| Plan Review Notes For Permit 10010495 |
| Permit Number |
10010495 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-01-27 15:35:01 | ****PROVISOS**** | | | ****REVISION REQUIRED BEFORE FIRST INSPECTION - ISSUED | | | AT CONTRACTOR'S RISK**** | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. IMPACT PROTECTION REQUIRED ,FBC1609.1.4, FBC R | | | 301.2.1.2. APPLICAITON STATES "STORM PROTECTION | | | EXISTING" BUT FBC COMPLIANT SHUTTERS REQUIRED - UNABLE | | | TO LOCATE A PERMIT WHICH SHOWS COMPLIANCE FOR THIS | | | ADDRESS. PROVIDE A PERMIT NUMBER FOR SHUTTERS OR | | | PROVIDE IMPACT PROTECTION. | | | | | | SEPARATE PERMIT REQUIRED FOR SHUTTERS OR REVISE PLAN | | | FOR IMPACT WINDOWS. | | | | | | IF SHUTTERS ARE PROPOSED, PROVIDE PRODUCT APPROVALS AND | | | COMPLETE THE SAMPLE INSTALLATION SCHEDULE (AVAILABLE IN | | | THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/ | | | PDF/SCHEDULE_FOR_INSTALLATION.PDF) | | | | | | 2. REVISE PLAN TO SHOW EMERGENCY MEANS OF ESCAPE | | | FBC310.4. | | | | | | 3. PROVIDE ROOM DESIGNATIONS, SEE FBC EXISTING BUILDING | | | 604.1. INFORMATION REGARDING EXISTING WINDOWS MAY BE | | | REQUIRED. | | | | | | 4. PROVIDE MULLION PRODUCT APPROVALS FOR REVIEW OR | | | REVISE PLAN TO CLARIFY THAT NO MULLIONS ARE TO BE USED. | | | | | | | | | |
|