| 2010-02-09 15:56:34 | *DENIED* |
| | |
| | ** ORIGINALLY REVIEWED UNDER EXPIRED PERMIT APPLICATION |
| | 08050795 |
| | |
| | |
| | 1) NOTE: THE PROJECT HAS BEEN SUBMITTED FOR PERMIT |
| | AFTER OCTOBER 1ST, 2009 AND MARCH 1ST, 2009 WHICH |
| | PLACES DESIGN REQUIREMENTS UNDER THE 2007 FBC W/2009 |
| | SUPPLEMENTS AS WELL AS THE 2008 NFPA-70. |
| | |
| | 2) NOTE: THE SUBMITTED FLORIDA ENERGY CALCULATIONS ARE |
| | NOT FROM THE CURRENT CODE CYCLE. IN FACT THEY ARE FROM |
| | THE 2004 FLA/COM 2.5. |
| | THEY ARE SUBSTANTIALLY DIFFERENT FROM NEWER CODE CYCLE |
| | REQUIREMENTS. |
| | PLEASE SEE 13-415.AB.5 FOR INTERIOR LIGHTING AND |
| | 13-415.AB.2.2 FOR EXTERIOR LIGHTING. |
| | PLEASE KNOW THAT ALL ITEMS ON THE PLANS FOR THE |
| | CONSTRUCTION, TYPE, BUILDING CHARACTERISTICS ARE |
| | REQUIRED TO BE IN THE INPUT DATA REPORT OF THE |
| | SUBMITTED CALCULATIONS. |
| | THERE ARE ITEMS EVEN ON THE IDR OF THE 2004 WHICH ARE |
| | NOT CORRELATING WITH THE PLANS. ONE EXAMPLE IS ALL THE |
| | FLOOR AREAS IN THE BUILDING ARE USING CREDIT FOR CARPET |
| | AND RUBBER PADDING HOWEVER THIS IS NOT POSSIBLE. AREAS |
| | SUCH AS BATHROOMS, ELECTRICAL ROOMS/AREAS, MECHANICAL |
| | ROOMS AND KITCHEN ARE NOT GOING TO HAVE CARPET AND |
| | RUBBER PADDING NOR ARE THEY PERMITTED TO HAVE CARPET |
| | INSTALLED. |
| | THERE ARE OTHER ITEMS HOWEVER AS THE VERSION IS |
| | COMPLETELY DIFFERENT WE ARE NOT ABLE TO REVIEW FOR |
| | CURRENT CODE. |
| | ** PLEASE BE SURE TO GO THROUGH ALL SYSTEMS AND |
| | COMPONENTS. THIS WAS SPECIFICALLY MENTIONED ON THE |
| | ORIGINAL REVIEW. THIS OFFICE ONCE AGAIN EMPHASIZES THE |
| | IMPORTANCE OF ALL SYSTEMS ON PLANS TO COORDINATE WITH |
| | THE INPUT DATA REPORT OF THE SUBMITTED ENERGY |
| | CALCULATIONS. IF THERE ARE QUESTIONS, PLEASE CALL. |
| | |
| | ** THIS INCLUDES THE POWER DENSITIES ON PLANS. |
| | ** PLEASE BE SURE TO SEE APPENDIX B FOR TRACK LIGHTING |
| | AND OTHER LIGHTING FOR CALCULATIONS. |
| | |
| | 3) NOTE: PLEASE SEE CODE REFERENCES ON PLANS SUCH AS |
| | THE 13-413 NOTES ON E001. THE SECTIONS NOTED ARE FROM |
| | THE ORIGINAL PRINTING OF THE 2007 FBC HOWEVER THAT |
| | VERSION AND PRINTING WAS NEVER ADOPTED. THE FIRST |
| | ADOPTED VERSION WAS THE 2007 WITH THE FIRST SET OF 2009 |
| | SUPPLEMENTS. THIS INCLUDED A COMPLETE RE-WRITE OF FBC |
