| Date |
Text |
| 2010-02-16 13:41:28 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW, #08050795: |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. SHTS 1 OF 2 IRRIGATION SHOW THE LOCATION OF THE |
| | CONTROLLER AND THE RAIN SENSOR. SECTION 106.1.2 & FS |
| | 373.62. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | |
| | 4. OK |
| | 5. OK |
| | |
| | 6. SHT 1 OF 15 SUBMIT CALCULATIONS FOR MINIMUM |
| | FACILITIES PER TABLES 1004.1.2 & 403.1. INDICATE IF |
| | EACH SPACE IS CONSENTRATED, STANDING SPACE OR |
| | UNCONSENTRATED. (EDUCATIONAL - MEETING ROOMS - WORKROOM |
| | - MULTIPURPOSE COMMUNITY ROOM). THE OCCUPANCY INDICATED |
| | 372 & 216 SHALL BE VERIFIED. |
| | ****RESPONSE NOTED, BUT THE FLOOR AREA IN SQUARE FOOT |
| | OCCUPANT SHALL REFLECT TABLE 1004.1.1 OF THE BUILDING |
| | CODE. RECHECK AREA AT THE LOBBY/RECEPTION AREA, (NET |
| | SF). THE MULTIPURPOSE ROOM SHALL BE 5 NET NOT 15 NET. |
| | THE OFFICE AREAS SHALL BE 100 GROSS NOT 3. THE |
| | EDUCATIONAL ROOM 20 NET. THE READING ROOM SHALL BE 50 |
| | NET OR 100 GROSS DEPENDING ON BOOK STACKS ETC. PLEASE |
| | RECHECK ALL AREAS. DEPENDING ON THE COMMENT RESPONSES, |
| | MORE COMMENTS MAY FOLLOW. |
| | |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | |
| | 12. SHT P401 SANITARY RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN AS THERE ARE OFFSETS IN THE PIPING SHOWN |
| | ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER |
| | DIAGRAM AS WELL AS THE BASE OF THE STACK TO TOILET |
| | ROOMS 223 & 224 DOES NOT REFLECT THE FLOOR PLAN. (RISER |
| | TURNS SOUTH & FLOOR PLAN TURNS NORTH). SECTION 106.1.1. |
| | PLEASE CORRELATE. |
| | ****RESPONSE NOTED, BUT THE COMMENT NOT ADDRESSED FOR |
| | THE OFFSETS AND THE BASE OF THE RISER TO TOILET ROOMS |
| | 223 & 224 IS NOT SHOWN ON THE FLOOR PLAN. |
| | |
| | 13. SHT P401 CONDENSATE RISER DIAGRAM THE PIPE SIZES DO |
| | NOT REFLECT THE FLOOR PLAN IN MANY AREAS. PLEASE |
| | CORRELATE AND SHOW ALL PIPE SIZES. ALSO THE CONDENSATE |
| | LINE DOWNSTREAM OF UNIT 1FC:6 IS SHOWN CONNECTING TO |
| | THE 2ND FLOOR CONDENSATE RISER ON THE RISER BUT NOT ON |
| | THE FLOOR PLAN. SECTION 106.1.1 & 314. |
| | ****RESPONSE NOTED, BUT SOME PIPE SIZES ARE STILL |
| | DIFFERENT AND SOME PIPE SIZES ARE NOT SHOWN. |
| | |
| | 14. SHT P401 WATER RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN IN ABOUT 7 OR 8 AREAS. THE STUB-OUTS FOR THE |
| | FIXTURES IN THE GANG BATHS ARE SHOWN TURNING THE WRONG |
| | WAY, (AWAY FROM THE FIXTURES), AND PIPING THE THE |
| | CEILING FOR BRANCH CONNECTIONS TO THE WATER MAINS DOES |
| | NOT RELFECT IN SOME AREAS. THE DRINKING FOUNTAIN |
| | SUPPLIES ARE NOT SHOWN ON THE RISER AS WELL AS THE |
| | SUPPLY LINES TO THE SHOWER AND A "BS" FOR THE SECOND |
| | FLOOR. SECTIONS 106.1.1 & 601.1. |
| | ****RESPONSE NOTED, BUT THE SHOWER SHOWN BETWEEN THE |
| | "BS" FIXTURES ON THE FLOOR PLAN IS SHOWN BEFORE THE |
| | FIRST BS FIXTURE ON THE RISER DIAGRAM. THE DRINKING |
| | FOUNTAINS AND ONE SINK SHOWN ON THE FLOOR PLAN FOR THE |
| | SECOND FLOOR ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE |
| | CORRELATE. |
| | |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | |
| | 21. SHT KP103 A SEPARATE GAS PERMIT IS REQUIRED. PLEASE |
| | SUPPLY THE FOLLOWING INFORMATION FOR GAS PERMIT |
| | APPROVAL: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. (CUT SECTIONS FROM THE METER TO THE |
| | FIRST RISER, AND THE DROP WITH THE VALVES AND UNIONS DO |
| | NOT INDICATE THE LENGTHS). |
| | ****RESPONSE NOTED, BUT THE DROP WITH THE VALVES & |
| | UNIONS DOES NOT INDICATE THE LENGTH. |
| | |
| | B. OK |
| | C. OK |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN |
| | COMMENT "21-A" ADDRESSED). |
| | ****RESPONSE NOTED, TO BE VERIFIED WHEN COMMENT 21-A IS |
| | ADDRESSED. |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | |
| | F. N/A |
| | G. N/A |
| | H. N/A |
| | I. N/A |
| | |
| | 22. OK |
| | |
| | ******NEW COMMENTS****** |
| | |
| | 1B. SHTS P101 FLOOR PLAN & P401 SANITARY ISOMETRIC |
| | RISER DIAGRAM. THE FLOOR DRAINS IN TOILET ROOMS 105 & |
| | 108 ARE NOT VENTED AS PIPED. SECTION 901.2. |
| | |
| | 2B. SHT PK103 CODE REFERENCE IN NOTE UNDER BUILDING GAS |
| | REQUIREMENT IS INDICATED AS FBC-2004. CODE IN EFFECT |
| | FOR THIS REVIEW IS FBC-2007. PLEASE UPDATE CODE |
| | REFERENCE. |
| | |
| | 3B. SHT PK103 PLEASE SUBMIT MANUF. SPECIFICATIONS FOR |
| | THE SECOND STAGE REGULATOR SHOWING LISTING/APPROVAL, |
| | MODEL NUMBER AND OUTLET CAPACITY. SECTIONS 410.1 & |
| | 410.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |