Plan Review Notes
Plan Review Notes For Permit 10010548
Permit Number 10010548
Review Stop B
Sequence Number 1
Notes
Date Text
2010-03-08 09:52:24BUILDING PLAN REVIEW
 PERMIT: 10010548
 ADD: 706 8TH STREET
 CONT: YOUCHAK& YOUCHAK, INC.
 TEL: (561)371-5548
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 MARCH3/ 2010
  
 1) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 1A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 1C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 1D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 1E) DOCUMENTS REQUIRED FOR THRESHOLD BUILDINGS. THREE
 SETS OF ALL DOCUMENTS WILL BE REQUIRED FOR THRESHOLD
 BUILDINGS. 109.3.6 WPB ADMINISTRATIVE CODE.
  
 2) SHEET LS-1:
  
 2A) BUILDING CODE ANALYSIS, THE PLANS INDICATE THE
 FIRST FLOOR IS 7564 SQ. FT. WHERE AS TABLE 503
 ALLOWABLE HEIGHT AND AREA FOR A A3 OCCUPANCY INDICATES
 FOR A BUILDING TYPE VB ONLY 6000SQ FT. PLEASE PROVIDE
 AREA MODIFICATIONS CALCULATIONS AS IN 506.1
 FBC-BUILDING.
  
 2B) OCCUPANT LOAD CALCULATIONS PLEASE SEE SECTION 303.1
 FOR ASSEMBLY OCCUPANCY TYPES A3
 READING ROOMS, LOBBIES AND KITCHEN. PLEASE REVIEW TABLE
 508.3.3PLEASE REVIEW FOOTNOTE E IN REGARDS TO
 SEPARATION.
  
 2C) OCCUPANT LOAD CALCULATIONS, SQUARE FOOT AREA PER
 OCCUPANT SHALL BE TAKEN FROM TABLE 1004.1.1. THIS WILL
 GREATLY CHANGE THE OCCUPANT LOADS LISTED IN THIS
 REVIEW. IN AREAS AS THE MULTIPURPOSE COMMUNITY ROOM WE
 HAVE TO LOOK AT THE WORST CASE SCENARIO OR 5 SQ FT PER
 PERSON.
 THE OTHER AREA OF CONCERN IS THE 2ND FLOOR MEETING
 ROOMS A& B.
  
 1004.1.1 AREAS WITHOUT FIXED SEATING. THE NUMBER OF
 OCCUPANTS SHALL BE COMPUTED AT THE RATE OF ONE OCCUPANT
 PER UNIT OF AREA AS PRESCRIBED IN TABLE 1004.1.1. FOR
 AREAS WITHOUT FIXED SEATING, THE OCCUPANT LOAD SHALL
 NOT BE LESS THAN THAT NUMBER DETERMINED BY DIVIDING THE
 FLOOR AREA UNDER CONSIDERATION BY THE OCCUPANT PER UNIT
 OF AREA FACTOR ASSIGNED TO THE OCCUPANCY AS SET FORTH
 IN TABLE 1004.1.1. WHERE AN INTENDED USE IS NOT LISTED
 IN TABLE 1004.1.1, THE BUILDING OFFICIAL SHALL
 ESTABLISH A USE BASED ON A LISTED USE THAT MOST NEARLY
 RESEMBLES THE INTENDED USE.
  
 2D) THE PLANS DO NOT INDICATE IF THIS MIXED USE
 OCCUPANCY BUILDING IS TRYING TO CLAIM OCCUPANCY
 SEPARATION PER 508.3.1.3 OR NON-SEPARATED OCCUPANCIES
 PER SECTION 508.3.2. PLEASE IDENTIFY, BEWARE SEPARATION
 OF NON-SEPARATED OCCUPANCIES WE STILL NEED TO REVIEW TO
 CORRIDOR FIRE RESISTANCE RATING PER TABLE 1017.1.
 PLEASE REVIEW FOR
 ASSEMBLY OCCUPANCY WITH OCCUPANT LOAD GREATER THAN 30,
 FIRE SPRINKLERED WILL STILL REQUIRE A 1 HR RATED
 CORRIDOR, INCLUDING CEILING IF WALLS ARE NOT RATED TO
 THE DECK ABOVE. NOTE WHEN TRAVELING THROUGH ADJOINING
 ROOMS THIS WOULD BE CONSIDERED PART OF A CORRIDOR,
 EDUCATIONAL ROOMS, CORRIDOR 117 THE READING ROOM, TO
 THE LOBBY AS WELL AS THE ELEVATOR LOBBY. PLEASE ALSO
 REVIEW SECTION 715 OPENING PROTECTIVE???S AND TABLE
 715.3.
  
