| 2010-02-03 11:08:59 | REVISION DENIED |
| | REFERENCE: |
| | FBC-2007 FUEL GAS |
| | |
| | A. SEPARATE GAS PERMIT REQUIRED. THE VALUE FOR THE |
| | MATERIAL, LABOR, DESIGN, APPLIANCES ETC. SHALL BE |
| | INDICATED ON THE APPLICATION FOR PERMIT. |
| | |
| | 1. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2007 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU |
| | G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). -- THE |
| | CHAR-BROILER IS NOT INDICATED IN THE GAS CALCULATION ON |
| | SHT 3.1P. |
| | |
| | 2. SHT 3.1P GAS ISOMETRIC RISER DIAGRAM. PLEASE |
| | INDICATE THE LOCATION OF THE STEAM TABLE. |
| | |
| | 3. THE SPECIFICATION SHEET FOR THE GAS REGULATOR DOES |
| | NOT SHOW A MODEL WITH THE CAPACITY FOR ALL APPLIANCES. |
| | MAXIMUM SHOWN IS 1,000,000 FOR MODEL 325-7L. THE BTU |
| | LOAD DOWNSTREAM OF THE REGULATOR IS SHOWN AS 1, 136,000 |
| | MBTU WITHOUT ADDING THE CHAR-BROILER. PLEASE SUBMIT |
| | REGULATOR SPECIFICATION SHEETS FOR AN APPROVED |
| | REGULATOR. SECTION 410.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |