| Plan Review Notes For Permit 10020007 |
| Permit Number |
10020007 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-02-09 09:44:03 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. THE FLOOR PLAN SHOWS INSWING DOORS, PRODUCT | | | APPROVALS ARE FOR OUTSWING DOORS. EITHER REVISE THE | | | FLOOR PLAN, PROVIDE PRODUCT APPROVALS FOR INSWING | | | DOORS, OR | | | | | | 2. PROVIDE A SITE PLAN TO SHOW HOW OUTSWING DOORS WILL | | | AFFECT EGRESS TRAVEL. AN AERIAL MAY BE USED. | | | | | | 3. THE APPLICATION IS FOR TEN DOORS, BUT PAPA SHOWS | | | THIS BUILDING AS TWO SEPARATE PARCELS. ONE PERMIT | | | APPLICATION FOR EACH PARCEL IS REQUIRED. IF THIS PARCEL | | | HAS TEN UNITS, PLEASE SHOW THE UNITS ON THE SITE PLAN | | | OR SHOW THE PROPERTY LINE ON THE FLOOR PLAN. | | | | | | 4. VALUE IS TOO LOW. THE VALUE WILL BE ADJUSTED TO | | | $10,000 PER CONVERSATION WITH CONTRACTOR. VALUE HAS NOT | | | BEEN ADJUSTED AT THIS TIME BECAUSE, IF A SEPARATE | | | PERMIT IS REQUIRED, THE VALUE WOULD BE SPLIT AMONGST | | | THE TWO PERMITS ($5K EACH). | | | | | | 5. DOOR THRESHOLD NOT TO EXCEED 1/2", FBC11-4.13.8. | | | EITHER PROVIDE A SPEC SHEET FOR THE THRESHOLD OR THIS | | | WILL BE A PROVISO ITEM. | | | | | | | | | | | | | | | | | | |
|