| | CHAPTER 13. PRESCRIPTIVE C METHODS ARE NOT IN ANY OF |
| | THE ADOPTED CODES. |
| | PLEASE VISIT THE FOLLOWING WEBSITE TO LOOK AT THE |
| | ADOPTED CODES, ADJUST TEXT, AND ADJUSTED CODES WHICH |
| | WERE SUBSTANTIALLY CHANGED AND REVISED. |
| | |
| | 4) NOTE: SAME COMMENT AS PREVIOUS REVIEW WITH RESPECT |
| | TO RUBBER STAMPED SIGNATURE ON COMPASS SURVEYING |
| | SHEETS. PLEASE SEE FS 472.025. |
| | |
| | 5) NOTE: PLEASE EXPLAIN RESPONSE TO PREVIOUS NOTE #10. |
| | THE RESPONSE STATES THE TRACK LIGHTING IS EXEMPT. |
| | PLEASE EXPLAIN WHERE THERE IS AN EXEMPTION IN THE |
| | PREVIOUS CODE OR THIS APPLICABLE CODE. |
| | THIS OCCUPANCY AND USE DOES NOT APPLY TO EXEMPTIONS. |
| | THIS IS IMPORTANT AS THE TRACK LIGHTING AS MENTIONED IN |
| | NOTE #2 ABOVE TRACK LIGHTING IN APPENDIX B FOR IDR IS |
| | MENTIONED. |
| | |
| | |
| | 6) NOTE: LIGHTING CONTROLS FOR BATHROOMS DO NOT MEET |
| | 13-415.AB.1.1,.1.2. |
| | AUTOMATED CONTROL REQUIRED ALONG WITH OVER RIDE. THE |
| | USE OF OCCUPANCY SENSORS TYPE DEVICES ARE PERMITTED |
| | HOWEVER THEY WOULD BE REQUIRED TO BE FAIL SAFE ON. THE |
| | RESPONSE MENTIONS ALONG WITH PLANS SHOWING A KEYED |
| | SWITCH TO BE LOCATED ABOVE THE CEILING. THIS IS NOT |
| | WHAT WAS MEANT BY THE PREVIOUS COMMENTS AND DOES NOT |
| | MEET FBC. PLEASE ADJUST PLANS. |
| | FBC 1006.1.2, NFPA-101 7.2.1.2.2 |
| | |
| | 7) NOTE: PLEASE SEE 13-415.AB.1.1,.1.2 FOR AREAS WHERE |
| | THE PLANS ONLY INDICATE SINGLE POLE SWITCHES FOR THE |
| | LIGHTING CONTROLS. THESE ARE SEPARATE SPACES LOCATED IN |
| | A BUILDING GREATER THAN 5K SQ FT. |
| | 101A, 117A. |
| | |
| | 8) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| | FOR NEW PROPOSED MTS. THE RESPONSE MENTIONS TO SEE |
| | ATTACHED HOWEVER NO SPECS COULD BE LOCATED IN PACKAGE. |
| | |
| | 9) NOTE: AS NOTED ON PREVIOUS REVIEW AS KITCHEN |
| | EQUIPMENT AND ELECTRICAL SYSTEMS IS NOT YET COMPLETE, |
| | SEVERAL ITEMS TO BE REVIEWED FOR CODE COMPLIANCE CAN |
| | NOT BE DONE AT THIS TIME. |
| | ** THIS MAY AFFECT FUTURE EQUIPMENT/SERVICE. |
| | |
| | 10) NOTE: ALTHOUGH NOT UNDER THE TECHNICAL REVIEW OF |
| | THIS OFFICE. THE STATE ELEVATOR CODE REQUIREMENTS HAVE |
| | CHANGED. |
| | PLEASE SEE CURRENT ADOPTED ASME A-17. |
| | PIT LEVELS 10FT CANDLES |
| | MECHANICAL AREAS/ROOMS, 19FTCANDLES |
| | SILL AREA IN LOBBY/LANDING AREA 10FT CANDLES. |
| | |
| | THIS INFORMATION IS GIVEN AS A BENEFIT SO AS NOT TO |
| | DELAY THE PROJECT AT THE FINAL INSPECTIONS. |
| | |
| | 11) NOTE: THE CIRCUITING FOR THE ELEVATOR EQUIPMENT |
| | ROOM FOR LIGHTS AND RECEPTACLES IS NOT LOCATED ON |
| | PLANS. 620.23 REQUIRED TO BE DEDICATED. |
| | PLEASE EXPLAIN THE SYMBOL ON THE PLANS FOR THE SAME |
| | ROOM LOCATION SHOWN ON E301. BY THE SYMBOL IT LOOKS TO |
| | BE A TRANSFORMER OR PERHAPS EVEN A ROOF-HATCH. |
| | |
| | 12) NOTE: AS NOTED ON PREVIOUS NOTE #32, THE SITE |
| | CONDUITS FOR THE ELECTRICAL SERVICE ON SHEET ES101 ARE |
| | STILL SHOWN GOING FROM FPL TRANSFORMER TO THE MAIN |
| | ELECTRICAL ROOM. |
| | THE RISER AND PLANS INDICATE A MAIN OUTSIDE, A MTS |
| | OUTSIDE ETC. |
| | HOW IS IT THESE CONDUITS ARE NOT SHOWN TO THE OUTSIDE |
| | SERVICE AND LOW VOLTAGE SERVICE LOCATIONS? |
| | |
| | 13) NOTE: INTER-SYSTEM GROUNDING IS REQUIRED AT MAIN |
| | SERVICE PER 250.94 OF THE REVISED 2008 NEC. |
| | |
| | 14) NOTE: ALL OUTSIDE RECEPTACLES SHALL BE WR TYPE PER |
| | REVISED 2008 NEC 406.8A. |
| | |
| | 16) NOTE: PREVIOUS NOTE #38. THE TRANSFORMER ON ES 101 |
| | SITE PLANS IS STILL SHOWN AS 100KVA, YET CALCULATIONS |
| | FOR AIC RATING STILL INDICATE A 225 KVA UNIT. |
| | PLEASE CORRELATE PLANS. IT IS UNCLEAR WHAT THE RESPONSE |
| | LETTER IS RESPONDING TO. |
| | |
| | 17) NOTE: PREVIOUS NOTE #40. THE RISER STILL INDICATES |
| | A 125AMP BREAKER FEEDING A 100AMP RATED DISCONNECT. |
| | RESPONSE MENTIONS THE OVER CURRENT PROTECTION AND |
| | SIZING FOR ELEVATOR MOTOR. THAT IS NOT THE COMMENT |
| | PREVIOUSLY MADE. THIS REVIEWER UNDERSTANDS THE OVER |
| | CURRENT PROTECTION AS LISTED IN THE CODE AND AS |
| | RESPONDED TO HOWEVER THE COMMENT WAS BASED ON THE FACT |
| | THE RATING OF THE DISCONNECT NEEDS TO COORDINATE WITH |
| | THE BREAKER OCP. |
| | |
| | 18) NOTE: PREVIOUS NOTE #29. SYSTEM IS REQUIRED TO BE |
| | DEDICATED FOR ELEVATOR EQUIPMENT ROOM. SHARING THE VRV |
| | AS RESPONDED WITH THE ANY OTHER AREAS ETC IS NOT |
| | PERMITTED. PLEASE SEE FBC 3006.2 AS THIS REQUIRES AND |
| | *INDEPENDENT* SYSTEM. |
| | IT HAS ALSO BEEN CONFIRMED ON NUMEROUS PREVIOUS |
| | PROJECTS WITH THE STATE ELEVATOR INSPECTOR. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |