Plan Review Notes
Plan Review Notes For Permit 10010398
Permit Number 10010398
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-02-06 12:47:34*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. THE PROJECT SITE ADDRESS, NAME OF OWNER AND OCCUPANT
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET. A POINT OF COMPASS (DIRECTIONAL INDICATOR) IS
 RECOMMENDED TO BETTER DETAIL LAYOUT OF THE FLOOR PLAN.
  
 3. PLANS FAIL TO INDICATE THE TYPE OF OCCUPANCY,
 OCCUPANT LOADS, WHETHER BUILDING HAS FIRE SPRINKLER
 AND/OR FIRE ALARM SYSTEMS, ETC.
  
 4. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 5. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALLS AND/OR CEILING IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
 6. HOW DOES THE SCOPE OF WORK IMPACT TRAVEL DISTANCE TO
 EXITS?
  
 7. IF EQUIPPED, DOES THE SCOPE OF WORK HAVE CAUSE FOR
 THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM(S) TO BE
 REMODELED?
  
 8. ON SHEET 3, PLEASE EXPLAIN 3 CHILD RIDES THIS AREA.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722