2010-02-03 15:29:14*****PROVISO*****
  
  
 READY FOR PERMIT ISSUANSE; PLAN SHEET FA-1 (1OF 1)
 STAMPED, INITIALED, AND DATED WITH THE FOLLOWING BELOW
 PROVISO:
  
 REVISED PLANS NEEDED (PRIOR TO OBTAINING A FIRE FINAL -
 302 ) DEPICTING THE FOLLOWING:
  
 1. THE 2002 EDITION OF NFPA 72 SHALL BE REFERENCED (NOT
 1999) IN NOTE #4.
 2. A SMOKE DETECTOR SHALL BE INSTALLED IN THE VICINITY
 OF THE FIRE ALARM ANNUNCIATOR LOCATED IN THE RECEPTION
 AREA. THE ADDITION OF THIS DEVICE SHALL BE REFLECTED IN
 THE FLOOR PLAN, RISER DIAGRAM, BATTERY CALCS, ETC.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW