
| | AS THIS IS A CHANGE OF OCCUPANCY FROM AN "EXISTING |
| | ASSEMBLY OCCUPANCY " TO A "NEW DAY CARE OCCUPANCY" , |
| | CHAPTER 16 OF NFPA 101 - LIFE SAFETY CODE - 2006 |
| | EDITION SHALL BE REFERENCED. |
| | |
| | 1. THE REQUIREMENTS OF 16.2.11 SHALL BE MET AS IT |
| | RELATES TO SPECIAL MEANS OF EGRESS FEATURES - WINDOWS |
| | FOR RESCUE. |
| | |
| | 2. SHOW THE LOCATION OF THE EXIT LIGHTS, EMERGENCY |
| | LIGHTS, AND FIRE EXTINGUISHERS ON THE APPROPIATE PLAN |
| | SHEET. |
| | |
| | 3. AS PER 16.2.6, PROVIDE TRAVEL DISTANCE TO EXITS. |
| | |
| | 4. AS PER 16.3.3.2, SPECIFY THE INTERIOR WALL AND |
| | CEILING FINISH MATERIALS. |
| | |
| | 5. PLANS SHOW NO DOOR DETAIL. BE REMINDED THAT : * |
| | EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS CAN |
| | OPEN THE DOOR FROM THE INSIDE OF THE CLOSET |
| | (16.2.2.2.4) ; * EVERY BATHROOM DOOR LOCK SHALL BE |
| | DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE |
| | OUTSIDE BY AN OPENING DEVICE THAT SHALL BE READILY |
| | ACCESSIBLE TO THE STAFF (16.2.2.2.5) . |
| | |
| | 6. SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| | CLIENTS (16.5.1.2) . |
| | |
| | 7. ON SHEET 2, IT IS NOTED THAT "ACCESS TO THE SECOND |
| | LEVEL TO BE 100% CLOSED OFF", HOWEVER SHEET 4 APPEARS |
| | TO INDICATE THAT THE SECOND LEVEL WILL BE UTILIZED IN |
| | SOME CAPACITY. IN ADDITION THE SUBMITTED FIRE ALARM |
| | PLAN (PERMIT #09120456) SHOWS DEVICES TO BE INSTALLED |
| | IN THE OFFICES, CONFERENCE ROOM, MEETING ROOM, AND THE |
| | KITCHEN ON THE SECOND FLOOR. PLEASE EXPLAIN THIS |
| | DISCREPANCY. |
| | |
| | 8. WILL THE KITCHEN/COOKING FACILTIES BE USED? |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |