| 2010-02-02 16:51:17 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW CYCLE COMMENTS FOR CONTINUITY. |
| | |
| | 1. OK |
| | |
| | 2. OK |
| | |
| | 3. OK |
| | |
| | 4. PAGES M101 AND M102: KEY NOTE #4 ON PAGE M101 CALLS |
| | FOR CARBON DIOXIDE DETECTORS FOR DEMAND CONTROL |
| | VENTILATION WHILE KEY NOTE #4 ON PAGE M102 CALLS FOR |
| | CARBON MONOXIDE DETECTORS. MAKE CORRECTIONS AND SHOW |
| | HOW THE REQUIRED RATE OF VENTILATION IS TO BE PROVIDED |
| | FOR THE SECOND FLOOR IN ACCORDANCE WITH FBCM SECTION |
| | 403. |
| | |
| | 5. OK |
| | |
| | 6. PAGE M102: THE 10 INCH ROUND DUCT PENETRATING THE |
| | CORRIDOR WALL AT ALCOVE 217 REQUIRES A SMOKE DAMPER IN |
| | ADDITION TO THE FIRE DAMPER SHOWN ON PLANS IN |
| | ACCORDANCE WITH FBCM 607.5.4. SHOW HOW THE SMOKE DAMPER |
| | IS TO BE ACTUATED IN ACCORDANCE WITH FBCM 607.3.2.1. |
| | |
| | 7. PAGE M102: OK. KITCHEN GREASE EXHAUST SYSTEM |
| | REQUIRES SEPARATE PLANS AND PERMIT APPLICATION. NO |
| | LONGER PART OF THIS REVIEW. |
| | |
| | 8. OK |
| | |
| | 9. OK |
| | |
| | 10. PAGE M202 DETAILS FOR ALL ROOF MOUNTED AND OUTDOOR |
| | EQUIPMENT AND APPLIANCES: DETAIL REFERENCES STRUCTURAL |
| | DRAWINGS. NO DETAIL FOR ROOF CURB INSTALLATION COULD BE |
| | FOUND IN STRUCTURAL DRAWINGS. ALSO, PROVIDE |
| | MANUFACTURER'S DATA FOR ALL OUTDOOR APPLIANCES SHOWING |
| | THEY ARE DESIGNED FOR WIND RESISTANCE PER FBCM 301.12. |
| | |
| | 11. OK |
| | |
| | 12. OK |
| | |
| | 13. OK. KITCHEN GREASE EXHAUST SYSTEM REQUIRES SEPARATE |
| | PLANS AND PERMIT APPLICATION. NO LONGER PART OF THIS |
| | REVIEW. |
| | |
| | 14. THE ENERGY CODE COMPLIANCE FOR SUBMITTED IS NO |
| | LONGER VALID AS OF MARCH 1, 2009. SUBMIT THE CORRECT |
| | METHOD A ENERGY CODE COMPLIANCE FORM FOR REVIEW. ALSO, |
| | COOLING LOAD CALCULATIONS SHALL BE APPENDED TO THE |
| | ENERGY CODE COMPLIANCE FORM IN ACCORDANCE WITH FBCB |
| | 13-407.AB.1. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |
| | RONALD J. REGUEIRO |
| | 561.805.6719 |
| | [email protected] |