Plan Review Notes
Plan Review Notes For Permit 10010548
Permit Number 10010548
Review Stop P
Sequence Number 1
Notes
Date Text
2010-02-16 13:41:28DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW, #08050795:
  
 1. OK
 2. OK
  
 3. SHTS 1 OF 2 IRRIGATION SHOW THE LOCATION OF THE
 CONTROLLER AND THE RAIN SENSOR. SECTION 106.1.2 & FS
 373.62.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 4. OK
 5. OK
  
 6. SHT 1 OF 15 SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1004.1.2 & 403.1. INDICATE IF
 EACH SPACE IS CONSENTRATED, STANDING SPACE OR
 UNCONSENTRATED. (EDUCATIONAL - MEETING ROOMS - WORKROOM
 - MULTIPURPOSE COMMUNITY ROOM). THE OCCUPANCY INDICATED
 372 & 216 SHALL BE VERIFIED.
 ****RESPONSE NOTED, BUT THE FLOOR AREA IN SQUARE FOOT
 OCCUPANT SHALL REFLECT TABLE 1004.1.1 OF THE BUILDING
 CODE. RECHECK AREA AT THE LOBBY/RECEPTION AREA, (NET
 SF). THE MULTIPURPOSE ROOM SHALL BE 5 NET NOT 15 NET.
 THE OFFICE AREAS SHALL BE 100 GROSS NOT 3. THE
 EDUCATIONAL ROOM 20 NET. THE READING ROOM SHALL BE 50
 NET OR 100 GROSS DEPENDING ON BOOK STACKS ETC. PLEASE
 RECHECK ALL AREAS. DEPENDING ON THE COMMENT RESPONSES,
 MORE COMMENTS MAY FOLLOW.
  
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
  
 12. SHT P401 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN AS THERE ARE OFFSETS IN THE PIPING SHOWN
 ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER
 DIAGRAM AS WELL AS THE BASE OF THE STACK TO TOILET
 ROOMS 223 & 224 DOES NOT REFLECT THE FLOOR PLAN. (RISER
 TURNS SOUTH & FLOOR PLAN TURNS NORTH). SECTION 106.1.1.
 PLEASE CORRELATE.
 ****RESPONSE NOTED, BUT THE COMMENT NOT ADDRESSED FOR
 THE OFFSETS AND THE BASE OF THE RISER TO TOILET ROOMS
 223 & 224 IS NOT SHOWN ON THE FLOOR PLAN.
  
 13. SHT P401 CONDENSATE RISER DIAGRAM THE PIPE SIZES DO
 NOT REFLECT THE FLOOR PLAN IN MANY AREAS. PLEASE
 CORRELATE AND SHOW ALL PIPE SIZES. ALSO THE CONDENSATE
 LINE DOWNSTREAM OF UNIT 1FC:6 IS SHOWN CONNECTING TO
 THE 2ND FLOOR CONDENSATE RISER ON THE RISER BUT NOT ON
 THE FLOOR PLAN. SECTION 106.1.1 & 314.
 ****RESPONSE NOTED, BUT SOME PIPE SIZES ARE STILL
 DIFFERENT AND SOME PIPE SIZES ARE NOT SHOWN.
  
 14. SHT P401 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN IN ABOUT 7 OR 8 AREAS. THE STUB-OUTS FOR THE
 FIXTURES IN THE GANG BATHS ARE SHOWN TURNING THE WRONG
 WAY, (AWAY FROM THE FIXTURES), AND PIPING THE THE
 CEILING FOR BRANCH CONNECTIONS TO THE WATER MAINS DOES
 NOT RELFECT IN SOME AREAS. THE DRINKING FOUNTAIN
 SUPPLIES ARE NOT SHOWN ON THE RISER AS WELL AS THE
 SUPPLY LINES TO THE SHOWER AND A "BS" FOR THE SECOND
 FLOOR. SECTIONS 106.1.1 & 601.1.
 ****RESPONSE NOTED, BUT THE SHOWER SHOWN BETWEEN THE
 "BS" FIXTURES ON THE FLOOR PLAN IS SHOWN BEFORE THE
 FIRST BS FIXTURE ON THE RISER DIAGRAM. THE DRINKING
 FOUNTAINS AND ONE SINK SHOWN ON THE FLOOR PLAN FOR THE
 SECOND FLOOR ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE.
  
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
  
 21. SHT KP103 A SEPARATE GAS PERMIT IS REQUIRED. PLEASE
 SUPPLY THE FOLLOWING INFORMATION FOR GAS PERMIT
 APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (CUT SECTIONS FROM THE METER TO THE
 FIRST RISER, AND THE DROP WITH THE VALVES AND UNIONS DO
 NOT INDICATE THE LENGTHS).
 ****RESPONSE NOTED, BUT THE DROP WITH THE VALVES &
 UNIONS DOES NOT INDICATE THE LENGTH.
  
 B. OK
 C. OK
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN
 COMMENT "21-A" ADDRESSED).
 ****RESPONSE NOTED, TO BE VERIFIED WHEN COMMENT 21-A IS
 ADDRESSED.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 F. N/A
 G. N/A
 H. N/A
 I. N/A
  
 22. OK
  
 ******NEW COMMENTS******
  
 1B. SHTS P101 FLOOR PLAN & P401 SANITARY ISOMETRIC
 RISER DIAGRAM. THE FLOOR DRAINS IN TOILET ROOMS 105 &
 108 ARE NOT VENTED AS PIPED. SECTION 901.2.
  
 2B. SHT PK103 CODE REFERENCE IN NOTE UNDER BUILDING GAS
 REQUIREMENT IS INDICATED AS FBC-2004. CODE IN EFFECT
 FOR THIS REVIEW IS FBC-2007. PLEASE UPDATE CODE
 REFERENCE.
  
 3B. SHT PK103 PLEASE SUBMIT MANUF. SPECIFICATIONS FOR
 THE SECOND STAGE REGULATOR SHOWING LISTING/APPROVAL,
 MODEL NUMBER AND OUTLET CAPACITY. SECTIONS 410.1 &
 410.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  