 2E) ANOTHER ISSUE WITH THE ONE HOUR RATING OF THE
 CORRIDOR LEADING FROM THE ASSEMBLY AREA THE
 MULTIPURPOSE COMMUNITY ROOM WOULD BE THE ELEVATOR
 MACHINE ROOM LOCATED WITHIN THIS RATED CORRIDOR. 3006.1
 ACCESS. AN APPROVED MEANS OF ACCESS SHALL BE PROVIDED
 TO ELEVATOR MACHINE ROOMS AND OVERHEAD MACHINERY
 SPACES.
 3006.4 MACHINE ROOMS AND MACHINERY SPACES. ELEVATOR
 MACHINE ROOMS AND MACHINERY SPACES SHALL BE ENCLOSED
 WITH FIRE BARRIERS COMPLYING WITH SECTION 706 OR
 HORIZONTAL ASSEMBLIES COMPLYING WITH SECTION 711 HAVING
 A FIRE-RESISTANCE RATING NOT LESS THAN THE REQUIRED
 RATING OF THE HOISTWAY ENCLOSURE SERVED BY THE
 MACHINERY. OPENINGS SHALL BE PROTECTED WITH ASSEMBLIES
 HAVING A FIRE-PROTECTION RATING NOT LESS THAN THAT
 REQUIRED FOR THE HOISTWAY ENCLOSURE DOORS.
  
 2F) THE ELEVATOR SHAFT DOES NOT PROVIDE A FIRE RATING
 AS PER SHAFTS SECTION 707.4 FBC-BUILDING NOR RATING OF
 HOISTWAY ENCLOSURE DOORS.
  
 2G) CLOSET ROOM 101A PLEASE PROVIDE A 1HR DETAIL FOR
 SEPARATION FROM STAIRS LOCATED ABOVE, SHEET A-8 DETAIL#
 1 INDICATES A PRE-ENGINEERED STEEL STAIR WITH CONCRETE
 FILLED PAN. SEE SECTION 1009.5.3.
  
 2H) SECOND FLOOR READING ROOMS A & B, WITHOUT TABLES
 AND CHAIRS INDICATED IN THESE ROOMS THE OCCUPANT LOAD
 FIGURED AT 7 SQ FT PER PERSON THE OCCUPANT LOAD IS 50.
 THIS
 WILL REQUIRE THE DOORS TO SWING IN THE DIRECTION OF
 TRAVEL PER SECTION 1008.1.2.
  
 2I) SECOND FLOOR READING ROOM B WILL ALSO NEED TWO
 MEANS OF EGRESS TABLE 1015.1.
  
 2J) STAIR# 2 INDICATES A 3??? VERTICAL STORM DRAIN
 WITHIN THE STAIRWELL, PLEASE REVIEW 1023.6 EXTERIOR
 RAMPS AND STAIRWAY PROTECTION. EXTERIOR EXIT RAMPS AND
 STAIRWAYS SHALL BE SEPARATED FROM THE INTERIOR OF THE
 BUILDING AS REQUIRED IN SECTION 1020.1. OPENINGS SHALL
 BE LIMITED TO THOSE NECESSARY FOR EGRESS FROM NORMALLY
 OCCUPIED SPACES.
  
