| 2010-08-18 15:50:15 | *****REVIEW COMMENTS - FIRE***** |
| | |
| | 1) SHEET C-3: WHY ARE THERE SO MANY VALVES BETWEEN THE |
| | TAPPING VALVE/SLEEVE AND THE INCOMING SERVICE RISER |
| | (GATE, BACKFLOW, PIV)? ABOVE GROUND CONTROL VALVES NEED |
| | TO BE SUPERVISED. PROVIDE CHECK VALVE FOR FIRE |
| | DEPARTMENT CONNECTION. |
| | |
| | 2) SHEET LA-1: PER FFPC NFPA 1, SECTION 18.3.3.1 & |
| | 18.3.4.2 NO GROWTH, VEGETATION ETC. IS ALLOWED WITHIN |
| | 7'-6" OF FIRE PROTECTION DEVICES (FIRE DEPARTMENT |
| | CONNECTION). THE FIRE DEPARTMENT CONNECTION SHALL BE |
| | VISIBLE AT ALL TIMES. |
| | |
| | 3) SHEET LS1: ELEVATOR EQUIPMENT DOOR NOT PERMITTED TO |
| | OPEN INTO STAIR ENCLOSURE PER FFPC NFPA 101, SECTION |
| | 7.1.3.2.1 (5). |
| | |
| | 4) SHEET LS1: ELEVATORS ARE NOT PERMITTED TO OPEN INTO |
| | A STAIR EXIT PER FFPC NFPA 101, SECTION 9.4.7. |
| | |
| | 5) SHEET LS1: AN EXIT ENCLOSURE SHALL NOT BE USED FOR |
| | ANY PURPOSE (LOBBY/RECEPTION) THAT HAS THE POTENTIAL TO |
| | INTERFERE WITH USE AS AN EXIT PER FFPC NFPA 101, |
| | SECTION 7.1.3.2.3. |
| | |
| | 6) SHEET LS1: ACCESS TO THE ENCLOSED USABLE SPACE BELOW |
| | THE STAIR SHALL NOT BE FROM WITHIN THE STAIR ENCLOSURE |
| | PER FFPC NFPA 101, SECTION 7.2.2.5.3.2. |
| | |
| | 7) SHEET LS1: PROVIDE ASSEMBLY OCCUPANT LOAD BASED UPON |
| | 15 SQ.FT. NET PER PERSON FOR NON-FIXED SEATING IN |
| | ACCORDANCE WITH TABLE 7.3.1.2 OF FFPC NFPA 101 AND |
| | SECTION 12.7.9.2.2. DEDUCT TABLE AREAS AND EGRESS PATHS |
| | FROM AVAILABLE SQUARE FOOTAGE. MAINTAIN ADEQUATE AISLES |
| | TO REACH ALL EXITS SERVING THE ASSEMBLY SPACE. |
| | |
| | 8) SHEET EF101: WHY WAS THE VISIBLE NOTIFICATION |
| | APPLIANCE REMOVED FROM READING ROOM #103. THIS DEVICE |
| | IS REQUIRED. |
| | |
| | 9) SHEET EF101: PROVIDE TAMPER SWITCHES FOR CONTROL |
| | VALVES SHOWN ON CIVIL PLANS. |
| | |
| | 10) SHEET E401: PROVIDE NOTE AS TO HOW ELEVATOR POWER |
| | WILL BE SHUNTED IF SPRINKLER AT TOP OF SHAFT IS |
| | ACTIVATED. |
| | |
| | 11) SHEET EK103: PROVIDE AUDIBLE/VISIBLE NOTIFICATION |
| | OF HOOD SUPPRESSION SYSTEM ACTIVATION. TIE INTO FIRE |
| | ALARM SYSTEM. |
| | |
| | 12) SHEET FP101: PROVIDE AVAILABLE WATER SUPPLY DATA. |
| | |
| | 13) SHEET FP101: SHOP DRAWINGS DO NOT REQUIRE |
| | ENGINEER'S SIGN/SEAL PER FAC 61G15-32.002. |
| | |
| | 14) SHEET FP101: PROVIDE TAMPER SWITCH ON FLOOR CONTROL |
| | VALVES. |
| | |
| | 15) SHEET FP101: PROVIDE CLOSELY SPACED SPRINKERS AND |
| | DRAFT STOPS AROUND CEILING OPENING ADJACENT TO STAIR #1 |
| | PER NFPA 13, SECTION 8.14.4.1. |
| | |
| | 16) SHEET FP701: CIVIL PLANS SHOW 6" BACKFLOW |
| | PREVENTER, A GATE VALVE AND A POST INDICATOR VALVE. |
| | COORDINATE VALVE QUANTITY AND SIZING BETWEEN |
| | ENGINEERING DISCIPLINES. |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF/FIRE MARSHAL |
| | & WESLEY JOLIN |
| | WPB FIRE PLAN REVIEW |
| | 561-805-6730 |