2010-02-11 14:28:58REDLINED/PROVISO*
  
  
  
 1) NOTE: PLEASE SEE FBC R313.1 AND 313.4 WHICH REQUIRES
 SMOKE ALARMS AND CARBON MONOXIDE ALARM(S) TO MEET
 CURRENTS CODES WHEN DOING WORK AS DESCRIBE IN THE
 SECTIONS NOTED. PLEASE ALSO SEE NFPA-72 11.5.1, 118.3
 FOR SMOKE ALARM LOCATIONS.
 THEY ARE REQUIRED INSIDE AND OUTSIDE ALL SLEEPING
 ROOMS, ON EACH LEVEL OF DWELLING AND CARBON MONOXIDE
 ALARMS.
 PLEASE ALSO SEE FS 553.885 FOR CARBON MONOXIDE ALARMS.
  
 2) NOTE: PLANS ARE MISSING REQUIRED DEDICATED BATH GFI
 (S) PER 210.52D, 210.11C3.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  