2010-08-18 15:50:15*****REVIEW COMMENTS - FIRE*****
  
 1) SHEET C-3: WHY ARE THERE SO MANY VALVES BETWEEN THE
 TAPPING VALVE/SLEEVE AND THE INCOMING SERVICE RISER
 (GATE, BACKFLOW, PIV)? ABOVE GROUND CONTROL VALVES NEED
 TO BE SUPERVISED. PROVIDE CHECK VALVE FOR FIRE
 DEPARTMENT CONNECTION.
  
 2) SHEET LA-1: PER FFPC NFPA 1, SECTION 18.3.3.1 &
 18.3.4.2 NO GROWTH, VEGETATION ETC. IS ALLOWED WITHIN
 7'-6" OF FIRE PROTECTION DEVICES (FIRE DEPARTMENT
 CONNECTION). THE FIRE DEPARTMENT CONNECTION SHALL BE
 VISIBLE AT ALL TIMES.
  
 3) SHEET LS1: ELEVATOR EQUIPMENT DOOR NOT PERMITTED TO
 OPEN INTO STAIR ENCLOSURE PER FFPC NFPA 101, SECTION
 7.1.3.2.1 (5).
  
 4) SHEET LS1: ELEVATORS ARE NOT PERMITTED TO OPEN INTO
 A STAIR EXIT PER FFPC NFPA 101, SECTION 9.4.7.
  
 5) SHEET LS1: AN EXIT ENCLOSURE SHALL NOT BE USED FOR
 ANY PURPOSE (LOBBY/RECEPTION) THAT HAS THE POTENTIAL TO
 INTERFERE WITH USE AS AN EXIT PER FFPC NFPA 101,
 SECTION 7.1.3.2.3.
  
 6) SHEET LS1: ACCESS TO THE ENCLOSED USABLE SPACE BELOW
 THE STAIR SHALL NOT BE FROM WITHIN THE STAIR ENCLOSURE
 PER FFPC NFPA 101, SECTION 7.2.2.5.3.2.
  
 7) SHEET LS1: PROVIDE ASSEMBLY OCCUPANT LOAD BASED UPON
 15 SQ.FT. NET PER PERSON FOR NON-FIXED SEATING IN
 ACCORDANCE WITH TABLE 7.3.1.2 OF FFPC NFPA 101 AND
 SECTION 12.7.9.2.2. DEDUCT TABLE AREAS AND EGRESS PATHS
 FROM AVAILABLE SQUARE FOOTAGE. MAINTAIN ADEQUATE AISLES
 TO REACH ALL EXITS SERVING THE ASSEMBLY SPACE.
  
 8) SHEET EF101: WHY WAS THE VISIBLE NOTIFICATION
 APPLIANCE REMOVED FROM READING ROOM #103. THIS DEVICE
 IS REQUIRED.
  
 9) SHEET EF101: PROVIDE TAMPER SWITCHES FOR CONTROL
 VALVES SHOWN ON CIVIL PLANS.
  
 10) SHEET E401: PROVIDE NOTE AS TO HOW ELEVATOR POWER
 WILL BE SHUNTED IF SPRINKLER AT TOP OF SHAFT IS
 ACTIVATED.
  
 11) SHEET EK103: PROVIDE AUDIBLE/VISIBLE NOTIFICATION
 OF HOOD SUPPRESSION SYSTEM ACTIVATION. TIE INTO FIRE
 ALARM SYSTEM.
  
 12) SHEET FP101: PROVIDE AVAILABLE WATER SUPPLY DATA.
  
 13) SHEET FP101: SHOP DRAWINGS DO NOT REQUIRE
 ENGINEER'S SIGN/SEAL PER FAC 61G15-32.002.
  
 14) SHEET FP101: PROVIDE TAMPER SWITCH ON FLOOR CONTROL
 VALVES.
  
 15) SHEET FP101: PROVIDE CLOSELY SPACED SPRINKERS AND
 DRAFT STOPS AROUND CEILING OPENING ADJACENT TO STAIR #1
 PER NFPA 13, SECTION 8.14.4.1.
  
 16) SHEET FP701: CIVIL PLANS SHOW 6" BACKFLOW
 PREVENTER, A GATE VALVE AND A POST INDICATOR VALVE.
 COORDINATE VALVE QUANTITY AND SIZING BETWEEN
 ENGINEERING DISCIPLINES.
  
  
 MIKE CARSILLO, BATTALION CHIEF/FIRE MARSHAL
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW