| 2010-08-17 07:31:34 | BUILDING PLAN REVIEW |
| | PERMIT: 10010548 |
| | ADD: 706 8TH STREET |
| | CONT: YOUCHAK& YOUCHAK, INC. |
| | TEL: (561)371-5548 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING PROVISO: |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | COMMENT # 7 THIS BUILDING HAS (3) THREE AREAS WITH FLAT |
| | ROOFED AREAS. ONE AREA HAS OVER A THREE FOOT HIGH |
| | PARAPET WHICH ELIMINATES THE CORNER ZONES (ZONE# 3). |
| | THE OTHER TWO AREAS IN DETAILS 3/A-5 AND A-A/A-7 OR |
| | DETAIL 1/A6 BOTH WILL REQUIRE ENHANCED FASTENING FOR |
| | ZONE# 3. THE STRUCTURAL SHEET S-5 FLAT ROOF INDICATES A |
| | PRESSURE OF -140.2. |
| | |
| | ROOFING PRODUCT APPROVAL SUBMITTED FOR FLAT ROOFS: |
| | FL 2948-R4/ 2004 |
| | JOHN MANVILLE |
| | MODIFIED BITUMEN ROOF SYSTEM |
| | PAGE 5 OF 6. LIMITATION 5.6 MECHANICALLY ATTACHED |
| | INSULATION OR MEMBRANE OR STRIP-BONDED INSULATION |
| | ALLOWS FOR ENHANCED FASTENING IN ZONES 2 & 3 BY A |
| | QUALIFIED DESIGN PROFESSIONAL COMMONLY USED METHODS ARE |
| | RAS 117 AND FM LPDS 1-29. |
| | APPENDIX 1 PAGE 9OF 26 |
| | SYSTEM NO. S-26 -112.5 (PSF). |
| | |
| | JIM WITMER C. B. O. |