| Date |
Text |
| 2010-08-23 12:55:04 | FBC PLUMBING 2007 |
| | FBC GAS 2007 |
| | PLUMBING REVIEW #2 |
| | DENIED: |
| | |
| | FROM PREVIOUS REVIEW OK |
| | |
| | NEW |
| | |
| | 1. ICE MACHINE FLOOR SINK IS REQUIRED TO DRAIN TO |
| | SANITARY. |
| | FBC PLUMBING 1003.2 |
| | |
| | 2. THE WASHING MACHINE IS SHOWN IN GREASE LINE. IS |
| | THERE A SPECIAL REASON? OTHERWISE, THE WASHING MACHINE |
| | SHOULD BE ROUTED TO THE SANITARY. 1003.2 |
| | |
| | 3. IF THE STEAM TABLE IS CLEAR WATER ONLY TO HEAT |
| | CONTAINERS, THE WASTE IS REQUIRED TO GO TO THE |
| | SANITARY. 1003.2 |
| | |
| | 3. THE DISHWASHER WASTE IS REQUIRED TO BE THROUGH AN |
| | INDIRECT WASTE, SUCH AS A FLOOR SINK. |
| | 802.1.7 |
| | |
| | 4. PLEASE INCLUDE CALCULATIONS FOR ALL FLOW FROM THE |
| | KITCHEN GREASE LINE AND DETERMINE THE SIZE OF THE |
| | GREASE INTERSEPTOR/S. NOTE*** MORE THAN ONE GREASE |
| | INTERCEPTOR MAY BE REQUIRED, DEPENDING ON THE |
| | CALCULATED FLOW FROM ALL FIXTURES. PDI G101 METHODS MAY |
| | BE USED TO SIZE THE INTERCEPTOR/S. USING THIS METHOD A |
| | 1011 GALLON CAPACITY WOULD BE REQUIRED FOR A TYPICAL 3 |
| | COMPARTMENT SINK ALONE. THE CHART ON SHEET C-7 LOOKS TO |
| | BE FOR AN OIL SEPARATOR FOR GARAGES. THE TABLE |
| | 1003.3.4.1 IS CALLED FOR IN THE PLUMBING CODE. |
| | |
| | 5. SHEET P201 SHOWS CONDENSATE TO GROUND. FOR A SINGLE |
| | UNIT UNDER 5 TONS THIS WILL BE OK. MULTIPLE UNITS ARE |
| | REQUIRED TO BE CONVEYED TO AN APPROVED PLACE OF |
| | DISPOSAL SO AS NOT CAUSE A NUISANCE. |
| | FBC PLUMBING 314.2.1 |
| | |
| | NOTE*** SHEET P201 & KD101 A DEEP SEAL FOR FLOOR DRAINS |
| | IS NO LONGER PERMITTED. A TRAP PRIMER WHICH IS ALREADY |
| | SHOWN ON THE PLAN IS REQUIRED. |
| | FBC 2007 PLUMBING 1002.4 |
| | |
| | |