Plan Review Notes
Plan Review Notes For Permit 10010548
Permit Number 10010548
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-04-05 08:29:30 
  
 1. THE FIRE DEPARTMENT CONNECTION (FDC) WILL REQUIRE
 KNOX LOCKING CAPS.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 HOOD,DUCT, AND FIRE SUPPRESSION SYSTEM.
  
 3. A ROOF DRAIN APPEARS IN EXIT # 2.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 ALARM SYSTEM.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER SYSTEM.
  
 6. THE FIRE DEPARTMENT CONNECTION SHOWN ON PAGE FP101
 DOES NOT MATCH C-3.
  
 7. IT APPEARS THAT NOT ALL PREVIOUS COMMENTS HAVE BEEN
 ADDRESSED.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION