| 2010-01-27 10:53:32 | DENIED |
| | REFERENCE: |
| | FBC-2007 RESIDENTIAL |
| | FBC-2007 CHAPTER 1 |
| | |
| | A. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOWIN DETAIL THAT WILL CONFORM |
| | TO THE PROVISIONS OF THIS CODE AND RELEVANT LAWS, |
| | ORDINANCES, RULES AND REGULATIONS AS DETERMINED BY THE |
| | BUILDING OFFICIAL. SOME OF THE INFORMATION INDICATED IS |
| | NOT LEGIBLE AND IS IN SUCH SMALL PRINT THAT A |
| | MAGNIFYING GLASS IS REQUIRED TO SEE. SECTION 106.1.1. |
| | PLEASE MAKE ALL INFORMATION LEGIBLE. |
| | |
| | B. THE APPLICATION FOR PERMIT STATES "DESCRIBE PROJECT |
| | IN DETAIL (FAILURE TO DO SO MAY RESULT IN DELAYS)" |
| | PLEASE INDICATE ALL WORK TO BE DONE UNDER THIS PERMIT. |
| | (3 GAS LIGHTS & A REFRIGERATOR ARE INDICATED ON THE |
| | PLANS). THIS IS NOT INDICATED ON THE APPLICATION. |
| | |
| | C. PLANS SHOW THE SHUT OFF VALVES FOR TWO OF THE GAS |
| | LIGHTS UNDERGROUND. PLEASE INDICATE COMPLIANCE WITH |
| | SECTION G2420.5. |
| | |
| | D. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS |
| | PERMIT: |
| | |
| | 1. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2007 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU |
| | G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). -- THE |
| | BTU LOAD FOR ALL APPLIANCES ARE NOT LEGIBLE AND THE |
| | TOTAL BTU LOAD FOR THE SYSTEM IS NOT INDICATED. THERE |
| | IS TWO "NEW LOADS" INDICATED BUT NO TOTAL LOAD. |
| | |
| | 2. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2007 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). -- LONGEST RUN IS |
| | INDICATED AS 90 FEET, BUT THE LONGEST RUN BY ADDING THE |
| | LENGHTS INDICATED ON THE PLANS IS INDICATED AS 98 FEET. |
| | PLEASE CLARIFY. |
| | |
| | 3. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2007 FUEL |
| | GAS CODE SECTION 304 & RESIDENTIAL CODE SECTION G2407. |
| | -- FOR THE NEW REFRIGERATOR. |
| | |
| | 4. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2007 FUEL GAS CODE |
| | SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU |
| | G2429. -- FOR THE NEW REFRIGERATOR. |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE |
| | SEC. G2413.2. -- FOR THE NEW REFRIGERATOR. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |