| 2010-01-26 20:43:34 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. THE BUILDING PLAN REVIEW INDICATES THAT THERE ARE | | | REQUIRED RATED TENANT SEPARATION WALLS WHICH ARE NOT | | | SHOWN AS SUCH ON PLANS. SOME OF THE AFFECTED WALLS ARE | | | SHOWN AS BEING PENETRATED BY DUCTS WITHOUT PROTECTION. | | | COORDINATE WITH CORRECTED ARCHITECTURAL PLASN TO SHOW | | | THE DUCT PENETRATIONS OF ALL RATED WALLS PROTECTED IN | | | ACCORDANCE WITH FBC-M 607.5 AND 607.8. | | | | | | 2. M1 FLOOR PLAN SHOWS NEW EXHAUST FAN IN NEW PORTION | | | OF WOMEN'S RESTROOM. NO INFORMATION WAS PROVIDED | | | REGARDING THIS FAN. PROVIDE EQUIPMENT SCHEDULE AND SHOW | | | REQUIRED RATINGS AND CFM OF THIS FAN AS WELL AS THE CFM | | | OF THE EXISTING EXHAUST SYSTEM TO DEMONSTRATE | | | COMPLIANCE WITH FBC-EB 709.1 AND FBC-M TABLE 403.3 | | | | | | 3. THERE ARE SEVERAL OTHER RECONFIGURED SPACES IN THE | | | WORK AREA. PROVIDE SPACE-BY-SPACE VENTILATION | | | CALCULATIONS FOR ALL RECONFIGURED SPACES IN ACCORDANCE | | | WITH FBC-EB 709.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|