| 2010-02-22 12:53:00 | BUILDING PLAN REVIEW |
| | PERMIT: 10020159 |
| | ADD: 854 CONNISTON RD |
| | CONT: CATOE CONSTRUCTIOJN |
| | TEL: (561)719-6395 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING REVIEW: |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | |
| | 1) SHEET# 1 EXISTING STAGE AND RAMP: |
| | 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER THAN |
| | 6" OR A HORIZONTAL PROJECTION GREATER THAN 72", THEN IT |
| | SHALL HAVE HANDRAILS ON BOTH SIDES. |
| | |
| | 2) SHEET# 2, |
| | FLORIDA BUILDING CODE BUILDING: 302.1 GENERAL. |
| | STRUCTURES OR PORTIONS OF STRUCTURES SHALL BE |
| | CLASSIFIED WITH RESPECT TO OCCUPANCY . |
| | 2ND FLOOR STORAGE OCCUPANCY: |
| | 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. IT |
| | SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT, |
| | PROPRIETOR OR OCCUPANT OF GROUP S AND GROUP F |
| | OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR |
| | LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT |
| | ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD |
| | CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY |
| | AN AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING THE |
| | SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER |
| | SQ FT. THE |
| | COMPUTATIONS & AFFIDAVIT SHALL BE FILED AS A PERMANENT |
| | RECORD OF THE BLDG DEPT. |
| | |
| | 110.4.3. |
| | SIGNS REQUIRED. IN EVERY BUILDING OR PART OF A BUILDING |
| | USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS PURPOSES, THE |
| | SAFE FLOOR LOADS, AS REVIEWED BY THE BUILDING OFFICIAL |
| | ON THE PLAN, SHALL BE MARKED ON PLATES OF APPROVED DE |
| | SIGN WHICH SHALL BE SUPPLIED & SECURELY AFFIXED BY THE |
| | OWNER OF THE BUILDING IN A CONSPICUOUS PLACE IN EACH |
| | STORY TO WHICH THEY RELATE. SUCH PLATES SHALL NOT BE |
| | REMOVED OR DEFACED, & IF LOST, REMOVED THE OWNER OF THE |
| | BUILDING SHALL REPLACE THEM. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |