| Plan Review Notes For Permit 10020131 |
| Permit Number |
10020131 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-02-11 14:28:58 | REDLINED/PROVISO* | | | | | | | | | | | | 1) NOTE: PLEASE SEE FBC R313.1 AND 313.4 WHICH REQUIRES | | | SMOKE ALARMS AND CARBON MONOXIDE ALARM(S) TO MEET | | | CURRENTS CODES WHEN DOING WORK AS DESCRIBE IN THE | | | SECTIONS NOTED. PLEASE ALSO SEE NFPA-72 11.5.1, 118.3 | | | FOR SMOKE ALARM LOCATIONS. | | | THEY ARE REQUIRED INSIDE AND OUTSIDE ALL SLEEPING | | | ROOMS, ON EACH LEVEL OF DWELLING AND CARBON MONOXIDE | | | ALARMS. | | | PLEASE ALSO SEE FS 553.885 FOR CARBON MONOXIDE ALARMS. | | | | | | 2) NOTE: PLANS ARE MISSING REQUIRED DEDICATED BATH GFI | | | (S) PER 210.52D, 210.11C3. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|