| 2010-02-09 16:43:16 | RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- REVISE WIND LOAD DATA. ACCORDING TO SEC. |
| | R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA |
| | RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE |
| | "C" NOT "B". REVISE AS REQUIRED. |
| | ALSO, REVISE THE DESIGN PRESSURES AS REQUIRED. |
| | |
| | 2- PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS FOR THE |
| | CHIMNEY CONSTRUCTION. SPECIFY ALL FRAMING MEMBERS AND |
| | ALL CONNECTORS A TOP, BOTTOM AND ATTACHMENT TO THE |
| | EXISTING ROOF FRAMING SYSTEM TO VERIFY COMPLIANCE WITH |
| | THE DESIGN PRESSURES OF SEC. R301 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. SECTION-CHIMNEY DOESN'T PROVIDE |
| | SPECIFICATIONS FOR HURRICANE STRAPS TO BE USED. NOTE |
| | STATING "PROVIDE GALV. METAL STRAP CONNECTORS FOR WIND |
| | LOADS 140MPH" IS NOT ENOUGH INFORMATION. ARCHITECT OF |
| | RECORD NEED TO SPECIFY ALL CONNECTORS REQUIRED TO |
| | RESIST ALL CALCULATED LOADS. |
| | |
| | 3- PROVIDE COMPLETE SPECIFICATIONS/DETAILS FOR UL |
| | APPROVED PREFABRICATED FIREPLACE AND CHIMNEY TO BE |
| | INSTALLED AS REQUIRED BY SECTIONS R1004 AND R1005 OF |
| | 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTES. |
| | NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| | |