2010-02-24 10:14:20** DENIED **
  
  
 1) NOTE: THE ELECTRICAL SCOPE/WORK DONE WITHOUT PERMITS
 MUST BE INCLUDED WITH THE APPLIED SCOPE OF WORK. THE
 LIGHTING SHOWN ON PLANS W IS NOT ON ANY FILE RECORD AS
 BEING PERMITTED MUST BE INCLUDED AND MEET CODE.
  
 PLEASE SEE FBC 13-415.AB.5 FOR LIGHTING PERFORMANCE
 CALCULATIONS. THE AMOUNT OF LIGHTING IN SOME AREAS
 EXCEEDS LIMITS PERMITTED BY CODE.
 A FIELD INSPECTION/EVALUATION MAY BE REQUIRED TO VERIFY
 CURRENT CONDITIONS.
  
 2) NOTE: NO CONTROLS SHOWN FOR NEW EXHAUST FANS.
 300, 310.16
 SEE MECHANICAL CODE FOR REQUIRED CONTROLS IN MECHANICAL
 REVIEW.
  
 3) NOTE: NO INFORMATION ON PLANS FOR ACCESSIBLE
 ELECTRICAL PANELS TO CONTAIN LOCKS ON COVERS AND CHILD
 TAMPER RESISTANT RECEPTACLES.
 NFPA-101 16.5.1
  
 ** SEE FIRE REVIEW COMMENTS WITH RESPECT TO SEPARATION
 WALL FROM MAIN ELECTRICAL ROOM TO THE OTHER AREAS OF
 BUILDING.
  
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717