| 2010-03-08 09:52:24 | BUILDING PLAN REVIEW |
| | PERMIT: 10010548 |
| | ADD: 706 8TH STREET |
| | CONT: YOUCHAK& YOUCHAK, INC. |
| | TEL: (561)371-5548 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | MARCH3/ 2010 |
| | |
| | 1) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 1A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 1B) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 1C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | 1D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 1E) DOCUMENTS REQUIRED FOR THRESHOLD BUILDINGS. THREE |
| | SETS OF ALL DOCUMENTS WILL BE REQUIRED FOR THRESHOLD |
| | BUILDINGS. 109.3.6 WPB ADMINISTRATIVE CODE. |
| | |
| | 2) SHEET LS-1: |
| | |
| | 2A) BUILDING CODE ANALYSIS, THE PLANS INDICATE THE |
| | FIRST FLOOR IS 7564 SQ. FT. WHERE AS TABLE 503 |
| | ALLOWABLE HEIGHT AND AREA FOR A A3 OCCUPANCY INDICATES |
| | FOR A BUILDING TYPE VB ONLY 6000SQ FT. PLEASE PROVIDE |
| | AREA MODIFICATIONS CALCULATIONS AS IN 506.1 |
| | FBC-BUILDING. |
| | |
| | 2B) OCCUPANT LOAD CALCULATIONS PLEASE SEE SECTION 303.1 |
| | FOR ASSEMBLY OCCUPANCY TYPES A3 |
| | READING ROOMS, LOBBIES AND KITCHEN. PLEASE REVIEW TABLE |
| | 508.3.3PLEASE REVIEW FOOTNOTE E IN REGARDS TO |
| | SEPARATION. |
| | |
| | 2C) OCCUPANT LOAD CALCULATIONS, SQUARE FOOT AREA PER |
| | OCCUPANT SHALL BE TAKEN FROM TABLE 1004.1.1. THIS WILL |
| | GREATLY CHANGE THE OCCUPANT LOADS LISTED IN THIS |
| | REVIEW. IN AREAS AS THE MULTIPURPOSE COMMUNITY ROOM WE |
| | HAVE TO LOOK AT THE WORST CASE SCENARIO OR 5 SQ FT PER |
| | PERSON. |
| | THE OTHER AREA OF CONCERN IS THE 2ND FLOOR MEETING |
| | ROOMS A& B. |
| | |
| | 1004.1.1 AREAS WITHOUT FIXED SEATING. THE NUMBER OF |
| | OCCUPANTS SHALL BE COMPUTED AT THE RATE OF ONE OCCUPANT |
| | PER UNIT OF AREA AS PRESCRIBED IN TABLE 1004.1.1. FOR |
| | AREAS WITHOUT FIXED SEATING, THE OCCUPANT LOAD SHALL |
| | NOT BE LESS THAN THAT NUMBER DETERMINED BY DIVIDING THE |
| | FLOOR AREA UNDER CONSIDERATION BY THE OCCUPANT PER UNIT |
| | OF AREA FACTOR ASSIGNED TO THE OCCUPANCY AS SET FORTH |
| | IN TABLE 1004.1.1. WHERE AN INTENDED USE IS NOT LISTED |
| | IN TABLE 1004.1.1, THE BUILDING OFFICIAL SHALL |
| | ESTABLISH A USE BASED ON A LISTED USE THAT MOST NEARLY |
| | RESEMBLES THE INTENDED USE. |
| | |
| | 2D) THE PLANS DO NOT INDICATE IF THIS MIXED USE |
| | OCCUPANCY BUILDING IS TRYING TO CLAIM OCCUPANCY |
| | SEPARATION PER 508.3.1.3 OR NON-SEPARATED OCCUPANCIES |
| | PER SECTION 508.3.2. PLEASE IDENTIFY, BEWARE SEPARATION |
| | OF NON-SEPARATED OCCUPANCIES WE STILL NEED TO REVIEW TO |
| | CORRIDOR FIRE RESISTANCE RATING PER TABLE 1017.1. |
| | PLEASE REVIEW FOR |
| | ASSEMBLY OCCUPANCY WITH OCCUPANT LOAD GREATER THAN 30, |
| | FIRE SPRINKLERED WILL STILL REQUIRE A 1 HR RATED |
| | CORRIDOR, INCLUDING CEILING IF WALLS ARE NOT RATED TO |
| | THE DECK ABOVE. NOTE WHEN TRAVELING THROUGH ADJOINING |
| | ROOMS THIS WOULD BE CONSIDERED PART OF A CORRIDOR, |
| | EDUCATIONAL ROOMS, CORRIDOR 117 THE READING ROOM, TO |
| | THE LOBBY AS WELL AS THE ELEVATOR LOBBY. PLEASE ALSO |
| | REVIEW SECTION 715 OPENING PROTECTIVE???S AND TABLE |
| | 715.3. |
| | |
| | 2E) ANOTHER ISSUE WITH THE ONE HOUR RATING OF THE |
| | CORRIDOR LEADING FROM THE ASSEMBLY AREA THE |
| | MULTIPURPOSE COMMUNITY ROOM WOULD BE THE ELEVATOR |
| | MACHINE ROOM LOCATED WITHIN THIS RATED CORRIDOR. 3006.1 |
| | ACCESS. AN APPROVED MEANS OF ACCESS SHALL BE PROVIDED |
| | TO ELEVATOR MACHINE ROOMS AND OVERHEAD MACHINERY |
| | SPACES. |
| | 3006.4 MACHINE ROOMS AND MACHINERY SPACES. ELEVATOR |
| | MACHINE ROOMS AND MACHINERY SPACES SHALL BE ENCLOSED |
| | WITH FIRE BARRIERS COMPLYING WITH SECTION 706 OR |
| | HORIZONTAL ASSEMBLIES COMPLYING WITH SECTION 711 HAVING |
| | A FIRE-RESISTANCE RATING NOT LESS THAN THE REQUIRED |
| | RATING OF THE HOISTWAY ENCLOSURE SERVED BY THE |
| | MACHINERY. OPENINGS SHALL BE PROTECTED WITH ASSEMBLIES |
| | HAVING A FIRE-PROTECTION RATING NOT LESS THAN THAT |
| | REQUIRED FOR THE HOISTWAY ENCLOSURE DOORS. |
| | |
| | 2F) THE ELEVATOR SHAFT DOES NOT PROVIDE A FIRE RATING |
| | AS PER SHAFTS SECTION 707.4 FBC-BUILDING NOR RATING OF |
| | HOISTWAY ENCLOSURE DOORS. |
| | |
| | 2G) CLOSET ROOM 101A PLEASE PROVIDE A 1HR DETAIL FOR |
| | SEPARATION FROM STAIRS LOCATED ABOVE, SHEET A-8 DETAIL# |
| | 1 INDICATES A PRE-ENGINEERED STEEL STAIR WITH CONCRETE |
| | FILLED PAN. SEE SECTION 1009.5.3. |
| | |
| | 2H) SECOND FLOOR READING ROOMS A & B, WITHOUT TABLES |
| | AND CHAIRS INDICATED IN THESE ROOMS THE OCCUPANT LOAD |
| | FIGURED AT 7 SQ FT PER PERSON THE OCCUPANT LOAD IS 50. |
| | THIS |
| | WILL REQUIRE THE DOORS TO SWING IN THE DIRECTION OF |
| | TRAVEL PER SECTION 1008.1.2. |
| | |
| | 2I) SECOND FLOOR READING ROOM B WILL ALSO NEED TWO |
| | MEANS OF EGRESS TABLE 1015.1. |
| | |
| | 2J) STAIR# 2 INDICATES A 3??? VERTICAL STORM DRAIN |
| | WITHIN THE STAIRWELL, PLEASE REVIEW 1023.6 EXTERIOR |
| | RAMPS AND STAIRWAY PROTECTION. EXTERIOR EXIT RAMPS AND |
| | STAIRWAYS SHALL BE SEPARATED FROM THE INTERIOR OF THE |
| | BUILDING AS REQUIRED IN SECTION 1020.1. OPENINGS SHALL |
| | BE LIMITED TO THOSE NECESSARY FOR EGRESS FROM NORMALLY |
| | OCCUPIED SPACES. |
| | |
| | 3) SHEET LA-1 PLEASE PROVIDE COMPLIANCE WITH : |
| | 11-4.1.3 ACCESSIBLE BUILDINGS: NEW CONSTRUCTION. |
| | 8) IN NEW CONSTRUCTION, AT A MINIMUM, THE REQUIREMENTS |
| | IN SECTION 11-4.1.3(8)(A) AND SECTION 11-4.1.3(8)(B) |
| | BELOW SHALL BE SATISFIED INDEPENDENTLY: |
| | |
| | (A)(I) AT LEAST 50 PERCENT OF ALL PUBLIC ENTRANCES |
| | [EXCLUDING THOSE IN SECTION 11-4.1.3(8)(B) BELOW] MUST |
| | BE ACCESSIBLE. AT LEAST ONE MUST BE A GROUND-FLOOR |
| | ENTRANCE. PUBLIC ENTRANCES ARE ANY ENTRANCES THAT ARE |
| | NOT LOADING OR SERVICE ENTRANCES. |
| | |
| | (II) ACCESSIBLE ENTRANCES MUST BE PROVIDED IN A NUMBER |
| | AT LEAST EQUIVALENT TO THE NUMBER OF EXITS REQUIRED BY |
| | THE APPLICABLE BUILDING/FIRE CODES. (THIS PARAGRAPH |
| | DOES NOT REQUIRE AN INCREASE IN THE TOTAL NUMBER OF |
| | ENTRANCES PLANNED FOR A FACILITY.) |
| | |
| | 4) SHEET A1 DOORS 103A, 112 & 112A NEED TO COMPLY WITH: |
| | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| | MANEUVERING CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL |
| | BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL. |
| | |
| | 5) STRUCTURAL SHEET S7 DETAIL 8 & 9 INDICATE A METAL |
| | DECK ROOFING WITH 5/8??? CDX PLYWOOD SHEATHING, THE |
| | SCHEDULE SHEET S5 DOES NOT PROVIDE TYPE OF FASTENERS, |
| | LENGTH NOR QUANTITY FOR ROOF ZONES 1, 2 & 3. |
| | |
| | 6)SHEET A-5 DETAILS 2 & 3 INDICATE THE USE OF 5/8??? |
| | PLYWOOD OVER STEEL DECK WITH USE OF BAR-JOIST AT |
| | 4???-0??? O. C. THE ROOFING REPORT FOR METAL ROOFING , |
| | PRODUCT NAME ???ZEE-LOCK??? HAS A OPTIONAL RIGID |
| | INSULATION. UNDER THE LISTING OF SYSTEMS LIMITATION THE |
| | REPORT STATES ??? RATIONAL ANALYSIS FOR THIS PRODUCT |
| | OUTSIDE OF USE AS DESCRIBED IN THIS REPORT SHALL BE |
| | PREPARED BY A QUALIFIED DESIGN PROFESSIONAL AND IN |
| | COMPLIANCE WITH FBC 2007. WILL THE FASTENERS FOR THE |
| | METAL ROOF ONLY PENETRATE THE 5/8??? CDX PLY WOOD OR |
| | WILL THEY ALSO NEED TO PENETRATE THE METAL ROOF |
| | DECKING. |
| | |
| | 7) SHEET A3 DOES INDICATE THE USE IN TWO AREAS OF FLAT |
| | ROOF CONSTRUCTION, CONCRETE DECK WITH BUILT-UP ROOF ON |
| | TAPERED INSULATION. PLEASE PROVIDE INSULATION |
| | CALCULATIONS FOR ROOF ZONES. THE PRODUCT APPROVAL FOR |
| | FLAT ROOF AND TAPERED INSULATION INDICATES THE USE OF |
| | SYSTEM # S-26, APPENDIX 1, PAGE 9 OF 26. ENHANCED |
| | FASTENING WILL BE |
| | REQUIRED FOR ROOF ZONE# 3. PRODUCT APPROVAL GOOD FOR |
| | -112.5 WHERE AS PLANS INDICATE ROOF ZONE 3 A -130.9. A |
| | SHOP DRAWING WILL BE REQUIRED INDICATING THE TAPERED |
| | INSULATION AND MINIMUM R-VALUE LOCATED AT ROOF DRAIN, |
| | THIS VALUE SHALL ALSO MATCH THE ENERGY CALCULATIONS. |
| | |
| | 8) S-7 DETAILS 12 & 13 THE SIZE AND SPACING OF THE |
| | BOTTOM STEEL IS NOT PROVIDED. |
| | |
| | |
| | 9) STRUCTURAL SHEET S7, S8 & S9 ALL INDICATE A BRICK |
| | VENEER ATTACHMENT METHODS, WALL ANGLES FOR SUPPORT |
| | LEDGES BUT THE PLANS DO NOT INDICATE WHERE THE BRICK |
| | VENEER WILL STOP, AT GRADE, BELOW GRADE, THIS IS STEM |
| | WALL CONSTRUCTION? |
| | 2114.2 CONCRETE BEARING LEDGE. BRICK, STONE OR OTHER |
| | VENEER SHALL BE SUPPORTED BY A CONCRETE-BEARING LEDGE |
| | AT LEAST EQUAL TO THE TOTAL THICKNESS OF THE BRICK, |
| | STONE OR OTHER VENEER, WHICH IS POURED INTEGRALLY WITH |
| | THE CONCRETE FOUNDATION. NO SUPPLEMENTAL CONCRETE |
| | FOUNDATION POURS WHICH WILL CREATE A HIDDEN COLD JOINT |
| | SHALL BE USED WITHOUT SUPPLEMENTAL TREATMENT IN THE |
| | FOUNDATION UNLESS THERE IS AN APPROVED PHYSICAL |
| | BARRIER. AN APPROVED PHYSICAL BARRIER SHALL ALSO BE |
| | INSTALLED FROM BELOW THE WALL SILL PLATE OR FIRST BLOCK |
| | COURSE HORIZONTALLY TO EMBED IN A MORTAR JOINT. IF |
| | MASONRY VENEER EXTENDS BELOW GRADE, A TERMITE |
| | PROTECTIVE TREATMENT MUST BE APPLIED TO THE CAVITY |
| | CREATED BETWEEN THE VENEER AND THE FOUNDATION, IN LIEU |
| | OF A PHYSICAL BARRIER. |
| | |
| | 10) A8 DETAILS 1A-1B BOTH INDICATE A ELEVATOR SHAFT, |
| | A-3 INDICATES A ELEVATOR SHAFT BELOW THE ROOF LINE, S1 |
| | & S2 BOTH INDICATE A OPEN SHAFT, PLEASE REVIEW: |
| | 3002.1.1 OPENING PROTECTIVE???S. OPENINGS IN HOIST WAY |
| | ENCLOSURES SHALL BE PROTECTED AS REQUIRED IN CHAPTER 7. |
| | 707.2 SHAFT ENCLOSURE REQUIRED. OPENINGS THROUGH A |
| | FLOOR/CEILING ASSEMBLY SHALL BE PROTECTED BY A SHAFT |
| | ENCLOSURE COMPLYING WITH THIS SECTION. |
| | 707.4 FIRE-RESISTANCE RATING. SHAFT ENCLOSURES SHALL |
| | HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS |
| | WHERE CONNECTING FOUR STORIES OR MORE, AND NOT LESS |
| | THAN 1 HOUR WHERE CONNECTING LESS THAN FOUR STORIES. |
| | THE NUMBER OF STORIES CONNECTED BY THE SHAFT ENCLOSURE |
| | SHALL INCLUDE ANY BASEMENTS BUT NOT ANY MEZZANINES. |
| | SHAFT ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING |
| | NOT LESS THAN THE FLOOR ASSEMBLY PENETRATED, BUT NEED |
| | NOT EXCEED 2 HOURS. |
| | |
| | 707.5 CONTINUITY. SHAFT ENCLOSURES SHALL BE CONSTRUCTED |
| | AS FIRE BARRIERS IN ACCORDANCE WITH SECTION 706 OR |
| | HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 711, OR BOTH, AND SHALL HAVE CONTINUITY IN |
| | ACCORDANCE WITH SECTION 706.5 FOR FIRE BARRIERS OR |
| | SECTION 711.4 FOR HORIZONTAL ASSEMBLIES AS APPLICABLE. |
| | |
| | |
| | 11) SHEET A-4 THE EAST ELEVATION INDICATES THE USE OF |
| | SIMULATED 6 INCH HORIZONTAL LAP |
| | SIDING STUCCO FINISH. PLEASE PROVIDE PRODUCT APPROVAL |
| | FOR SIDING. COMPONENTS AND CLADDING. FL BLD CODE |
| | 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 3 |
| | SETS OF PRODUCT APPROVALS FOR THESHOLD BUILDINGS. |
| | NOTE ONLY TWO REPORTS WERE SUPPLIED FOR THE OTHER |
| | APPROVALS SUBMITTED! |
| | |
| | 12) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |