Plan Review Notes
Plan Review Notes For Permit 10010548
Permit Number 10010548
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2010-11-08 16:25:42720 8TH STREET
 PERMIT #10010548
  
 REVIEW COMMENTS - FIRE
  
 1) SHEET C-3: WHY ARE THERE SO MANY VALVES BETWEEN THE
 TAPPING VALVE/SLEEVE AND THE INCOMING SERVICE RISER
 (GATE, BACKFLOW, PIV)? ABOVE GROUND CONTROL VALVES NEED
 TO BE SUPERVISED. PROVIDE CHECK VALVE FOR FIRE
 DEPARTMENT CONNECTION.
 11/8/10 - REVIEW COMMENT HAS BEEN SATISFIED. WJ
  
 2) SHEET LA-1: PER FFPC NFPA 1, SECTION 18.3.3.1 &
 18.3.4.2 NO GROWTH, VEGETATION ETC. IS ALLOWED WITHIN
 7'-6" (FRONT AND SIDES) OF FIRE PROTECTION DEVICES
 (FIRE DEPARTMENT CONNECTION). THE FIRE DEPARTMENT
 CONNECTION SHALL BE VISIBLE AT ALL TIMES.
 11/8/10 - REPEAT COMMENT. WJ
  
 3) SHEET LS1: ELEVATOR EQUIPMENT DOOR NOT PERMITTED TO
 OPEN INTO STAIR ENCLOSURE PER FFPC NFPA 101, SECTION
 7.1.3.2.1 (5).
 11/8/10 - REPEAT COMMENT. WJ
  
 4) SHEET LS1: ELEVATORS ARE NOT PERMITTED TO OPEN INTO
 A STAIR EXIT PER FFPC NFPA 101, SECTION 9.4.7.
 11/8/10 - REPEAT COMMENT. WJ
  
 5) SHEET LS1: AN EXIT ENCLOSURE SHALL NOT BE USED FOR
 ANY PURPOSE (LOBBY/RECEPTION) THAT HAS THE POTENTIAL TO
 INTERFERE WITH USE AS AN EXIT PER FFPC NFPA 101,
 SECTION 7.1.3.2.3.
 11/8/10 - REPEAT COMMENT. WJ
  
 6) SHEET LS1: ACCESS TO THE ENCLOSED USABLE SPACE BELOW
 THE STAIR SHALL NOT BE FROM WITHIN THE STAIR ENCLOSURE
 PER FFPC NFPA 101, SECTION 7.2.2.5.3.2.
 11/8/10 - REPEAT COMMENT. WJ
  
 7) SHEET LS1: PROVIDE ASSEMBLY OCCUPANT LOAD BASED UPON
 15 SQ.FT. NET PER PERSON FOR NON-FIXED SEATING IN
 ACCORDANCE WITH TABLE 7.3.1.2 OF FFPC NFPA 101 AND
 SECTION 12.7.9.2.2. DEDUCT TABLE AREAS AND EGRESS PATHS
 FROM AVAILABLE SQUARE FOOTAGE. MAINTAIN ADEQUATE AISLES
 TO REACH ALL EXITS SERVING THE ASSEMBLY SPACE.
 11/8/10 - REPEAT COMMENT. WJ
  
 8) SHEET EF101: WHY WAS THE VISIBLE NOTIFICATION
 APPLIANCE REMOVED FROM READING ROOM #103. THIS DEVICE
 IS REQUIRED.
 11/8/10 - REPEAT COMMENT. WJ
  
 9) SHEET EF101: PROVIDE TAMPER SWITCHES FOR CONTROL
 VALVES SHOWN ON CIVIL PLANS.
 11/8/10 - REPEAT COMMENT. WJ
  
 10) SHEET E401: PROVIDE NOTE AS TO HOW ELEVATOR POWER
 WILL BE SHUNTED IF SPRINKLER AT TOP OF SHAFT IS
 ACTIVATED.
 11/8/10 - REPEAT COMMENT. WJ
  
 11) SHEET EK103: PROVIDE AUDIBLE/VISIBLE NOTIFICATION
 OF HOOD SUPPRESSION SYSTEM ACTIVATION. TIE INTO FIRE
 ALARM SYSTEM.
 11/8/10 - REPEAT COMMENT. WJ
  
 12) SHEET FP101: PROVIDE AVAILABLE WATER SUPPLY DATA.
 11/8/10 - REPEAT COMMENT. WJ
  
 13) SHEET FP101: SHOP DRAWINGS CANNOT REQUIRE
 ENGINEER'S SIGN/SEAL PER FAC 61G15-32.002.
 11/8/10 - REPEAT COMMENT. WJ
  
 14) SHEET FP101: PROVIDE TAMPER SWITCH ON FLOOR CONTROL
 VALVES.
 11/8/10 - REVIEW COMMENT HAS BEEN SATISFIED. WJ
  
 15) SHEET FP101: PROVIDE CLOSELY SPACED SPRINKERS AND
 DRAFT STOPS AROUND CEILING OPENING ADJACENT TO STAIR #1
 PER NFPA 13, SECTION 8.14.4.1.
 11/8/10 - REVIEW COMMENT HAS BEEN SATISFIED ON FIRE
 PROTECTION DRAWINGS. ARCHITECTURAL PLANS TO SHOW
 18-INCH DEEP DRAFT STOPS. WJ
  
 16) SHEET FP701: CIVIL PLANS SHOW 6" BACKFLOW
 PREVENTER, A GATE VALVE AND A POST INDICATOR VALVE.
 COORDINATE VALVE QUANTITY AND SIZING BETWEEN
 ENGINEERING DISCIPLINES.
 11/8/10 - REPEAT COMMENT. WJ
  
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 561-805-6730