2010-08-17 07:31:34BUILDING PLAN REVIEW
 PERMIT: 10010548
 ADD: 706 8TH STREET
 CONT: YOUCHAK& YOUCHAK, INC.
 TEL: (561)371-5548
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 COMMENT # 7 THIS BUILDING HAS (3) THREE AREAS WITH FLAT
 ROOFED AREAS. ONE AREA HAS OVER A THREE FOOT HIGH
 PARAPET WHICH ELIMINATES THE CORNER ZONES (ZONE# 3).
 THE OTHER TWO AREAS IN DETAILS 3/A-5 AND A-A/A-7 OR
 DETAIL 1/A6 BOTH WILL REQUIRE ENHANCED FASTENING FOR
 ZONE# 3. THE STRUCTURAL SHEET S-5 FLAT ROOF INDICATES A
 PRESSURE OF -140.2.
  
 ROOFING PRODUCT APPROVAL SUBMITTED FOR FLAT ROOFS:
 FL 2948-R4/ 2004
 JOHN MANVILLE
 MODIFIED BITUMEN ROOF SYSTEM
 PAGE 5 OF 6. LIMITATION 5.6 MECHANICALLY ATTACHED
 INSULATION OR MEMBRANE OR STRIP-BONDED INSULATION
 ALLOWS FOR ENHANCED FASTENING IN ZONES 2 & 3 BY A
 QUALIFIED DESIGN PROFESSIONAL COMMONLY USED METHODS ARE
 RAS 117 AND FM LPDS 1-29.
 APPENDIX 1 PAGE 9OF 26
 SYSTEM NO. S-26 -112.5 (PSF).
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
  