 3) SHEET LA-1 PLEASE PROVIDE COMPLIANCE WITH :
 11-4.1.3 ACCESSIBLE BUILDINGS: NEW CONSTRUCTION.
 8) IN NEW CONSTRUCTION, AT A MINIMUM, THE REQUIREMENTS
 IN SECTION 11-4.1.3(8)(A) AND SECTION 11-4.1.3(8)(B)
 BELOW SHALL BE SATISFIED INDEPENDENTLY:
  
 (A)(I) AT LEAST 50 PERCENT OF ALL PUBLIC ENTRANCES
 [EXCLUDING THOSE IN SECTION 11-4.1.3(8)(B) BELOW] MUST
 BE ACCESSIBLE. AT LEAST ONE MUST BE A GROUND-FLOOR
 ENTRANCE. PUBLIC ENTRANCES ARE ANY ENTRANCES THAT ARE
 NOT LOADING OR SERVICE ENTRANCES.
  
 (II) ACCESSIBLE ENTRANCES MUST BE PROVIDED IN A NUMBER
 AT LEAST EQUIVALENT TO THE NUMBER OF EXITS REQUIRED BY
 THE APPLICABLE BUILDING/FIRE CODES. (THIS PARAGRAPH
 DOES NOT REQUIRE AN INCREASE IN THE TOTAL NUMBER OF
 ENTRANCES PLANNED FOR A FACILITY.)
  
 4) SHEET A1 DOORS 103A, 112 & 112A NEED TO COMPLY WITH:
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 5) STRUCTURAL SHEET S7 DETAIL 8 & 9 INDICATE A METAL
 DECK ROOFING WITH 5/8??? CDX PLYWOOD SHEATHING, THE
 SCHEDULE SHEET S5 DOES NOT PROVIDE TYPE OF FASTENERS,
 LENGTH NOR QUANTITY FOR ROOF ZONES 1, 2 & 3.
  
 6)SHEET A-5 DETAILS 2 & 3 INDICATE THE USE OF 5/8???
 PLYWOOD OVER STEEL DECK WITH USE OF BAR-JOIST AT
 4???-0??? O. C. THE ROOFING REPORT FOR METAL ROOFING ,
 PRODUCT NAME ???ZEE-LOCK??? HAS A OPTIONAL RIGID
 INSULATION. UNDER THE LISTING OF SYSTEMS LIMITATION THE
 REPORT STATES ??? RATIONAL ANALYSIS FOR THIS PRODUCT
 OUTSIDE OF USE AS DESCRIBED IN THIS REPORT SHALL BE
 PREPARED BY A QUALIFIED DESIGN PROFESSIONAL AND IN
 COMPLIANCE WITH FBC 2007. WILL THE FASTENERS FOR THE
 METAL ROOF ONLY PENETRATE THE 5/8??? CDX PLY WOOD OR
 WILL THEY ALSO NEED TO PENETRATE THE METAL ROOF
 DECKING.
  
 7) SHEET A3 DOES INDICATE THE USE IN TWO AREAS OF FLAT
 ROOF CONSTRUCTION, CONCRETE DECK WITH BUILT-UP ROOF ON
 TAPERED INSULATION. PLEASE PROVIDE INSULATION
 CALCULATIONS FOR ROOF ZONES. THE PRODUCT APPROVAL FOR
 FLAT ROOF AND TAPERED INSULATION INDICATES THE USE OF
 SYSTEM # S-26, APPENDIX 1, PAGE 9 OF 26. ENHANCED
 FASTENING WILL BE
 REQUIRED FOR ROOF ZONE# 3. PRODUCT APPROVAL GOOD FOR
 -112.5 WHERE AS PLANS INDICATE ROOF ZONE 3 A -130.9. A
 SHOP DRAWING WILL BE REQUIRED INDICATING THE TAPERED
 INSULATION AND MINIMUM R-VALUE LOCATED AT ROOF DRAIN,
 THIS VALUE SHALL ALSO MATCH THE ENERGY CALCULATIONS.
  
 8) S-7 DETAILS 12 & 13 THE SIZE AND SPACING OF THE
 BOTTOM STEEL IS NOT PROVIDED.
  
  
 9) STRUCTURAL SHEET S7, S8 & S9 ALL INDICATE A BRICK
 VENEER ATTACHMENT METHODS, WALL ANGLES FOR SUPPORT
 LEDGES BUT THE PLANS DO NOT INDICATE WHERE THE BRICK
 VENEER WILL STOP, AT GRADE, BELOW GRADE, THIS IS STEM
 WALL CONSTRUCTION?
 2114.2 CONCRETE BEARING LEDGE. BRICK, STONE OR OTHER
 VENEER SHALL BE SUPPORTED BY A CONCRETE-BEARING LEDGE
 AT LEAST EQUAL TO THE TOTAL THICKNESS OF THE BRICK,
 STONE OR OTHER VENEER, WHICH IS POURED INTEGRALLY WITH
 THE CONCRETE FOUNDATION. NO SUPPLEMENTAL CONCRETE
 FOUNDATION POURS WHICH WILL CREATE A HIDDEN COLD JOINT
 SHALL BE USED WITHOUT SUPPLEMENTAL TREATMENT IN THE
 FOUNDATION UNLESS THERE IS AN APPROVED PHYSICAL
 BARRIER. AN APPROVED PHYSICAL BARRIER SHALL ALSO BE
 INSTALLED FROM BELOW THE WALL SILL PLATE OR FIRST BLOCK
 COURSE HORIZONTALLY TO EMBED IN A MORTAR JOINT. IF
 MASONRY VENEER EXTENDS BELOW GRADE, A TERMITE
 PROTECTIVE TREATMENT MUST BE APPLIED TO THE CAVITY
 CREATED BETWEEN THE VENEER AND THE FOUNDATION, IN LIEU
 OF A PHYSICAL BARRIER.
  
 10) A8 DETAILS 1A-1B BOTH INDICATE A ELEVATOR SHAFT,
 A-3 INDICATES A ELEVATOR SHAFT BELOW THE ROOF LINE, S1
 & S2 BOTH INDICATE A OPEN SHAFT, PLEASE REVIEW:
 3002.1.1 OPENING PROTECTIVE???S. OPENINGS IN HOIST WAY
 ENCLOSURES SHALL BE PROTECTED AS REQUIRED IN CHAPTER 7.
 707.2 SHAFT ENCLOSURE REQUIRED. OPENINGS THROUGH A
 FLOOR/CEILING ASSEMBLY SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE COMPLYING WITH THIS SECTION.
 707.4 FIRE-RESISTANCE RATING. SHAFT ENCLOSURES SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS
 WHERE CONNECTING FOUR STORIES OR MORE, AND NOT LESS
 THAN 1 HOUR WHERE CONNECTING LESS THAN FOUR STORIES.
 THE NUMBER OF STORIES CONNECTED BY THE SHAFT ENCLOSURE
 SHALL INCLUDE ANY BASEMENTS BUT NOT ANY MEZZANINES.
 SHAFT ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING
 NOT LESS THAN THE FLOOR ASSEMBLY PENETRATED, BUT NEED
 NOT EXCEED 2 HOURS.
  
 707.5 CONTINUITY. SHAFT ENCLOSURES SHALL BE CONSTRUCTED
 AS FIRE BARRIERS IN ACCORDANCE WITH SECTION 706 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH, AND SHALL HAVE CONTINUITY IN
 ACCORDANCE WITH SECTION 706.5 FOR FIRE BARRIERS OR
 SECTION 711.4 FOR HORIZONTAL ASSEMBLIES AS APPLICABLE.
  
  
 11) SHEET A-4 THE EAST ELEVATION INDICATES THE USE OF
 SIMULATED 6 INCH HORIZONTAL LAP
 SIDING STUCCO FINISH. PLEASE PROVIDE PRODUCT APPROVAL
 FOR SIDING. COMPONENTS AND CLADDING. FL BLD CODE
 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 3
 SETS OF PRODUCT APPROVALS FOR THESHOLD BUILDINGS.
 NOTE ONLY TWO REPORTS WERE SUPPLIED FOR THE OTHER
 APPROVALS SUBMITTED!
  
 12) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  