Date Text
2010-01-27 10:53:32DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
 FBC-2007 CHAPTER 1
  
 A. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOWIN DETAIL THAT WILL CONFORM
 TO THE PROVISIONS OF THIS CODE AND RELEVANT LAWS,
 ORDINANCES, RULES AND REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL. SOME OF THE INFORMATION INDICATED IS
 NOT LEGIBLE AND IS IN SUCH SMALL PRINT THAT A
 MAGNIFYING GLASS IS REQUIRED TO SEE. SECTION 106.1.1.
 PLEASE MAKE ALL INFORMATION LEGIBLE.
  
 B. THE APPLICATION FOR PERMIT STATES "DESCRIBE PROJECT
 IN DETAIL (FAILURE TO DO SO MAY RESULT IN DELAYS)"
 PLEASE INDICATE ALL WORK TO BE DONE UNDER THIS PERMIT.
 (3 GAS LIGHTS & A REFRIGERATOR ARE INDICATED ON THE
 PLANS). THIS IS NOT INDICATED ON THE APPLICATION.
  
 C. PLANS SHOW THE SHUT OFF VALVES FOR TWO OF THE GAS
 LIGHTS UNDERGROUND. PLEASE INDICATE COMPLIANCE WITH
 SECTION G2420.5.
  
 D. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS
 PERMIT:
  
 1. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). -- THE
 BTU LOAD FOR ALL APPLIANCES ARE NOT LEGIBLE AND THE
 TOTAL BTU LOAD FOR THE SYSTEM IS NOT INDICATED. THERE
 IS TWO "NEW LOADS" INDICATED BUT NO TOTAL LOAD.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- LONGEST RUN IS
 INDICATED AS 90 FEET, BUT THE LONGEST RUN BY ADDING THE
 LENGHTS INDICATED ON THE PLANS IS INDICATED AS 98 FEET.
 PLEASE CLARIFY.
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2007 FUEL
 GAS CODE SECTION 304 & RESIDENTIAL CODE SECTION G2407.
 -- FOR THE NEW REFRIGERATOR.
  
 4. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU
 G2429. -- FOR THE NEW REFRIGERATOR.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2. -- FOR THE NEW REFRIGERATOR.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  