2010-08-23 12:55:04FBC PLUMBING 2007
 FBC GAS 2007
 PLUMBING REVIEW #2
 DENIED:
  
 FROM PREVIOUS REVIEW OK
  
 NEW
  
 1. ICE MACHINE FLOOR SINK IS REQUIRED TO DRAIN TO
 SANITARY.
 FBC PLUMBING 1003.2
  
 2. THE WASHING MACHINE IS SHOWN IN GREASE LINE. IS
 THERE A SPECIAL REASON? OTHERWISE, THE WASHING MACHINE
 SHOULD BE ROUTED TO THE SANITARY. 1003.2
  
 3. IF THE STEAM TABLE IS CLEAR WATER ONLY TO HEAT
 CONTAINERS, THE WASTE IS REQUIRED TO GO TO THE
 SANITARY. 1003.2
  
 3. THE DISHWASHER WASTE IS REQUIRED TO BE THROUGH AN
 INDIRECT WASTE, SUCH AS A FLOOR SINK.
 802.1.7
  
 4. PLEASE INCLUDE CALCULATIONS FOR ALL FLOW FROM THE
 KITCHEN GREASE LINE AND DETERMINE THE SIZE OF THE
 GREASE INTERSEPTOR/S. NOTE*** MORE THAN ONE GREASE
 INTERCEPTOR MAY BE REQUIRED, DEPENDING ON THE
 CALCULATED FLOW FROM ALL FIXTURES. PDI G101 METHODS MAY
 BE USED TO SIZE THE INTERCEPTOR/S. USING THIS METHOD A
 1011 GALLON CAPACITY WOULD BE REQUIRED FOR A TYPICAL 3
 COMPARTMENT SINK ALONE. THE CHART ON SHEET C-7 LOOKS TO
 BE FOR AN OIL SEPARATOR FOR GARAGES. THE TABLE
 1003.3.4.1 IS CALLED FOR IN THE PLUMBING CODE.
  
 5. SHEET P201 SHOWS CONDENSATE TO GROUND. FOR A SINGLE
 UNIT UNDER 5 TONS THIS WILL BE OK. MULTIPLE UNITS ARE
 REQUIRED TO BE CONVEYED TO AN APPROVED PLACE OF
 DISPOSAL SO AS NOT CAUSE A NUISANCE.
 FBC PLUMBING 314.2.1
  
 NOTE*** SHEET P201 & KD101 A DEEP SEAL FOR FLOOR DRAINS
 IS NO LONGER PERMITTED. A TRAP PRIMER WHICH IS ALREADY
 SHOWN ON THE PLAN IS REQUIRED.
 FBC 2007 PLUMBING 1002.4
  
  