2010-02-09 16:43:16RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- REVISE WIND LOAD DATA. ACCORDING TO SEC.
 R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE
 "C" NOT "B". REVISE AS REQUIRED.
 ALSO, REVISE THE DESIGN PRESSURES AS REQUIRED.
  
 2- PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS FOR THE
 CHIMNEY CONSTRUCTION. SPECIFY ALL FRAMING MEMBERS AND
 ALL CONNECTORS A TOP, BOTTOM AND ATTACHMENT TO THE
 EXISTING ROOF FRAMING SYSTEM TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES OF SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE. SECTION-CHIMNEY DOESN'T PROVIDE
 SPECIFICATIONS FOR HURRICANE STRAPS TO BE USED. NOTE
 STATING "PROVIDE GALV. METAL STRAP CONNECTORS FOR WIND
 LOADS 140MPH" IS NOT ENOUGH INFORMATION. ARCHITECT OF
 RECORD NEED TO SPECIFY ALL CONNECTORS REQUIRED TO
 RESIST ALL CALCULATED LOADS.
  
 3- PROVIDE COMPLETE SPECIFICATIONS/DETAILS FOR UL
 APPROVED PREFABRICATED FIREPLACE AND CHIMNEY TO BE
 INSTALLED AS REQUIRED BY SECTIONS R1004 AND R1005 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTES.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  