Plan Review Notes
Plan Review Notes For Permit 10010525
Permit Number 10010525
Review Stop B
Sequence Number 1
Notes
Date Text
2010-03-04 14:21:33RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $2355.25.
 THIS INCLUDES THE BALANCE FOR THE PERMIT FEES AND FOR
 UPDATED VALUATION AND RADON FEES.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS/ELEVATIONS.
  
 B) SKYLIGHTS. NEED FLORIDA PRODUCT APPROVAL FOR 2007
 CODE VERSION.
 ***NOTE: NOA 03-1016.01 SUBMITTED EXPIRED ON 11/13/09.
  
 C) STORM SHUTTERS: NOA 04-0130.02 SUBMITTED EXPIRED ON
 02/08/09.
 ***NOTE: NEED TO PROVIDE ALSO A COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
 AND, CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND SPECIFIC ANCHOR TYPE AND
 SPACING TO BE USED.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS.
 ***NOTE: CLEARLY MARK ON MULLION PRODUCT APPROVAL
 SPECIFIC MULLION SIZE AND FASTENERS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 E) GARAGE DOOR AS SHOWN ON PLANS.
  
 F) HURRICANE STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
 ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIC CONNECTORS SPECIFIED ON
 PLANS. THIS APPLIES TO STRUCTURAL CONNECTORS ONLY.
 PROVIDE COMPLETE PRODUCT APPROVAL FOR ALL OTHERS.
  
 G) AWNING WINDOW AS SHOWN ON WINDOW SCHEDULE.
  
 H) METAL ROOF AS SHOWN ON PLANS.
  
 I) METAL RIDGE VENTILATION AS SHOWN ON PLANS.
  
 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 6- NEED TO SPECIFY ON PLANS CARBON MONOXIDE ALARMS
 INSTALLED WITHING 10 FEET OF EACH ROOM USED FOR
 SLEEPING. SEC. R313.4.
  
 7- ENERGY CALCULATIONS:
 A) PROVIDE CURRENT 2007 REVISED FORM. THE ONE SUBMITTED
 WAS FOR 2004 CODE.
 B) REVISE SQUARE FOOTAGE ON ITEM #6 TO MATCH PLANS.
  
 8- PROVIDE COMPLETE INFORMATION FOR PREFABRICATED
 FIREPLACE AS SPECIFIED ON KEY PLAN NOTES ON SHEET A-1
 AND SHOW ON PLANS WHERE IS GOING TO BE INSTALLED.
 FIREPLACE TO BE LISTED AND COMPLYING WITH UL 127.
  
 9- WINDOWS ON MASTER BEDROOM, BEDROOM #3 AND GUEST
 BEDROOM DON'T COMPLY WITH THE EGRESS REQUIREMENTS OF
 SEC. R310.1.1 AND R310.1.2 OF 2007 FLORIDA RESIDENTIAL
 CODE. REVISE SIZE AS REQUIRED.
  
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 PRIVACY WALLS SHOWN ON PLANS.
  
 11- PROVIDE ONE BATHROOM WITH A DOOR THAT HAS A LEAST
 29" CLEAR OPENING AS REQUIRED BY SEC. 11-11.1 OF FBC
 2007 AND SEC. 1005 OF 2007 EXISTING BUILDING CODE.
  
 12- PROVIDE ROOF CROSS VENTILATION AS REQUIRED BY SEC.
 R806.1. RIDGE VENTILATION AS SHOWN ON ELEVATIONS AND
 ROOF PLAN DOESN'T PROVIDE CROSS VENTILATION. NEED TO
 PROVIDE VENTILATION ON EAVES OR GABLE ENDS TO OBTAIN
 CROSS VENTILATION.
 ALSO, PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING HOW TO BUILT THE RIDGE VENTILATION ON A METAL
 ROOF AS SPECIFIED ON PLANS.
  
 13- SPECIFY ALL ROOF LIVE AND DEAD LOADS INCLUDING THE
 ATTIC LIVE LOADS AS REQUIRED BY TABLE R301.5. CLEARLY
 IDENTIFY TRUSS TOP CHORD LIVE AND DEAD LOADS AND TRUSS
 BOTTOM CHORD LIVE AND DEAD LOADS.
  
 14- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 FRAMING AT NEW SKYLIGHTS AS SPECIFIED ON KEY PLAN NOTES
 ON SHEET A-1.
  
 15- SHEET A0:
 A- REVISE CONSTRUCTION TYPE SHOWN ON PROJECT DATA
 INFORMATION. THIS BUILDING IS NOT CONSTRUCTION TYPE IV.
 SEE SEC. 602 OF 2007 FBC FOR CORRECT TYPE OF
 CONSTRUCTION.
  
 B) WALL LEGEND NOTES:
 *REVISE INSULATION R VALUE SHOWN ON THE EXTERIOR WALLS.
 COORDINATE WITH THE ENERGY CALCULATIONS.
 **COORDINATE NOTES FOR HARDIPLANK INSTALLATION.
 INFORMATION SHOWN ON NEW EXTERIOR WALL NOTE DOESN'T
 MATCH HARDIPLANK NOTES SHOWN BELOW. SEE COMMENTS ON
 PLANS.
  
 16- SHEET A-1:
 A) REVISE THE DESIGN CRITERIA. ACCORDING TO SEC.
 R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE THIS BUILDING IS LOCATED ON EXPOSURE
 "C". REVISE EXPOSURE AND THE DESIGN PRESSRUES
 ACCORDINGLY.
 ALSO, REVISE CODE SECTION. NEED TO USE FBC 2007 NOT
 2004.
  
 B) REVISE ENERGY CALCULATIONS REQUIREMENTS INFORMATION
 TO MATCH ENERGY CALCULATIONS SUBMITTED. COORDINATE WITH
 ITEM #7A ABOVE.
  
 C) REVISE WALL LEGEND INFORMATION. SEE ITEM #15B ABOVE.
  
 D) REVISE KEY PLAN NOTE #6. SEE SEC. R307 FOR MIN. SIZE
 ALLOWED.
  
 E) PROVIDE COMPLETE DETAILS AND SPECIFICATION FOR
 SCREEN ENCLOSURE AS SPECIFIED ON KEY PLAN NOTE #10.
  
 F) SPECIFY SAFETY GLAZING FOR WINDOWS LOCATED ON BOTH
 BATHROOMS. SEC. R308.4(5). AND FOR WINDOW IN THE GREAT
 ROOM NEXT TO THE GARAGE SWING DOOR. SEC. R308.4((6).
  
 G) PROVIDE COMPLETE SPECIFICATIONS FOR DOOR LEADING
 FROM THE GARAGE TO THE LAUNDRY AREA TO SHOW COMPLIANCE
 WITH SEC. R309.1.
  
 H) ENTRY DOOR DOESN'T MATCH DOOR SHOWN ON FRONT
 ELEVATION AND DOOR SPECIFIED ON DOOR SCHEDULE. REVISE
 AS REQUIRED TO MATCH. SEE ITEM #4A ABOVE.
  
 17- SHEET A-2:
 A)REVISE ROOF NOTES INFORMATION TO MATCH INFORMATION
 SHOWN ON ROOF SPECIFICATIONS ON SHEET A-3.
  
 B) REVISE ELEVATION NOTES TO MATCH PRODUCT APPROVALS
 SUBMITTED. PRODUCT APPROVALS SUBMITTED HAVE NOT IMPACT
 GLAZING.
  
 C) ELEVATIONS TO SHOW THE RIDGE VENT. COORDINATE WITH
 ITEM #4I ABOVE.
  
 D) SIZE OF POST SHOWN ON WEST AND REAR ELEVATION TO
 MATCH SIZE OF POST SHOWN ON SHEET S-2.
  
 E) WINDOW SHOWN ON FRONT BATHROOM TO MATCH WINDOW SHOWN
 ON WINDOW SCHEDULE. REVISE AS REQUIRED.
  
 18- SHEET A-3:
 A) ROOF FRAMING PLAN AT FRONT PART OF THE BUILDING IS
 INCORRECT. SEE ELEVATIONS AND REVISE AS REQUIRED.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 CONTINUOUS RIDGE VENT SHOWN ON ROOF FRAMING PLAN.
  
 19-SHEET A-4:
 A) REVISE WINDOW SCHEDULE: WINDOW TYPE IS CASEMENT OR
 SINGLE HUNG. IMPACT OR NON IMPACT (COORDINATE WITH
 PRODUCT APPROVAL SUBMITTED. REVISE FOOTNOTE. NEED TO
 SPECIFY 2007 FBC NOT 2004.
  
 B) REVISE WINDOW GENERAL NOTE #1. STOREFRONT SYSTEM
 DOESN'T APPLY TO THIS PROJECT.
  
 C) REVISE DOOR ELEVATION TYPE F. IS THIS A FRENCH DOOR
 OR SLIDING GLASS DOORS. SEE PLANS. ALSO, WHAT'S "TRIPLE
 SLIDING GLASS"?.
  
 20- SHEET S-1:
 A) PROVIDE TRUSS ANCHOR SCHEDULE TO VERIFY COMPLIANCE
 WITH SEC. R301.
  
 B) ROOF FRAMING PLAN AT FRONT PART OF THE BUILDING IS
 INCORRECT. SEE ELEVATIONS AND REVISE AS REQUIRED.
  
 21- SHEET S-2:
 A) PROVIDE ONLY THE DETAILS THAT APPLY TO THIS PROJECT.
 KEY EACH DETAIL ON THIS SHEET ON FOUNDATION AND ROOF
 FRAMING PLAN TO VERIFY PROPER INSTALLATION.
  
 B) WALL FRAMING DETAIL IS INCORRECT. IS MISSING THE
 OPENING HEADER. CLARIFY WHY THERE IS ONLY ONE 2X STUD
 SHOWN FOR THE WINDOW SILL. REVISE NUMBER OF STUDS
 REQUIRED AT JAMBS. PROVIDE COMPLETE FRAMING DETAIL FOR
 DOUBLE FRENCH DOORS. PROVIDE COMPLETE FRAMING DETAILS
 FOR INSTALLATION OF DOUBLE WINDOWS AS SHOWN ON PLANS.
 HOW ARE THE OPENINGS FRAMINGS REINFORCED TO RECEIVE THE
 STORM SHUTTERS?
  
 C) SECTION 5: REVISE ROOF SHEATHING SPECIFICATIONS TO
 MATCH SPECIFICATIONS SHOWN ON SHEET A-3. SIMPSON H6
 CONNECTOR IS NOT A TRUSS TO WALL CONNECTOR AND IT
 DOESN'T PROVIDE RESISTANCE FOR LATERAL LOADS. SEE
 SIMPSON CATALOG AND REVISE AS REQUIRED. SPECIFY HOW ARE
 THE 2X6 STUDS ATTACHED AT TOP AND BOTTOM. CLARIFY WHY
 IS THERE A CONCRETE CURB SHOWN ON THE SECTION.
  
 D) SECTION 6: FOOTING DOENS'T MATCH FOUNDATION PLAN.
 REVISE COLUMN BASE CONNECTOR (IT CAN'T BE EMBEDDED IN
 THE CONCRETE AS SHOWN ON THE DETAIL). REVISE COLUMN CAP
 CONNECTOR. SEE SIZE OF BEAM AND SIMPSON CATALOG AND
 REVISE AS REQUIRED. SPECIFY FASTENERS USED FOR THE
 HORIZONTAL BRACING. PROVIDE COMPLETE SPECIFICATIONS FOR
 GABLE END OUTLOOKERS INCLUDING FASTENERS. PROVIDE
 SPECIFICATIONS AND DETAILS FOR CONNECTION OF GABLE END
 TRUSS TO THE BEAM BELOW.
  
 22- SHEET S-3:
 A) PROVIDE ONLY THE DETAILS THAT APPLY TO THIS PROJECT
 AND KEY THEM TO THE FOUNDATION AND ROOF FRAMING PLANS.
  
 B) DESIGN LOADS: SPECIFY ALL LOADS INCLUDING THE ATTIC
 LIVE LOAD AS REQUIRED BY TABLE R301.5. REVISE EXPOSURE
 TO BE "C". SEE ITEM #16A ABOVE.
  
 C) REVISE PLYWOOD SHEATHING NOTES TO MATCH
 SPECIFICATIONS SHOWN ON SHEET A-3.
  
 23- PLEASE TAKE THE COPY OF PLANS THAT WAS REVIEWED AND
 REDLINED AND RETURN AFTER CORRECTIONS ARE DONE TO THE
 ORIGINAL DRAWINGS TO EXPEDITE THE REVIEW PROCESS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712