| 2010-02-08 10:12:05 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS. SEC. N1100.2 OF 2007 |
| | FLORIDA RESIDENTIAL CODE. PLEASE MAKE SURE CORRECT |
| | UPDATED FORM IS PROVIDED (SEE 2009 REVISIONS) AND MAKE |
| | SURE ALL THE INFORMATION IS COMPLETED AND FORMS ARE |
| | SIGNED AND DATED BY ALL THE REQUIRED PERSONS. |
| | |
| | 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE |
| | DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT |
| | IF FEES ARE DUE. |
| | |
| | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 4- SHEET A.01: UPDATE BUILDING INFORMATION. CURRENT |
| | CODE IS THE 2007 FLORIDA RESIDENTIAL CODE NOT 2004. AND |
| | REVISE CODE SECTION CITED ON THE WIND LOAD INFORMATION. |
| | SEC. 1606 IS NOT FOR WIND LOAD, BUT FOR DEAD LOAD. |
| | REVISE AS REQUIRED. |
| | |
| | 5- SHEET A.02: SPECIFY HOW ARE THE LEDGERS SPECIFIED ON |
| | THE SECOND FLOOR AND ROOF FRAMING PLANS ATTACHED TO THE |
| | STRUCTURE TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL |
| | CODE. SPECIFY ALL CONNECTORS. |
| | |
| | 6- SHEET A.03: |
| | A) REVISE THICKNESS OF STUCCO . MIN. 7/8" THICKNESS |
| | REQUIRED. SEE TABLE R702.1(1) OF 2007 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | B) SPECIFY 2 LAYERS OF WATER RESISTANT BARRIER AS |
| | REQUIRED BY SEC. R703.6.3 OF 2007 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | BALCONY RAILING TO SHOW COMPLIANCE WITH TABLE R301.5 |
| | AND SEC. R312 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ROOF |
| | DRAINAGE AND OVERFLOW SCUPPERS AS REQUIRED BY SECTIONS |
| | R903.4 AND R903.4.1 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | SPECIFY ALL SIZES AND SPECIFIC LOCATION. |
| | |
| | E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | BALCONY FLOOR ASSEMBLY. SPECIFY FINISH FLOORING AND |
| | COMPLETE SPECIFICATIONS TO SHOW COMPLIANCE WITH THE |
| | WIND LOADS OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | F) PROVIDE COMPLETE SPECIFICATIONS FOR ROOF SHEATHING |
| | FASTENING TO SHOW COMPLIANCEWITH SEC. R803.2.3.1 OF |
| | 2007 FLORIDA RESIDENTIAL CODE. NEED TO SPECIFY RING |
| | SHANK NAILS AND NAILING SPACING IS 4" O.C. IN ROOF ZONE |
| | 3. |
| | |
| | 7- FLAT ROOF PRODUCT APPROVAL SUBMITTED: |
| | A) MISSING THE TECHNICAL REPORT SHOWING SPECIFIC |
| | APPROVED ASSEMBLY TO BE INSTALLED AND SPECIFIC BASE |
| | SHEET FASTENING OPTION. ALSO, NEED TO PROVIDE THE |
| | SIGNED AND SEALED RAS 117 CALCULATIONS FOR THE NAIL |
| | ENHANCING AT PERIMETER AND CORNER AREAS TO MEET THE |
| | DESIGN PRESSURES OF SEC. R301 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 8- OWES PERMIT FEE BALANCE OF $1043.50. |
| | |